TR-RT LED lighting controllers - User Manual
or microseconds. For currents, ‘A’ or ‘ma’ can be added to indicate amps
or milliamps. The default unit is amps.
Note:
parameters are in ‘USA/UK’ format so that a half is written ‘0.5’ not
‘0,5’. For example:
Parameter
Meaning
0.1
0.1 millisecond
200μs
200 microseconds
0.1s
0.1seconds
100ma
100mA
2.45A
2.45A
2.3
2300mA or 2.3A
The command codes and their meaning are described in
. The upper case commands are shown, followed by
lower case letters denoting the numeric argument.
11.3.1 General commands
Any changes you make using Ethernet commands are not saved
permanently until you send the
AW
command.
Report the version of firmware running in the TR-RT
This command returns the firmware version. For example:
VR
returns
TR-RT420-20 (HW02) V031
Set the rating of a light
This command sets the current or voltage rating for a light. If a
current rating is being set, then the voltage rating value should be 0.
VLo,v,c
Where:
o
= output channel (1 to 2 or 4, depending on model)
v
= voltage rating (0 or 12 to 36)
c
= current rating (0 or 10mA to 3A)
Set continuous mode
The output is set to continuous mode at a percentage of full
brightness.
RSc,s
Where:
c
= output channel (1 to 2 or 4, depending on model)
s
= setting in percent (s = 0 to 100)
—
31
—