Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
36
Figure 30: Ground studs on inside of batt. cabinet roof
Figure 31: Ground bus bar at base of UPS rear
Table 5: Key to Figure 30 and Figure 31 above
I
TEM
#
G
ROUND NAME
I
NSTRUCTIONS
3
B
ATTERY
CABINET
GROUND
CONNECTION
Connect a cable to either of the ground studs (10 mm diam.) in the roof of
the battery cabinet Figure 30 and connect the other end of the cable to the
ground bus bar at the bottom rear of the UPS.
Use a cable of 3/0 AWG, and a tightening torque of 250 pound-inches (28.2
N-m) on both ends of the cable.
Recommended cable shoe: mfr. Panduit, cat.no. S3/0-76R-5.
4
UPS
GROUND
BUS BAR
On the UPS's ground bus bar (located at the bottom rear of the UPS)
connect the ground cable from the battery cabinet to the ground bolt (10 mm
diam.) indicated by item 4 in Figure 31. Open the ground bolt, slip on the
cable shoe, and reclose the ground bolt.
Recommended cable shoe: mfr. Panduit, cat.no. S3/0-76R-5.