13-17-615 Page 16
Figure 2-3 - System Pressure Address
NOTE: Steps 9 &10 are only necessary for kit 314ETK6028 for packages with 3 pressure
transducers. If using kit 313ETK6028 continue to step 11.
9. Scroll down to
Separator Pressure
and press enter to bring up the onscreen number pad. Using
the number pad enter
0
as the
Separator Pressure
address and press enter. The numbers
should turn GREEN to show they have been accepted. If an invalid value has been entered the
numbers will turn RED.
10. Next, scroll down to the
Plant Pressure
and press enter to bring up the onscreen number pad.
Using the number pad enter
18
as the
Plant Pressure
address and press enter. The numbers
should turn GREEN to show they have been accepted. If an invalid value has been entered the
numbers will turn RED.
11. Exit to the main menu using the back soft key.
12. While at the home screen press the stop button
to reload I/O Mapping to apply the new
configuration.
Now that the pressure transducer is mapped the AirSmart G2 Controller needs to be programmed for
sequencing operation. The operating mode must be changed to
Sequenced
under
Operational Settings
for the controller to listen for communication on the sequencing interface.
1. Press the menu button
soft key while at the home screen to enter the settings menu.
2. If the distributor level password has not been entered, press the unlock button
soft key and
enter a distributor level or higher password using the onscreen number pad.
3. Navigate to and select
Operational Settings
.
4. Navigate to and select
Operating Mode
.
5. Under the
Operating Mode
menu navigate to and select
Sequenced
and press enter.