FC66002179 – Rev.00
10
Setting the function dipswitches:
1.
Take off the controller cover by removing the screw at the bottom.
Important:
to make subsequent assembly easier, be careful not to change the position of the two rotary controls
(function selector and thermostat) and their respective potentiometers on the electronic card.
2.
Arrange the dipswitches in the sequence corresponding to one of the configurations described in this manual.
Fig.5
List of dipswitches and respective functions .
Dipswitch
N°
Function: Position
OFF ON
1
Cooling / heating changeover:
Local
Remote
2
Cooling / heating changeover:
Manual
Automatic
3
Automatic cooling / heating changeover according to temperature
of:
Air
(not available)
Water
4
Neutral zone for automatic cooling / heating changeover according
to air temperature:
5 °C
2°C
5
Presence of valve in water circuit:
NO
YES
6
Presence of electric heating element (not available for FLAT):
NO
YES
7
Number of pipes making up water circuit.
2 Pipes
4 Pipes
8
Installation on wall or on unit
Unit
Wall
dipswitches
1
2
3
4
5
6
7
On
Off
8