Registering System Components
All the field units and repeaters in the system need to be registered in the concentrator. This registration
process is performed on the concentrator; there is no need for any registration process on the controller.
Connecting or disconnecting the controller will not affect the registration process.
Notes:
It is recommended to position all the field units and repeaters near the concentrator
while performing registration. This maximizes the communication strength between the
units and facilitates successful registration.
Upon performing registration, each field unit and repeater unit downloads its default
configuration settings from the default values defined in the concentrator. You may
want to modify these default settings in the concentrator before performing
registration. For more information, refer to
Configuring Field Units and Repeaters
page 31.
Concentrator Programming Buttons
– Confirmation.
Figure 5: Concentrator Buttons
– Browse forward in menus.
– Browse backward in menus.
– Go back to main menu, or Exit.
– Go back to previous menu.
– Off.
Registering Field Units
1.
On the concentrator, perform the following:
a.
Press
until “INSTALLER MENU” is displayed on the screen, and press
to select it.
b.
Enter technician code
9999
. The concentrator emits four beeps and requests confirmation. Do
not change the technician code.
c.
Press
until “DEVICES” is displayed on the screen, and press
to select it.