Test the Infrared Detector Edges:
- Obstruct the Infrared Detector Edges. The DETECTOR EDGES LED should be
ON
.
- The RE-OPEN relay should be
activated
to send the RE-OPEN signal to the elevator controller.
- The elevator controller will send the Door Open command signal back to the VFE- 2500 to OPEN the door.
The LED of the Open Input module should be
ON
.
If the Infrared Detector Edges function does not work:
- Check the table below for correct connections between edges and the VFE2500.
ECI CERTIFIED INFRARED DETECTOR EDGES WIRE COLORS
ECI
P/N
MFG.
TX (CN5)
RX (CN4)
CONNECTION
BETWEEN TX
& RX
V+
LCSE
0V
V+
LCSE
0V
906-3013
JANUS
RED
BLUE
ORG (
♦
)
ORG (
♦
)
WHT - WHT
906-3020 TRITRONICS
RED
WHT
ORG
NONE
906-3030
FORMULA
SYSTEMS
BLU
1
BRN
1
GRN
YEL
BLU
1
BRN
1
GRN
YEL
NONE
906-3030
FORMULA
SYSTEMS
SECOND
VERSION
BROWN
GREEN
YELLOW
BLUE
BROWN
GREEN
YELLOW
BLUE
NONE
(
♦
)
:
Connect an additional wire from 0V to a true EARTH GROUND.
- Check for 24VDC between 0V and +V on either CN4 & CN5.
- Test the Infrared Detector Edges again
If it still does not work. Then,
- Jump 0V to LCSE on either CN4 or CN5 connector for NPN type.
- Jump +V to LCSE on either CN4 or CN5 connector for PNP type
- The DETECTOR EDGES LED should be
ON
.
- The RE-OPEN Relay should be
activated.
If the above tests work as described, turning ON the detector edges LED, then the problem is in the Infrared Detector
Edges. Otherwise, the problem is in the VFE2500.
If the Infrared Detector Edges have intermittent problems:
- Check continuity of the TX and RX cables of the detector edges.
- If the cables are good, but the problem still exists, then check the
Earth Ground
connection to the edges.
- Lower the Carrier Frequency in Par. 1 gradually until problems are resolved.
Note!
The lower carrier frequency will create more audible noise from the motor.
6ϴ
68
Содержание MOVFE 2500
Страница 1: ...2500 3069 1 888 425 2262 2500 3069 ELECTRICAL...
Страница 2: ...Rev 1 10 20 I...
Страница 24: ...19 6 DEFAULT PARAMETERS 19...
Страница 26: ...21 FAULTS AN EXAMPLE OF FAULTS DISPLAY COUNTERS 21...
Страница 27: ...22 USER LIST 22...
Страница 28: ...23 23...
Страница 29: ...24 24...
Страница 30: ...25 25...
Страница 31: ...26 MAXIMUM CLOSE SPEED AND FORCE 26...
Страница 32: ...27 ECI DEFAULT PARAMETER SETS 27...
Страница 34: ...29 SPEED PROFILES OF THE VFE2500 FOR NORMAL DOOR 29...
Страница 35: ...30 SPEED PROFILES OF THE MOVFE2500 FOR HEAVY DOOR 30...
Страница 36: ...31 SPEED PROFILES OF THE MOVFE2500 FOR NARROW DOOR 31...
Страница 91: ...Rev 10 20 85...
Страница 92: ......