Electronic control setting
Mycomfort
• Modulating fan
• P09 = 1
• P10 = 1
EVO
• Modulating fan
• Config. DOUT > Operating mode
• Digital output logic > NC
Water cassette supports external control function through an external command.
In order to drive terminal control needs a 0-10V analog output for fan speed modulating and a free potential contact for operating mode setting (Sum/
Win)
Control regulating logics will keep water probes, air probes and condensate discharge pump under control. This function allows to manage the cassette
through Galletti EVO and MyComfort Large controls.
Please follow the diagram for a correct wiring.
Data cables must not be close to electromagnetic interference
sources.