09: Bypass frequency range setting 

Interface 

Setting 

 

Parameter 1 & 2:

Set the acceptable high frequency point and 

acceptable low frequency point for Bypass mode by pressing the 
Down key or Up key. 

HLS: 

Bypass high frequency point 

For 50Hz output frequency models:   

51-55Hz: 

setting the frequency low loss point from 51Hz to 

55HZ(Default: 53.0Hz) 
For 60Hz output frequency models:   

61-65Hz: 

setting the frequency low loss point from 61Hz to 

65Hz(Default: 63.0Hz) 

LLS: 

Bypass low Frequency point 

For 50Hz output frequency models:   

45-49Hz: 

setting the frequency low loss point from 45Hz to 

49HZ(Default: 47.0Hz) 

For 60Hz output frequency models:   

55-59Hz: 

setting the frequency low loss point from 55Hz to 

59Hz(Default: 57.0Hz) 

 

10: Programmable outlets enable/disable 

Interface 

Setting 

 

Parameter 2: 

Enable or disable programmable outlets.   

ENA:

 Programmable outlets enable 

DIS:

 Programmable outlets disable (Default) 

 

11: Programmable outlets setting 

Interface 

Setting 

 

Parameter 2: 

Set up backup time limits for programmable 

outlets.   

0-999: 

setting the backup time limits in minutes from 0-999 

for programmable outlets which connect to non-critical devices 

on battery mode. (Default: 999) 

 

12: Autonomy limitation setting 

Interface 

Setting 

 

Parameter 2: 

Set up backup time on battery mode for general 

outlets.   

0-999: 

setting the backup time in minutes from 0-999 for 

general outlets on battery mode. 

DIS: 

Disable the autonomy limitation and the backup time will 

depend on battery capacity. (Default) 

Note: 

When setting as “0”, the backup time will be only 10 

seconds. 

Содержание 1K

Страница 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Страница 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Страница 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Страница 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Страница 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Страница 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Страница 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Страница 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Страница 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Страница 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Страница 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Страница 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Страница 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Страница 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Страница 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Страница 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Страница 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Страница 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Страница 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Страница 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...

Отзывы: