34
Supervisor menu
(allows system tests to be performed, and configurations to be changed. cont.
A password is required to enter this mode, see section 3.7 for details.).)
Menu Item
Values
(as shown on display)
Description
Config channel
Submenu:
Alarm L1 #1
Level 1 alarm relay
configuration
for each channel
Press the Up and
Down buttons
to cycle through
configuration for
channels #2,#3,#4
Direction
Values =
Rising
Falling
On threshold
Values = 0.1 to Range
(full scale)
Off threshold
Values =
0.1 to L1 On threshold
(rising
alarms)
L1 threshold to full
scale - 0.1 (Falling
alarms
Relay type
Values =
Latched
Energised
Indication
Values =
Visible
Hidden
Rising alarms required where there is normally no gas.
Falling alarms required where gas should normally be
present (e.g. oxygen).
Level at which the relay will activate.
Level at which the Level 1 relay will reset. Allows hysteresis
for applications such as ventilation control where the fan
should continue to run until the gas reaches a low level.
Latched means that in an alarm state, the relay will stay
active when the Accept/Reset button is pressed, and will
only reset when the alarm or fault has cleared and the
Accept/Reset key is pressed again.
Non-latched means that the relay will stay active when the
Accept/Reset key is pressed, but will reset automatically
when the alarm has cleared.
Latch-accept means that in an alarm condition the relay
will reset when the Accept/Reset button is pressed.
De-energised means that the relay coil is not energised in
a non-alarm state (normally de-energised).
Energised means that the relay coil is energised in a non-
alarm state (normally energised or ‘fail-safe’)
Visible means that an alarm will trigger the alarm LED
bar, internal sounder, external audible visual alarms, and
display the alarm message.
Hidden means that an alarm will only cause the alarm
icon
in the channel display to show. No other audible
or visual alarms will activate (used for ventilation control
applications)
A similar menu is available for Level 2 alarm relays, with the exception that the 'Off Threshold' and 'Indication' options are not
available.
Alarm L2 #1*
Direction
Threshold
Relay type
Relay drive
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
Menu system overview