Basic System Module (BSM)
Signaling Line Circuits
Figure 3.4.3 illustrates the typical releasing circuit wiring for the 7100 Series control panel.
Figure 3.4.3 Typical Releasing Circuit Wiring
NOTE:
This installation has been approved by Factory Mutual only.
(+)
4
5
(-)
(-)
1
(-)
3
(+)
2
(+)
(-)
AOM
(+)
8
6
7
9
SLC
TERMINALS
-
+
POWER SUPPLY
TERMINALS
7
AMM-2F
5
4
5
9
0
6
8
3
2
1
9
8
7
6
4
0
1
2
3
MONITOR MODULE
CONNECTED TO SLC
NOTICE:
SOLENOID
SEE ADDENDUM, P/N 9000-0427 FOR A
LIST OF APPROVED RELEASING
DEVICES
MAX. 20 FT. 18AWG (MIN.)
IN RIGID CONDUIT
SUPERVISED
NON POWER-LIMITED
USE ONLY THE LISTED AND APPROVED METHODS AND DEVICES REFERENCED IN THIS MANUAL TO ACTUATE
A FIRE EXTINGUISHING SYSTEM. REFER TO THE INSTALLATION MANUAL FOR THE PROPER USE OF THE
SYSTEM IN A PARTICULAR APPLICATION. EXTINGUISHING AGENTS THAT SUPPRESS FIRES BY OXYGEN
DILUTION SUCH AS CARBON DIOXIDE AND VARIOUS INERT GASES SHALL BE PROVIDED WITH LISTED,
APPROVED, MECHANICALLY OPERATED TIME DELAYS AND STOP VALVES TO CONTROL THE DISCHARGE
TO A PROTECTED AREA.
WIRING FROM THE POWER SUPPLY TO THE AOM MODULE NOT TO EXCEED 2 OHMS. POWER FOR ACTUATING
RELEASE SOLENOIDS MUST BE OBTAINED FROM THE NON-RESETTABLE POWER TERMINALS OF THE SPSU-V,
BSM-2, THE GAMEWELL-FCI FC-72 PS-6 OR APS-6, OR ANY 24 VDC REGULATED POWER SUPPLY LISTED FOR
FIRE SIGNALING SYSTEMS PER UL 864 AND/OR 1481 AND FACTORY MUTUAL SYSTEM APPROVED.
CONNECTIONS TO THE SOLENOID WIRE LEADS AND REL47K SUPERVISORY DEVICE MUST BE VIA LISTED
TERMINAL BLOCKS IN A STANDARD LISTED ELECTRICAL BOX CLOSE-NIPPLED TO THE SOLENOID.
7
5
4
9
0
6
8
3
2
1
5
9
8
7
6
4
0
1
2
3
Notifier P/N REL47K
END-OF-LINE RESISTOR
P/N 151-00014
SUPERVISORY RELAY
GAMEWELL-FCI P/N 119-90015
TENS
DIGITS
ONES
DIGIT
MODULE ADDRESS SWITCHES
ASSIGN EACH MODULE A UNIQUE SLC ADDRESS
VIO
YE
L
The 7100 is Factory Mutual Approved for Releasing Device Service.