The following pages provide an illustration of all possible Micronet configurations, along with the respective
dipswitch sequences, any special operating features and specific notes.
Choose the configuration that is best suited to your installation’s requirements and apply it as described.
Controller installation configuration
Depending on where you plan to install the MICRONET panel, you must first set dipswitch 8 as shown below
Position of dipswitch 8 for configuration 5:
1 2 3 4 5 6 7
8
On/Off On/Off On/Off On/Off On/Off On/Off On/Off
On/Off
On
Off
Function configuration
The Micronet controller can be configured in different ways: among the various functions available, you can enable
the ones you wish specifically to implement. The various configurations are set by positioning the dipswitches on
the electronic card accordingly.
C1 (Standard): two pipes
System characteristics
Number of pipes:
2
Valve:
NO
Heating element:
NO
List of functions activated in configuration 1:
•
Room thermostat with control over air temperature
•
Local manual Cooling/Heating changeover
•
On/ off according to water temperature
•
Timing (not available for wall-mounted Micronet controller)
Position of dipswitches for configuration 1:
1 2 3 4 5 6 7
Off Off Off Off Off Off Off
On
Off
ON = installation on wall
OFF = installation on unit