Centric Installation Guide, rel. 4.7
82
2
In chapter 7 there were instructions for installing the LCD panel. These instructions were deleted, as the
LCD panel now comes to the customer fully installed.
2018-09-05
– Doc. vsn. 3.7.
1
In Technical Specs, updated Overload Withstand information, as per as per A.Z., J.G., S.BZ., S.M
2018-12-26, doc version 3.8
1
Further updates to logo, page headers, contact info.
2019-03-10, doc. vsn. 3.9
1
On page "ii" a warning was added stating that "an internal maintenance bypass switch is incompatible with
this UPS in a parallel configuration. If a parallel configuration is required, the maintenance bypass switch
must be external to the UPSs."
2019-08-4, doc. vsn. 4.0
1
Full document parallel system procedure
2019-12-9, doc. vsn. 4.2
2020-01-01, doc. vsn. 4.3
1
Maintenance bypass warnings
2
New spec's
2020-01-23, doc. vsn. 4.4
1
TN-XX and IT warning
2
Battery breaker warning
2020-01-23, doc. vsn. 4.5
1
LVD update
2020-03-25, doc. vsn. 4.6
1
Icw rating
2
Removal of data sheet
2020-04-05, doc. vsn. 4.7
1
Rearranged ac input terminals for easy single feed on cn50