1-5. Maintenance, service and faults 

 

The UPS system operates with hazardous voltages. Repairs may be carried out only 
by qualified maintenance personnel.   

 

Caution - 

risk of electric shock. Even after the unit is disconnected from the mains 

(building wiring outlet), components inside the UPS system are still connected to the 
battery and electrically live and dangerous.   

 

Before carrying out any kind of service and/or maintenance, disconnect the batteries 
and verify that no current is present and no hazardous voltage exists in the terminals 
of high capability capacitor such as BUS-capacitors.   

 

Only persons are adequately familiar with batteries and with the required 
precautionary measures may replace batteries and supervise operations. 
Unauthorized persons must be kept well away from the batteries.   

 

Caution -

 risk of electric shock. The battery circuit is not isolated from the input 

voltage. Hazardous voltages may occur between the battery terminals and the ground. 
Before touching, please verify that no voltage is present!   

 

Batteries may cause electric shock and have a high short-circuit current. Please take 
the precautionary measures specified below and any other measures necessary when 
working with batteries:   

remove wristwatches, rings and other metal objects   

use only tools with insulated grips and handles.   

 

When changing batteries, install the same number and same type of batteries.   

 

Do not attempt to dispose of batteries by burning them. This could cause battery 
explosion.   

 

Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and 
eyes. It may be toxic.   

 

Please replace the fuse only with the same type and amperage in order to avoid fire 
hazards.   

 

Do not dismantle the UPS system. 

 

Содержание 1K

Страница 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Страница 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Страница 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Страница 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Страница 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Страница 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Страница 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Страница 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Страница 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Страница 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Страница 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Страница 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Страница 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Страница 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Страница 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Страница 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Страница 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Страница 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Страница 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Страница 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...

Отзывы: