WC66000122 - Rev 03
It is strictly forbidden to reproduce this manual, even partially
15
SACBUS CONNECTION
Set micro-switch 1 of SW2 on OFF for the MASTER UNIT, and on
ON for the SLAVE UNITS.
NOTES
• Only one unit can be set as the MASTER.
• When a unit is set as SLAVE, the parameters coming from its remote
controller will be ignored and the unit will reproduce the exact same
settings as the MASTER UNIT remote controller.
• Use a shielded bipolar electric cable with a 0.5mm
2
section. The cable
must not be any lighter than H05VVC4V5-K (according to IEC 20-20
CENELEC HD21).
• Max. length (total cable sum): 250m
Min. length between units: 0.5m
• If there is a power outage, the units will start back up again with the last
settings on the MASTER UNIT remote controller.
MASTER UNIT / SLAVE UNIT SETTING