15
13: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external battery
bank is connected.
14: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the maximum charger current.
When the UPS is equipped with additional charger, the available
setting options are 2/3/4.
2/3/4:
setting the maximum charger current in 2/3/4 Ampere.
When the UPS is long run model, the available setting options are
1/2/4/6/8.
1/2/4/6/8:
setting the maximum charger current in 1/2/4/6/8
Ampere. (Default: 8A)
15: Charger Boost voltage setting
Interface
Setting
Parameter 2:
Set up the charger boost voltage.
225-240:
setting the charger boost voltage from 225 to
240(unit: 0.01V/cell). (Default: 236)
16: Charger Float voltage setting
Interface
Setting
Parameter 2:
Set up the charger float voltage.
220-233:
setting the charger float voltage from 220 to
233(unit: 0.01V/cell). (Default:228)
00: Exit setting
Interface
Setting
Exit the setting mode.