Galleon 1K Скачать руководство пользователя страница 7

 

Step 3: Communication connection 

Communication port: 

USB port                            RS-232 port                  Intelligent slot 

 

 

 

To allow for unattended UPS shutdown/start-up and status monitoring, connect the 
communication cable one end to the USB/RS-232 port and the other to the communication port 
of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up 
and monitor UPS status through PC. 

 
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing 
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring 

options.   
 

Step 4: Network connection 

Network/Fax/Phone surge port

 

 

Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of 
the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line 

cable.

 

 

Step 5: Disable and enable EPO function 

Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the 
wire between pin 1 and pin 2. 

 
 

 
 
 

 
 

 

Step 6: Turn on the UPS   

Press the ON/Mute button on the front panel for two seconds to power on the UPS. 

Note: The battery charges fully during the first five hours of normal operation. Do not 
expect full battery run capability during this initial charge period. 

 

Step 7: Install software 

For optimal computer system protection, install UPS monitoring software to fully configure UPS 

shutdown. Please follow steps below to download and install monitoring software:

 

1. Go to the website 

http://www.power-software-download.com

 

2. Click ViewPower software icon and then choose your required OS to download the software.   
3. Follow the on-screen instructions to install the software. 
4. When your computer restarts, the monitoring software will appear as an orange plug icon 
located in the system tray, near the clock. 
 

It’s in closed status for UPS 
normal operation.   

 

Содержание 1K

Страница 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Страница 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Страница 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Страница 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Страница 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Страница 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Страница 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Страница 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Страница 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Страница 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Страница 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Страница 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Страница 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Страница 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Страница 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Страница 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Страница 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Страница 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Страница 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Страница 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...