FC66002179 – Rev.00
7
Instructions for installing Micronet
Important
: The Micronet controller has been designed for fan coil units belonging to the FLAT series; should you
wish to use it to control other types of units, you must make sure that the operating limits are complied with (see
relevant section herein).
The MICRONET controller incorporates 2 sets of
dipswitches for configuring the control functions and
assigning the controller a network address.
FUNCTION DIPSWITCHES
Group of 8 dipswitches to be configured as follows:
The dipswitches from 1 to 7 may be used to configure
the controller functions as illustrated in the tables in the
“Function Configuration” section.
The position of dipswitch 8 identifies the type of
installation of the control panel (ON = wall-mounted,
0FF = on unit). In practical terms, it activates the
timing function (only for installation directly on FLAT
fan coil units) or a function for correcting the reading of
the ambient temperature sensor (wall installation).
The standard MICRONET controller is designed for wall
mounting and is therefore equipped with an
incorporated air temperature sensor and non-wired
water temperature sensor.
If the controller is to be installed on an FLAT fan coil
unit, the incorporated air temperature sensor will have
to be replaced with a sensor for on-board installation,
provided with an extension cord (included in the on-
board installation kit, code FYKMB)
“ADDRESS” DIPSWITCHES
Group of 7 dipswitches whose configuration serves to ascribe a network address to the controller, based on the
conversion table included in the “Installation booklet” (code FC67001412), which must be completely filled in to
facilitate the setup procedures for the ERGO supervisor software.
WARNING
The address 0 (all dipswitches OFF) is not allowed!!
WARNING
The address 127 (all dipswitches ON) identifies the MASTER in the SMALL network and is thus reserved for this
purpose. No terminal in the LARGE network may be configured with the address 127!!
IMPORTANT
Make sure to note down the configuration of the function and address dipswitches on the sticker on the back of
the controller. Also specify the room where the controller will be installed.
Important:
For each of the terminals connected to the supervision network it is necessary fill out the table included
in the installation booklet, specifying the address of the terminal itself, where it is located, the configuration of the
dipswitches defining the network address, the model of the terminal unit installed and the configuration of the
dipswitches that define the functions (2 or 4 pipes, valves, etc...).