Speaker Masters
Not applicable to the IP controller
Speaker master modules work with speaker remote modules in an
Elemec3
system to control volume
levels of speakers driven from central amplifiers. The E3 speaker master module changes individual
loudspeaker power tap levels on command from the E3 controller on a system-wide or individual speaker
basis. The range of adjustment is in steps from off/mute to full power. Each speaker master monitors and
controls up to four audio channels:
1.
Assign amplifier channels to each of the four audio channels. An amplifier channel is assignable to
only one speaker master audio channel.
2.
Assign up to 32 speaker remotes to each speaker master audio channel.
The speaker master powers the speaker remote modules on each channel and transmits power level
tap commands and receives speaker coil health check status from the speaker remote modules.
The E3 system excludes speaker masters from the B system in A-B systems the same way it excludes
amplifiers when redundancy is not a requirement.
Add Speaker Master
1.
Click the
S
PEAKER
M
ASTERS
button, located under the
A
MPLIFIERS
button on the
S
YSTEM
P
ROPERTIES
screen, to open the
S
PEAKER
M
ASTER
S
ETUP
screen (see Figure 26).
Figure 26. Speaker Mater Setup
Poll Window
—HH:MM–HH:MM(DAILY)—Click the ellipsis button to change the time frame the
speaker masters use to poll the speaker remotes to set transformer tap levels and obtain status from the
remotes.
N
OTE
:
The global
TIME ZONE SETTING
is viewable and configurable on the
S
PEAKER
M
ASTER
P
OLL
W
INDOW
dialog box and from the
S
CHEDULED
E
VENT
C
ONFIGURATION
screen (see the
Scheduled Events section).
Fault Mode:
—Ignore, Normal, or