manualshive.com logo in svg
background image

9

 DANGER: ELECTRICAL SHOCK HAZARD. Turn off power 

at the main fuse box or circuit breaker by removing the fuse or 

switching the circuit breaker to the OFF position and securing 

it. An all-pole mains switch with a contact separation of at 

least 3mm in each pole shall be incorporated in the electrical 

installation of the building.
 

 WARNING: THIS SMOKE ALARM MUST BE INSTALLED BY

QUALIFIED (LICENSED) ELECTRICIANS ONLY.
Wiring Requirements

• This smoke alarm should be installed with an AS/NZS Wiring 

Rules approved junction box. All connections must be installed 

by a qualified electrician and be in accordance with the relevant 

requirements of the AS/NZS Wiring Rules AS3000 Standards.

• The appropriate power source is 240VAC 50Hz continuous single 

phase sine wave current supplied from a non-switchable circuit 

which is not protected by a RCD.

•  

 

WARNING:

 This alarm cannot be operated from power derived 

from a square wave or modified square wave inverter. These type 

of inverters are sometimes used to supply power to the structure in 

off grid installations, such as solar or wind derived power sources. 

These power sources produce high peak voltages that will damage 

the alarm.

 

Wiring instructions for AC harness 

!

Caution! Turn off the main power to the circuit before 

wiring the alarm.

•  For alarms that are used as single station, 

DO NOT CONNECT 

THE RED WIRE TO ANYTHING

. Leave the red wire insulating cap 

in place to make certain that the red wire cannot contact any metal 

parts or the electrical box.

5. Wiring Instructions

4. Locations To Avoid

•  Avoid dead air spaces such as the peak of an 

“A”

 frame ceiling. 

“Dead 

Air”

 at the top may prevent smoke from reaching the alarm in time to 

provide early warning. Refer to 

Figure 2A

 and 

2B

.

N.B. - Smoke alarms are not to be used with detector 

guards unless the combination (alarm and guard) has been 

evaluated and found suitable for that purpose.

Содержание Ongard OG20

Страница 1: ...read this user guide which should be saved for future reference and passed on to any subsequent owner Photoelectric Smoke Alarm with Hush User Guide 240V AC 50Hz 15mA max 9V back up single or multiple...

Страница 2: ...Safety Habits 18 14 What To Do When The Alarm Sounds 19 15 Warranty Contact Details 20 Thank you for purchasing this smoke alarm It is an important part of your family s home safety plan You can trus...

Страница 3: ...type or model of smoke CO or heat alarm Hush quiets unwanted alarms for up to 9 minutes Alarm memory identifies which alarm has activated Optional use tamper resistant feature serves as a safeguard ag...

Страница 4: ...otoelectric Smoke Sensor Interconnecting Smoke and Heat Alarms Up to any combination of 17 other alarm models Compatible Models include OG10 OG20 OG20LL OG30 Operating Temperature 0 C to 40 C Operatin...

Страница 5: ...r humidifiers If a hallway or room is more than 9 1m long put alarms at both ends For maximum household protection see Figure 1C Things to Consider For Ceiling Mounting Smoke from a fire will rise to...

Страница 6: ...MENT KITCHEN HALL GARAGE MASTER BEDROOM FIRE EXTINGUISHERS SMOKE ALARMS FIRE BLANKET or Heat Alarm DINING ROOM LIVING ROOM Smoke Alarms for Minimum Protection IonisationType Smoke Alarm with Alarm Sil...

Страница 7: ...CEILING PEAK CEILING 300mm MINIMUM 600mm MINIMUM MAXIMUM SIDE WALL BEST PLACEMENT DO NOT INSTALL DO NOT INSTALL DEAD AIR NOT IN THIS AREA ANYWHERE IN THIS AREA 500mm 1000mm DEAD AIR ACCEPTABLE PLACEME...

Страница 8: ...chen alarm is desired it should have an ionisation alarm silencer feature or be a photoelectric alarm or heat alarm Do not place in the garage Mobile Home Installation For Well Insulated Mobile Homes...

Страница 9: ...RCD WARNING This alarm cannot be operated from power derived from a square wave or modified square wave inverter These type of inverters are sometimes used to supply power to the structure in off grid...

Страница 10: ...er connection will result in damage to the alarm failure to operate or electrical shock hazard Make certain alarms are wired to a continuous non switched final sub circuit Note Use approved listed Aus...

Страница 11: ...arts Do not tamper 1 Secure a suitable junction box near the position of the smoke alarm ensure the quick connect cable length is long enough to reach the junction box for termination to be made 2 Con...

Страница 12: ...Red LED Blinks once every 5 minutes and 20 seconds Mains power is present indicating normal operation Red LED Blinks once a second smoke alarm senses smoke and simultaneously sounds an audible alarm...

Страница 13: ...ush Test button for at least five 5 seconds The smoke alarm will sound 3 long beeps pause 3 longs beeps repeating for up to 10 seconds after the Hush Test button is released NOTE If smoke alarms are i...

Страница 14: ...push the button on the initiating unit Red LED flashing every second to silence the alarm for up to 10 minutes If the smoke is not too dense that unit and all interconnected units will silence After...

Страница 15: ...ke alarm sounds unwanted alarms when residents are cooking taking showers etc 1 Hire an electrician to move smoke alarm to a new location See Section 3 Installation Instructions and Section 4 Location...

Страница 16: ...en installing the battery press the battery lever down into the battery compartment and install the battery See Figure 5 Caution If the battery compartment is closed without a battery the red battery...

Страница 17: ...electric alarms Photoelectric sensing alarms may detect visible fire particles associated with slow smouldering fires sooner than ionisation alarms Home fires develop in different ways and are often u...

Страница 18: ...o test your plan before an emergency You may not be able to reach your children It is important they know what to do Current studies have shown alarms may not awaken all sleeping individuals It is the...

Страница 19: ...t open it slightly and be ready to slam it shut if heat and smoke rush in Stay close to the floor if the air is smoky Breathe shallowly through a cloth wet if possible Once outside go to your selected...

Страница 20: ...come within guarantees that cannot be excluded under the ACL 5 2 The Customer is entitled to a replacement or refund for major failure and for compensation for other reasonably foreseeable loss or da...

Страница 21: ...make a claim If a defect in the product appears within the Warranty Period you are entitled to submit a warranty claim by first visiting the Garland website address below and filling out the Return F...

Страница 22: ...This warranty is provided by Madison Technologies 149 Beaconsfield St Silverwater NSW 2128 1800 66 99 99 www garlandcables com au ABN 56 010 669 379...

Отзывы: