13-18-612 Page 22
3-4
Quick Start Guide
Operation of the AirSmart controller is easy. Simply select a Target Pressure and then press the Run
button to start the compressor, no other settings are required. The Target Pressure comes
preset from the factory at pressure as ordered. The Unload Pressure is preset to 10 psi higher. If a
different pressure setting is desired, the following steps can be used as a guide.
Setting the Target Pressure
The Target Pressure setting is used to set the operating point of the compressor. To make any
adjustments in the operation of the compressor, the machine must be stopped and in the Ready
mode. Stop the compressor by pressing the Stop/Reset
button. The front panel display
should read “READY” on line 3.
Next, press the Enter
button to access the Adjustment Menu tree
Since the Target Pressure setting is under the Operation Adjustment menu, press Enter
again to access that sub-menu
The Target Pressure is the second item in the Operation Adjustment sub-menu so press the
Down
button to navigate to the Target Pressure setting.
To change the Target Pressure, press the Enter
button to edit the value.
A flashing cursor will appear covering the least significant digit in the Target Pressure value, use
the Plus
and Minus
buttons to change its value. Use the Right
and Left
0 PSI 75°F
10 HRS AUTOMATIC
READY
NO SERVICE ADVISORY
ADJUSTMENT MENU
OPERATION ADJUSTMENT
(SELECT SUB MENU)
OPERATION ADJUSTMENT
LANGUAGE-LANGUAGE
ENGLISH (US)
(SELECT PARAMETER)
OPERATION ADJUSTMENT
TARGET PRESSURE
100 PSI
(EDIT PARAMETER)
OPERATION ADJUSTMENT
TARGET PRESSURE
100 PSI
(SELECT PARAMETER)
Содержание AirSmart VS80-110B
Страница 31: ...13 18 612 Page 30 4 5 Figure 4 2 PIPING AND INSTRUMENTATION ILLUSTRATION 300CGE797 A Ref Drawing...
Страница 33: ...13 18 612 Page 32 4 7 300CGE546 04 Ref Drawing Page 2 of 4...
Страница 34: ...13 18 612 Page 33 4 8 300CGE546 04 Ref Drawing Page 3 of 4...
Страница 35: ...13 18 612 Page 34 4 9 300CGE546 04 Ref Drawing Page 4 of 4...
Страница 37: ...13 18 612 Page 36 4 11 301CGE546 B Ref Drawing Page 2 of 4...
Страница 38: ...13 18 612 Page 37 4 12 301CGE546 B Ref Drawing Page 3 of 4...
Страница 39: ...13 18 612 Page 38 4 13 301CGE546 B Ref Drawing Page 4 of 4...
Страница 41: ...13 18 612 Page 40 4 15 302CGE546 05 Ref Drawing Page 2 of 4...
Страница 42: ...13 18 612 Page 41 4 16 302CGE546 05 Ref Drawing Page 3 of 4...
Страница 43: ...13 18 612 Page 42 4 17 302CGE546 05 Ref Drawing Page 4 of 4...
Страница 45: ...13 18 612 Page 44 4 19 303CGE546 B Ref Drawing Page 2 of 4...
Страница 46: ...13 18 612 Page 45 4 20 303CGE546 B Ref Drawing Page 3 of 4...
Страница 47: ...13 18 612 Page 46 4 21 303CGE546 B Ref Drawing Page 4 of 4...
Страница 70: ...13 18 612 Page 69 9 2 Figure 9 1 MINIMUM DISCHARGE PRESSURE CHECK VALVE...
Страница 86: ...NOTES...
Страница 87: ...NOTES...