10. Close the MCB
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
Theses steps must be done with external circuit breaker
switched off.
Failure to follow these instructions can result in death or
serious injury.
GARO ATLE CCS + CHAdeMO IT (3-phase P1/P2/P3+GND
3x208-240V
AC
)
The connecting point of the unit shall be protected by:
• a 80A tripolar MCB (C-curve or equivalent),
• a 30mA Type B RCD.
Wiring must be at:
• 4x16mm² minimum (flexible conductor),
• 4x25mm² maximum (rigid conductor).
GARO ATLE CCS + CHAdeMO (3-phase P1/P2/P3 + N + GND
3x400V
AC
)
The connecting point of the unit shall be protected by:
• a 50A tetrapolar MCB (C-curve or equivalent),
• a 30mA Type A or B RCD.
Wiring must be at:
• 5x16mm² minimum (flexible conductor),
• 5x25mm² maximum (rigid conductor).
GARO ATLE CCS + C AC (3-phase P1/P2/P3 + N +
GND 3x400V
AC
)
The connecting point of the unit shall be protected by:
• a 80A tetrapolar MCB (C-curve or equivalent),
• a 30mA Type B RCD.
Wiring must be at:
• 5x16mm² minimum (flexible or rigid conductor),
• 5x25mm² maximum (rigid conductor).
GARO ATLE CCS + C AC IT (3-phase P1/P2/
P3+GND 3x208-240V
AC
)
The connecting point of the unit shall be protected by:
• a 80A tripolar MCB (C-curve or equivalent),
• a 30mA Type B RCD.
Wiring must be at:
• 4x16mm² minimum (flexible conductor),
• 4x25mm² maximum (rigid conductor).
19
EN