Leak detector Vakumatik IVF R34
-
Verification of setting values
of the leak detector
(see Section 4.1):
„Alarm On“ P
AE
and „Pump Off“
P
PA
.
If these values are incorrect then the correct values
can be set by means of the pressure switch (1.23).
-
Verification of the values "Pump On" P
PE
and
"Alarm Off" P
AA
.
These values are not set, but
rather result from the switching hysteresis of the
microswitches for alarm and/or pump control.
Specified values are reference values.
- During the functional test,
check the pump / motor
(1.21) for
abnormal
operating noises.
- In the above mentioned valve position, the leak
detector may also be checked for leak tightness.
Interstitial space inspection (leak detector disconnected via 3-way valves):
-
In the following position, the interstitial
space (12) may be checked without leak
detector, for example, for leak tightness.
Maximum pump vacuum test:
-
By connecting the measuring device to
the test valve of the suction line (1.15),
the maximum pump vacuum may be
tested using the position specified on
the left.
-
Pump must generate vacuum of
at least
-
3
00 mbar
.
Microswitch
alarm
Microswitch
pump
17