Cable distance
Cable type
Cable format*
HBUS
single reader
connected
using data
only in a single
cable
Cardax IV
single reader
connected
using data
only in a single
cable***
HBUS/Cardax IV
single reader
connected using
power and
data in a single
cable****
CAT 5e or
better**
4 twisted pair each 2 x
0.2 mm
2
(24 AWG)
500 m (1640 ft) 200 m (650 ft)
100 m (330 ft)
BELDEN
9842**
(shielded)
2 twisted pair each 2 x
0.2 mm
2
(24 AWG)
500 m (1640 ft) 200 m (650 ft)
100 m (330 ft)
SEC472
4 x 0.2 mm
2
Not
twisted pairs (24 AWG)
400 m (1310 ft) 200 m (650 ft)
100 m (330 ft)
SEC4142
4 x 0.4 mm
2
Not
twisted pairs (21 AWG)
400 m (1310 ft) 200 m (650 ft)
150 m (500 ft)
C303900/
C303901
Gallagher
HBUS Cable
2 Twisted pair each 2
x 0.4 mm
2
(21 AWG,
Data) and 2 x 0.75
mm
2
Not Twisted Pair
(~18 AWG, Power)
500 m (1640 ft) 200 m (650 ft)
450 m (1490 ft)
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for optimal HBUS RS485 performance.
*** Not applicable for PIV or Bluetooth® enabled reader installations.
**** Tested with 13.6V at start of cable.
Notes:
•
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
•
If other cable types are used, operating distances and performance may be reduced
depending on the cable quality.
•
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires
13.6 Vdc to function correctly. The cable length and the number of readers connected will
have an impact on the voltage at each reader.
3
Distance between readers
The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions.
When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of
the wall is not less than 200 mm (8 inches) away.
200 mm