Parallel communication
When two or more Centric units are operated in parallel, parallel communication must take place between
them in a "ring" arrangement. This is accomplished by the use of Gamatronic-provided cables with D-15
connectors on each end. Parallel communication keeps the parallel units synchronized with each nother,
and is used to pass commands and status information between units.
Each Centric UPS has two D-15 parallel communication connection terminals.
Figure 41shows how to connect the parallel communication terminals for parallel operation of two and three
Centric units. Be aware that when connecting one UPS to the other, it does not matter which of the two D15
terminals you use on each UPS.
Figure 41: Parallel comm. connections (cable cat.no. GPIN15350)