background image

9

Control By Event

To program control by event functions between nodes, exit the SmartNet program
and at the SmartNet prompt type: TOKENSET.EXE. This will start the program
that allows the user to assign alarms from any node on the system to activate any
output on any other node of the system. This file can be programmed to activate on
individual alarms or any alarm from a circuit in a node. The user enters a node
number, a circuit number, and device number. By typing ALL in the device category
the program will respond to any alarm from that circuit. Outputs are programmed 1
to 254  These outputs correspond to input circuits 57 and 58 in the target node with
126 devices per circuit respectively (circuit 57 is 1-126, circuit 58 is 129-254).

Example: An alarm from node #1, circuit #4, device #12, that activates node #2,
circuit # 57, device #1 would look like this:

Control by event will be programmed using the CBE programming in the individual
nodes. In the above example the user would program node #2, circuit #57, device #1
to a specific input group that would activate and output group corresponding to the
input from node #1.

Tokenset.txt

Type the numbers in the selected areas. Type ALL (capital letters) in the device area
for every “Fire Alarm” device on a circuit to generate a token. Arrow keys are used
to move up and down through selected areas. Plus and minus keys are used to add or
delete in selected areas (confirmation window will appear if delete id selected).
LIST will print out a list of the tokenset programming.
OK will save and exit the program.
CANCEL will exit without saving.

Note: 

The TOKENSET.EXE file can be run on another computer and the resulting

TOKENSET.TXT file can be copied to the SMARTNET directory of the network
computer.

THIS ALARM --------------------------------------------------------- SENDS THIS TOKEN

     NODE

       NODE

 CIRCUIT

     TOKEN

   DEVICE

 1

 <

 >

 +

 -

 12

 <

 >

 +

 -

 4

 <

 >

 +

 -

 2

 <

 >

 +

 -

 1

 <

 >

 +

 -

   LIST

    OK

 CANCEL

Technical Manuals Online! - http://www.tech-man.com

Содержание IF600

Страница 1: ...F600 SMARTNET FIRE ALARM SYSTEM NETWORK Installation Operation Manual The Gamewell Company 60 Pleasant Street Part No 71646 Ashland MA 01721 Issue 8 21 98 Technical Manuals Online http www tech man co...

Страница 2: ...Gamewell Company Such information and technical drawings may not be copied or reproduced in any manner or disclosed to organizations that might be competitive to Gamewell without the express prior wri...

Страница 3: ...ystem performance and minimize risk of damage to the equipment we suggest using all Gamewell Components 4 There is no substitute for proper maintenance and testing of this or any life safety product G...

Страница 4: ...Password window 5 CONTROLS 5 General 5 Control Buttons 5 Acknowledging 5 Signal Silence 5 Resetting 6 Multiple Alarms and or Troubles 6 Confirming 6 Deleting 6 Scroll control 6 Trouble 6 Alarm 6 PROG...

Страница 5: ...ssigning Node Names 11 Node Name 11 Access Level Three 11 Sensitivity Download 11 APPENDIX A 12 Communication Settings 12 APPENDIX B 13 SmartNet Data stream information 13 APPENDIX C 24 Wiring Diagram...

Страница 6: ...A M1095 in appendix B Four LED s are provided to indicate the status of the communications See A M1095 in appendix B for details MSTR FIB Module The MSTR FIB modules provides the same features as the...

Страница 7: ...rge protection device or U P S un interuptable power supply s Note Consult PC manual for power requirements Wire Connections The network interconnecting cable should consist of a shielded 4 conductor...

Страница 8: ...dding or deleting nodes will be done through a separate maintenance program Figure 1 VISUAL STATUS DISPLAY Gamewell SmartNet 6NMXXXXXX Current Date and Time Suprervisory Alarms 0 Trouble 0 Alarms 0 Si...

Страница 9: ...ondition When an abnormal condition alarm supervisory or trouble occurs the operator is prompted to confirm and acknowledge the condition To confirm the condition highlight the abnormal condition with...

Страница 10: ...he associated action can be taken Acknowledge Acknowledges alarms and troubles and silences the panel audible Reset Resets alarm and trouble conditions Signal Silence Turns on and off the local indica...

Страница 11: ...rmed Password required Deleting When a condition shown in a status window has been corrected or eliminated the item in the window will be marked with an arrow on the left side and the delete button wi...

Страница 12: ...o SmartNet directory in the computer 2 Put disk into floppy drive type A return type INSTALL return 3 Follow directions on the screen 4 Power down and power up the computer to start the network Servic...

Страница 13: ...the system will output NODE 0 SYSTEM NORMAL every 2 minutes If NO is selected the heartbeat information is not transmitted Assigning various levels of access to these functions can be accomplished by...

Страница 14: ...ould look like this Control by event will be programmed using the CBE programming in the individual nodes In the above example the user would program node 2 circuit 57 device 1 to a specific input gro...

Страница 15: ...ant to transfer from by clicking the mouse on the node number in the node window Press the enter key to get the password prompt from that panel Select the display option of the system menu Select eith...

Страница 16: ...6 Prefix 7 Node 0 Exit 7 Current Node Name Is Enter New Node Name 60 Pleasant St Do You Want To Clear Node Name Y N N New Node Name Is 60 Pleasant St Press Any Key To Continue Node Name The Node name...

Страница 17: ...3 02F8 COM 2 02D8 COM 2 02E8 S1 3 Default COM 4 02C8 COM 4 Indicates switch closed IRQ SW 4 SW 5 SW 6 SW 7 SW 8 2 3 4 5 S1 Default 7 S2 Default Indicates switch closed s Note S1 is used to select the...

Страница 18: ...detect a device connected to the comm port These parameters can be changed in the PRIV INI file COM1 Transmission speed 9600 Baud Bits 8 Parity None Stop bits 1 The message text output will be in the...

Страница 19: ...us section will display the condition of the reporting Node The word Status will be followed by either Alarm Fault Normal Bus Comm or Control NODE NUMBER STATUS NUMBER OF ALARMS DATE TIME ACTION CIRCU...

Страница 20: ...System power up Begin System I O Assignments System programming itself Programming Mode Entered Ignore any data from this point until Exit Program Mode is received Exit Program Mode See Programming Mo...

Страница 21: ...hort in the secondary class A cable Printer fault Node 0 Master printer error Alarm Tested in Message during walk test AtoD Malfunction System Problem LCD Malfunction System Problem System In Walk Tes...

Страница 22: ...m Unknown Event System Problem CIRCUIT NUMBER The circuit number appears where the word CKT is followed by the circuit number 1 131 NODE NUMBER STATUS NUMBER OF ALARMS DATE TIME ACTION CIRCUIT NUMBER...

Страница 23: ...F USER DEFINABLE TEXT UP TO 40 CHARACTERS OF USER DEFINABLE TEXT The user definable text is used to describe the location of the circuit or device and is usually job specific Care should be taken when...

Страница 24: ...ommencing System Reset System reset button pressed Status FAULT 08 31 95 16 21 Ver Seq in Ckt I Fire Alarm 1 st Floor Room Number I Fire Alarm Verification sequence started not an actual alarm at this...

Страница 25: ...cing System Reset Status NORMAL 08 31 95 16 24 System Idle Status ALARM 08 31 95 16 24 Supv Alarm in Ckt 3 Alarm Tamper Switch 1st Floor Supervisory Alarm Circuit 3 Status NORMAL 08 31 95 16 24 I O Re...

Страница 26: ...vated Signals reactivated Status RESET 08 31 95 16 26 Commencing System Reset Status ALARM 08 31 95 16 26 Supv Alarm in Ckt 26 Dev 14 Sprinkler Tamper Switch I st Floor Room Number I Supervisory Alarm...

Страница 27: ...28 System Idle NODE 0 Status FAULT 07 09 1998 10 28 04 0 10 28 04 AM 7 9 98 Printer Fault Printer error at the Master NODE 0 Status CONFIRMED 07 09 1998 10 28 25 0 10 28 04 AM 7 9 98 Printer Fault USE...

Страница 28: ...8 10 29 AM Secondary Bus Error Break or short in the Seconday cable was detected at the Master Node 2 Status BUS 7 9 98 10 31 27 AM Primary Bus Error Break or short in primary cable between Node 1 and...

Страница 29: ...em w MSTR FIB SIM 422 FIB D W1164 3 Network System w MSTR FIB SIM FIB D W1164 4 Network System using CP 864SN Line Protectors A W538 Cable Connection for MSTR 422 A M1094 1 AC Connections for SN600 PC...

Отзывы: