Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
109
2.
Select
ENABLE SHUTDOWN by long AC FAIL (Off)
and press
Ent
to toggle enable/disable:
[Main Menu > SETUP > (password) > Battery > Enable/Dis Options]
1> ENABLE SHUTDOWN by long AC FAIL (Off)
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable
1> DISABLE SHUTDOWN by long AC FAIL(On )
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable
Figure 203: Enable/Disable shutdown by long AC failure
Note
: Option 1 in Figure 203 allows the user to enforce shutdown after a given length of input
ac failure, even when the batteries are still fully charged.
Item 2,
ENABLE Current Sensors (Off)
and item 3,
ENABLE BATT Temperature sensor (Off)
in
the screens shown in Figure 203 toggle between enable/disable in the same manner as item 1,
ENABLE SHUTDOWN by long AC FAIL (Off)
.