background image

3

3.0 Description

3.1 Function

Externally Heated Purge Air dryers are an economical 

and reliable way to dry compressed air to dew points 

below the freezing point of water.  Desiccant dryers lower 

the dew point of compressed air by adsorbing the water 

vapor present in the compressed air onto the surface of 

the desiccant.  Adsorption continues until equilibrium is 

reached between the partial pressure of the water vapor 

in the air and that on the surface of the desiccant.
These dryers continuously dry compressed air by using 

two identical towers, each containing a desiccant bed.  

While one tower is on-stream drying, the other tower is 

off-stream being regenerated (reactivated, i.e. dried out).  

The towers are alternated on- and off-stream so that dry 

desiccant is always in contact with the wet compressed 

air.  In this way a continuous supply of dry air downstream 

of the dryer is possible.  The switching from one tower to 

the other is controlled by a solid-state controller on either 

a fixed time basis (standard) or a demand basis (optional).

1.  Fixed Cycle Regeneration (Standard)
 

When a tower is placed off-line, it is slowly depressur-

ized and the desiccant is regenerated by driving off 

(desorbing) the water collected on its surface.  Regen-

eration is accomplished by expanding a portion of the 

dried air to atmospheric pressure.  This extremely dry 

air (purge air) is then passed through a heater.  This 

heated air flows through the desiccant bed, desorbs 

the moisture from the desiccant, and carries the de-

sorbed water out of the dryer.  The heater is turned 

off when the Heat Saver temperature sensor detects 

bed heating is complete.  The purge air continues to 

flow through the off-stream tower, cooling the desic

-

cant bed and reducing the dew point spike after tower 

change over. The tower is then repressurized to full 

line pressure.  This prevents desiccant bed movement 

and downstream pressure loss when the tower goes 

back on-line.

2.  Optional Demand Cycle Regeneration

 

(With Venturi Blower)

 

When a tower is placed off-line, it is slowly depres-

surized and the desiccant is regenerated by driving 

off (desorbing) the water collected on its surface.  Re-

generation is accomplished by expanding a portion of 

the dried air to atmospheric pressure through a venturi 

blower.  The venturi blower also draws ambient air into 

the purge line.  This combination of purge and ambient 

air is then passed through a heater.  This heated air 

flows through the desiccant bed, desorbs the moisture 

from the desiccant, and carries the desorbed water 

out of the dryer.  The heater and venturi suction valve 

are turned off when the Heat Saver temperature sen-

sor detects bed heating is complete.  Dry purge air 

continues to flow through the off-stream tower, cooling 

the desiccant bed and reducing the dew point spike 

after tower change over. The tower is then repres-

surized to full line pressure.  This prevents desiccant 

bed movement and downstream pressure loss when 

the tower goes back on-line.

4.0 Installation

4.1  System Arrangement

Install the dryer downstream of an aftercooler, separator, 

receiver, and high-efficiency oil-removing filter(s) so that 

the dryer inlet air is between 40°F (4.4°C) and 120°F 

(49°C) and contains no liquid water or oil.  Liquid water 

and/or inlet air temperatures above 100°F (37.8°C) can 

reduce drying capacity.  Contact your local distributor for 

information on proper dryer sizing at elevated inlet air 

temperatures.

Adequate filtration is required upstream of the dryer in 

order to protect the desiccant bed from liquid and solid 

contamination.  Use an Air Line Filter in systems supplied 

by a non-lubricated (oil-free) air compressor.  In systems 

supplied by a lubricated air compressor, use a High Ef-

ficiency Oil Removal Filter.  A coarser filter will be required 

upstream of the Oil Removal Filter if heavy liquid or solid 

loads are present.
To ensure downstream air purity (prevent desiccant dust 

from  traveling  downstream)  adequate  filtration  down

-

stream of the dryer is required.  A High Temperature 

Afterfilter,  typically  rated  at  450°F  (232°C)  operating 

temperature and capable of removing all desiccant fines 

1 micron and larger should be installed at the dryer outlet.

DANGER — This dryer must be fitted with a high 

efficiency coalescing filter and liquid drainer that is 

maintained properly.  Failure to do so could result 

in an in-line fire.
WARNING — The afterfilter, if installed, must be rated 

for 450°F (232°C).

4.2  Ambient Air Temperature

Locate the dryer under cover in an area where the ambi-

ent air temperature will remain between 35°F (2°C) and 

120°F (49°C).  

NOTE:  

If dryer is installed in ambients below 35°F 

(2°C), low ambient protection requiring heat tracing 

and insulation of the prefilter bowls, auto drains and/or 

sumps, and lower piping with inlet switching and purge/

repressurization valves is necessary to prevent conden-

sate from freezing.  If installing heat tracing, observe elec-

trical class code requirements for type of duty specified.  

Purge mufflers and their relief mechanisms must be kept 

clear from snow and ice buildup that could prevent proper 

discharge of compressed air.

Содержание DHP Series

Страница 1: ...3 645 4th Edition For Sales and Service 800 883 2477 Or visit Sales and Service at www gardnerdenverproducts com Contents 1 0 General Safety Information 2 2 0 Receiving Storing and Moving 2 3 0 Descri...

Страница 2: ...GER WARNING and CAUTION are used to indicate hazard seriousness levels as follows DANGER Immediate hazard which will result in severe injury or death WARNING Hazard or unsafe practice which could resu...

Страница 3: ...nt bed desorbs the moisture from the desiccant and carries the desorbed water out of the dryer The heater and venturi suction valve are turned off when the Heat Saver temperature sen sor detects bed h...

Страница 4: ...bypass piping may be installed to allow uninter rupted airflow during servicing If the downstream appli cation cannot tolerate unprocessed air for short periods install a second dryer in the bypass l...

Страница 5: ...licable from the desiccant fill port at the top of each tower Refer to Figures 3 and 3a for the fill port location CAUTION Pouring desiccant creates a fine dust safety goggles gloves and a dust mask s...

Страница 6: ...OVED FOR CLARITY P L S GAS INLET M T GAS OUTLET CONNECTION TOP VIEW R SLOT TYP 4 PLACES CENTERLINE OF CUSTOMER DRY GAS OUTLET CONNECTION H CENTERLINE OF CUSTOMER WET GAS INLET CONNECTION E MAX F G C D...

Страница 7: ...1 2 NPT 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE T 1 1 2 NPT 1 1 2 NPT 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4...

Страница 8: ...sed on the on stream cham ber and open on the regenerating chamber If triggered the dryer control system will energize the red alarm LED on the control panel and de energize the common alarm relay The...

Страница 9: ...OWER INSULATION OPTIONAL HIGH TENSION ENCLOSURE CONTROL ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REAR VIEW TOWER INLET VALVE ASME CODE TAG HOT PIPE INSULATION OPTIONAL HEATER TEMP THE...

Страница 10: ...RIGHTTOWER PRESSURE GAUGE HIGHTENSION ENCLOSURE CONTROL ENCLOSURE ASME RELIEFVALVE HOT PIPE INSULATION OPTIONAL PURGE INLET CHECK VALVE IN VXD TOWER INLET VALVE ASME CODE TAG PURGE ADJUSTING VALVE REM...

Страница 11: ...the Right Purge Check Valve down through the right tower and exits through the Right Tower Purge Ex haust Valve D The Heater is de energized when the Right Chamber temperature sensor detects desiccan...

Страница 12: ...st muffler Next Purge Supply Valve E and Left Tower Purge Exhaust Valve D are opened and the Heater is turned on The Venturi Blower Intake Shutoff Valve F is opened Purge air passes through the ventur...

Страница 13: ...FF position to en able both the dryer fault alarms and service alarms to activate the common alarm This is the default configuration Install jumper JP6 in the ON position if the common alarm is to act...

Страница 14: ...the Heated Desic cant Dryer Control a Program Mode b Setup Mode c Alarm Service Mode d Display Mode e Test Mode 2 Each Mode is described below 6 5 4 Program Mode 1 Press and hold and for 3 seconds to...

Страница 15: ...et Point for Dew Point Demand Control This feature is only active when JP3 is on DPNT CNTL SETPT XX C XXX F 1 Press to increment the setting to the desired value a Standard set point is 30 C 22 F b Th...

Страница 16: ...acknowledge the selection and move to next screen Exit Program Mode when there are no more active screens to display 6 5 5 Setup Mode 1 Press and hold for 3 seconds to enter Setup Mode 2 Setup Mode i...

Страница 17: ...le sequence is stopped a local alarm is displayed and the common alarm relay is de energized c Alarm Left Tower Regenerating High Pressure will be displayed if regenerating the left tower Alarm Right...

Страница 18: ...TWR DEW POINT UNDER RANGE ALARM RIGHT TWR DEW POINT OVER RANGE ALARM LEFT TOWER TEMP UNDER RANGE ALARM LEFT TOWER TEMP OVER RANGE ALARM RIGHT TWR TEMP OVER RANGE ALARM RIGHT TWR TEMP UNDER RANGE ALARM...

Страница 19: ...Energy Management Control the dryer sequence continues but bypasses the HOLD step and proceeds to tower switchover after 4 hours of drying iii This alarm is self clearing at which time the alarm LED s...

Страница 20: ...d to the controller whether the controller is switched on or off When a service time interval expires see also 14 d below the controller operates as follows a The service LED blinks and the appropriat...

Страница 21: ...reminder filters HOURS TO SERVICE FILTERS XXXX Service reminder desiccant HOURS TO SERVICE DESICCANT XXXX Service reminder valves HOURS TO SERVICE VALVES XXXX Outlet Dew Point Displayed only if JP3 i...

Страница 22: ...en Open Open then Closed 2PS Closed Closed then Open Open Open Open Open then Closed Closed Closed Closed Closed Closed Closed LT drying solenoid B On On On On On On Off Off Off Off Off Off LT depress...

Страница 23: ...essurized Exception If switching failure is disabled then pressure condition is ignored Screen 7 Step 7 TEST7 RT DRYING RT XX C XXX F Screen 8 Step 8 TEST8 DEPR LT LT XX C XXX F NOTE Sequence step wil...

Страница 24: ...s dust in the muffler cartridges This sometimes occurs after start up due to dusting of the desiccant during tower filling and dryer transport If the tower pressure gauge of the off stream tower rises...

Страница 25: ...valves will react as follows 1 For models with poppet style inlet valves models 300 600 both inlet valves will open Both towers will repressurize 2 For models with butterfly inlet valves models 750 3...

Страница 26: ...on of the inlet temperature F xxx ASCII representation of the heater temperature F xxx ASCII representation of the left bed temperature F xxx ASCII representation of the right bed temperature F xxx AS...

Страница 27: ...27 Example If jumper 8 5 and 1 are installed a value of 128 16 1 145 is returned To decode the algorithm If number 128 jumper 8 on number number 128 If number 64 jumper on number number 64 etc...

Страница 28: ...desiccant Layer 1 must be installed first at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed e Utilizing an appropriate sized funnel f...

Страница 29: ...placement may be required sooner if pressure drop across the cartridge prevents the Dew Point Analyzer from operating properly WARNING The Dew Point Analyzer filter housing is a pressure containing de...

Страница 30: ...failed to close 6 Drying tower Depressurization Valve failed to close 7 Regenerating tower Outlet Check Valve failed to close 1 Check compressor supplying dryer 2 Check equipment downstream of dryer...

Страница 31: ...rge Exhaust Valve failed to close 3 Regenerating tower Depressurization Valve failed to close 1 Check pressure switch operation using tower pressure gauge for comparison Replace switch if defective 2a...

Страница 32: ...Left Tower or Right Tower 1 Desiccant bed overloaded 2 Poor regeneration 3 Moisture probe damaged or defective 4 Loss of desiccant drying capacity 1 Check inlet air flow rate temperature and pressure...

Страница 33: ...PRESSURE PSIG PURGE SET PRESSURE PSIG MODEL ORIFICE DIA IN 300 7 32 34 58 400 1 4 34 37 500 9 32 34 47 600 5 16 34 38 750 11 32 34 46 900 3 8 34 58 1050 13 32 34 25 1300 29 64 34 38 1500 31 64 34 50...

Страница 34: ...PHIC SYMBOLS FOR FLUID POWER DIAGRAMS SOLENOID VALVES A C E F ARE SHOWN DE ENERGIZED AS SHOWN FLOW DIRECTION IS INDICATES OPTION 3 2 1 PILOT GAS LINE RIGHT CHAMBER REGEN LEFT CHAMBER DRYING NOTES 4 SO...

Страница 35: ...INLET VALVE V1 LEFT V2 RIGHT 2 PURGE EXHAUST VALVE V3 LEFT V4 RIGHT 3 PURGE CHECK VALVE V5 LEFT V6 RIGHT 4 OUTLET CHECK VALVE V7 LEFT V8 RIGHT 6 PURGE HEATER WITH INSULATION 7 HEATER TEMPERATURE THER...

Страница 36: ...S SOLENOID VALVES A C E F ARE SHOWN DE ENERGIZED AS SHOWN FLOW DIRECTION IS INDICATES OPTION 3 2 1 PILOT GAS LINE RIGHT CHAMBER REGEN LEFT CHAMBER DRYING NOTES 4 SOL H RTD4 HS1 SOL D RTD 1 V3 V4 SOL C...

Страница 37: ...E P R E S S U R IZ A T IO N R E P R E S S U R IZ A T IO N S W E E P 55 3 H O L D 2 176 55 S W E E P 3 L O S S O F P O W E R H O L D FIXED CYCLE TIMING LEFT CHAMBER DRYING RIGHT CHAMBER REGEN RIGHT CH...

Страница 38: ...ONLY 3 G 1 26 RED GREEN BROWN BLACK EXTERNALLY LOCATED OPTION 102 101 120VAC 101 110 RED BLACK GREEN 21 ADD FOR MODELS 900 3200 ONLY TB5 90 91 ORANGE 32 33 34 35 90 91 EXTERNALLY LOCATED DEWPOINT TRAN...

Страница 39: ...1 26 RED GREEN BROWN BLACK EXTERNALLY LOCATED OPTION 102 101 120VAC 101 110 RED BLACK GREEN 21 ADD FOR MODELS 900 3200 ONLY TB5 90 91 ORANGE 32 33 34 35 90 91 EXTERNALLY LOCATED DEWPOINT TRANSMITTER 4...

Страница 40: ...URE CONTROL ENCLOSURE 22 46 6 4 11 15 17 14 2 27 58 11 23 AIR OUT LEFT CHAMBER RIGHT CHAMBER AIR IN 1 9 45 44 3 10 42 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW 7 8 Gardner De...

Страница 41: ...4237 G3154237 G3154237 G3154237 1 17 Exhaust Muffler G3204478 G3130773 G3130773 G3072056 2 Exhaust Muffler Replacement Core G3126761 G3121200 G3121200 G3094580 1 2 22 Purge Adjusting Valve G1196180 G1...

Страница 42: ...LOSURE 45 46 25 23 11 5 27 2 54 15 14 11 4 10 44 7 8 22 3 42 9 1 1A 17A 6 MODEL 750 17 2 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW AIR IN AIR OUT LEFT CHAMBER RIGHT CHAMBER I...

Страница 43: ...G3072056 N A N A N A N A N A 2 Exhaust Muffler Replacement Core G3094580 N A N A N A N A N A 2 2 17a Depress Muffler N A G3071392 G3071392 G3071392 G3090655 G3090655 2 Depress Muffler Replacement Cor...

Страница 44: ...CONTROL ENCLOSURE 8 7 25 22 46 6 10 4 11 15 54 2 14 5 27 11 23 1 1A 3 9 42 45 44 17A 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW AIR OUT LEFT CHAMBER RIGHT CHAMBER AIR IN Gard...

Страница 45: ...Air Filter Element G3158592 G3158592 G3158592 1 15 Pilot Air Pressure Regulator G3154237 G3154237 G3154237 1 17a Depress Muffler G3130773 G3130773 G3130773 2 Depress Muffler Replacement Core G3121200...

Страница 46: ......

Страница 47: ......

Страница 48: ...uiring routine replacement are not warranted Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF AL...

Отзывы: