Section 4: Programming/Operation Instructions
4.1 LED Indicators
Figure 4.1.1 illustrates the LED Indicators panel. Table 4.1.1 lists the LED indicators..
Figure 4.1.1 LED Indicators Panel
Designation Description
Comments
AC Power On
(green)
Lights to indicate presence of 120/240 VAC input.
Alarm
(red)
Lights when system is in alarm, flashes until alarm is
acknowledged.
Supervisory
(yellow) Lights
when
supervisory condition exists, flashes until
trouble acknowledge is performed.
System Trouble
(yellow)
Lights to indicate trouble condition, flashes until trouble
is acknowledged.
Power Fault
(yellow)
Lights during a LOW or NO Battery condition.
Ground Fault
(yellow)
Lights to indicate a ground on a field conductor
NAC 1 Silenced
(yellow)
Lights to indicate that NAC Circuit has been silenced via
the Signal Silence Switch
(if programmed as silenceable).
NAC 2 Silenced
(yellow)
Lights to indicate that NAC Circuit has been silenced via
the Signal Silence Switch
(if programmed as silenceable).
System
Silenced
(yellow)
Lights when a System Silence has been performed.
Flashes when disabled.
Table 4.1.1 LED Indicators