2

Important Health and Safety Information for Installers and Service Engineers

Health and Safety at Work Act 1974
Consumer Protection Act 1987
COSHH Regulations 1988
The following information is given as a requirement of the
above legislation.
Great care is taken by GAH (HEATING PRODUCTS) LIMITED
to ensure that Electrastream systems are designed and
manufactured to meet general safety requirements when
properly used and installed as recommended in this manual.
It is the responsibility of Users and Engineers to ensure that
adequate protective clothing and glasses are worn when
working with the Electrastream system.

SEALS AND INSULATION

SEALS AND INSULATION

SEALS AND INSULATION

SEALS AND INSULATION

SEALS AND INSULATION
Insulation and sealing materials are used in the construction
of the Electrastream cylinders.  Units are sealed and when
used in the manner for which they are intended the insulating
and sealing materials do not present any known hazard.
However always observe the following recommendations:-
1. Avoid inhalation of fibres or dust, wear face mask.
2. Avoid eye contamination by fibres or dust - wear eye
protection.
3. As far as possible avoid any skin contact with Fibreglass
Insulation, Glass Rope, Mineral Wool, Insulation Pads and
Ceramic Fibre.

PPPPPatent application 01514800.2

atent application 01514800.2

atent application 01514800.2

atent application  01514800.2

atent application 01514800.2

©

©

©

©

©

 2010 GAH (HEATING PRODUCTS) L

 2010 GAH (HEATING PRODUCTS) L

 2010 GAH (HEATING PRODUCTS) L

 2010 GAH (HEATING PRODUCTS) L

 2010 GAH (HEATING PRODUCTS) LTD.

TD.

TD.

TD.

TD.

Electrastr

Electrastr

Electrastr

Electrastr

Electrastream is a T

eam is a T

eam is a T

eam is a T

eam is a Trademark of GAH (HEATING PRODUCTS) L

rademark of GAH (HEATING PRODUCTS) L

rademark of GAH (HEATING PRODUCTS) L

rademark of GAH (HEATING PRODUCTS) L

rademark of GAH (HEATING PRODUCTS) LTD.

TD.

TD.

TD.

TD.

Manual by Harber Technical Services Tel/Fax  01263 515444

E-mail:[email protected]      www.harbertech.co.uk

GAH (Heating Pr

GAH (Heating Pr

GAH (Heating Pr

GAH (Heating Pr

GAH (Heating Products) Ltd.

oducts) Ltd.

oducts) Ltd.

oducts) Ltd.

oducts) Ltd.

Building 846
Bentwaters Parks
Rendlesham
Woodbridge
Suffolk IP12 2TW

TTTTTel:

el:

el:

el:

el: 01394  421160

01394  421160

01394  421160

01394  421160

01394  421160

Fax:

Fax:

Fax:

Fax:

Fax: 01394  421170

01394  421170

01394  421170

01394  421170

01394  421170

email: [email protected]
www.gah.co.uk

In pursuance of a policy of constant development, GAH (HEATING PRODUCTS) LIMITED
reserve the right to change Electrastream parts or design without notice, therefore
certain details included in this manual may not be correct at the time of printing.  Any
modification and improvements detailed in this manual does not commit GAH to update
any system previously supplied.

Manual Part No. ...................MAN1019
Manual Ref ..........................ES02
Issue ...................................13
Date ....................................25/02/13

GAH (HEATING PRODUCTS) LIMITED will not accept

responsibility for any damage or personal injury caused

by not giving due consideration to the above safety

recommendations.

OTHER MATERIALS

OTHER MATERIALS

OTHER MATERIALS

OTHER MATERIALS

OTHER MATERIALS

SEALANTS, ADHESIVES AND PAINTS

Sealants, Adhesives and Paints are used in the construction of
the Electrastream components. When used in the manner for
which they are intended they do not present any known hazard.

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC
The Cylinder Tri-Core Heater, Pump, Thermostats and Contactor
Box all have electrical supply of 230V (enough to endanger
life).
Always isolate before connection, adjustment, servicing and
repair.
When the Tri-Core Heater cover is removed high power live
electrical terminals are exposed.
ISOLATE THE TRI-CORE HEATER BEFORE REMOVING ITS
COVER.
Earth protection - Earth Continuity Conductors must be fitted
and must comply with IEE Wiring Regulations.

HTS REF GAH ELECTRASTREAM 25/02/13

HEAL

HEAL

HEAL

HEAL

HEALTH & SAFETY

TH & SAFETY

TH & SAFETY

TH & SAFETY

TH & SAFETY

34

22mm SUPPLY

FROM MAINS

15mm TO TUNDISH

PRESSURE RELIEF
VALVE
Set at 6 Bar

22mm SUPPLY TO CYLINDER AND
ELECTRASTREAM ACCUMULATOR

Fig. 4-3b  Combination Valve

3.5 Bar  PRESSURE

REDUCING VALVE

Fig. 4-3c  Expansion Vessel Connection

¾”” BSP PORT FOR
EXPANSION VESSEL

IN-LINE STRAINER

GAH offer a range of quality Water
Softeners, for information contact
GAH (HEATING PRODUCTS) LTD.

4-3.4  Hot Water Expansion Vessel

An Expansion Vessel is supplied for the hot water system, this should be fitted to the
combination valve which has a ¾”” BSP port provided for this.  The expansion vessel
must always be open to the system with NO shut off or isolation valves in the connection
pipe.
Clearance is required on top of the vessel to access the pressure valve.
It is the responsibility of the installer to set the correct pre-charge pressure of the vessel.

INST

INST

INST

INST

INSTALLA

ALLA

ALLA

ALLA

ALLATION      4

TION      4

TION      4

TION      4

TION      4

4-3.5  Accumulator (Electrastream Plus only)

The accumulator may be installed at any convenient location within the property,
outhouse, garage, loft or basement.  For optimum efficiency this should be fitted furthest
from the incoming mains supply.
The accumulator should be installed vertically.
The floor must give adequate support to the filled accumulator.
Accumulators must have frost protection when they are installed where low temperatures
could be a potential problem - see  1-4.7.
Note that space is required to the top of the vessel to access the pressure valve.
Provision must be made to enable the accumulator to be drained when required.

IMPORTANT  The accumulator is supplied at 2 Bar pressure.  It is

recommended to set the pressure at 1.5 Bar below the mains pressure
with a minimum of 0.8 Bar - see 5-1.2.

4-3.6  Scale Protection

IMPORTANT  All installations should have a scale protection device fitted
and in areas known to have hard water, a water softening device is
strongly recommended.  The cylinder is not guaranteed against damage

caused by scale.  Higher water temperatures of 65°C and above can
cause excessive scale.

GAH recommend and promote the use of scale prevention devices and water softeners in
areas that are known to have hard water.  Installed correctly they prolong the life of
equipment and help prevent limescale formation in the pipework.  Water Softeners
provide the advantages of soft water, as well as preventing scale build up on taps and
shower heads.
Water softeners and any mains fed system must be of adequate capacity and should be
installed with suitably sized hoses to prevent any possibility of flow reduction.
The location and position of the Scale Protection Device or Water Softener should be as
the manufacturers recommendations.

Note
As Electrastream Plus is a sealed system,
the pressure at the taps is not affected by
the height of the cold water storage.

44444

Содержание Electrastream

Страница 1: ...ld water supply and Electric Central Heating with water filled radiators suitable for Self contained Flats Small Dwellings Offices Home Offices and Granny Annexes 9 kW 30 000 Btu for Heating and Hot Water 27 02 13 T T T T Twin Coil Cylinder option available for SOLAR ener win Coil Cylinder option available for SOLAR ener win Coil Cylinder option available for SOLAR ener win Coil Cylinder option av...

Страница 2: ...GAH ELECTRASTREAM 25 02 13 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 2 Important Health and Safety Information for Installers and Service Engineers Health and Safety at Work Act 1974 Consumer Protection Act 1987 COSHH Regulations 1988 The following information is given as a requirement of the above legislation Great care is taken by GAH HEATING PRODUCTS LIMITED to e...

Страница 3: ...ORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 3 CONTENTS CONTENTS CONTENTS CONTENTS CONTENTS 1 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 2 OPERA 2 OPERA 2 OPERA 2 OPERA 2 OPERATOR CONTROLS TOR CONTROLS TOR CONTROLS TOR CONTROLS TOR CONTROLS 3 TECHNICAL INFORMA 3 TECHNICAL INFORMA 3 TECHNICAL INFORMA 3 TECHNICAL I...

Страница 4: ...HAVE BEEN DELIVERED AND ARE TING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION R IN SATISFACTORY CONDITION R IN SATISFACTORY CONDITION R IN SATISFACTORY CONDITION R IN SATISFACTORY CONDITION Refer to 1 3 efer to 1 3 efer to 1 3 efer to 1 3 efer to 1 3 Delivery Standard Electrastream systems will be delivered wrapped on single palle...

Страница 5: ...he cylinder and mixed with cold water by a thermostatic mixing valve this ensures safer lower temperatures at the hot water outlets The hot water within the unvented indirect cylinder also heats the water for the heating system via the indirect coil within the cylinder The circulating pump for the heating system is controlled by a thermostat and programmable timer with override so that heat is ava...

Страница 6: ...Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does not commit GAH to update any system previously supplied Manual Part No MAN1019 Manual Ref ES02 Issue 13 Date 25 02 13 GAH HEATING PRODUCTS LIMITED will not accept responsibility for any damage or per...

Страница 7: ...TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 7 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 1 INTRODUCTION 1 n o i t p O l e d o M e d o C r e d n i l y C m a e r t s a r t c e l E m a e...

Страница 8: ...444 E mail info harbertech co uk www harbertech co uk GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Products Ltd oducts Ltd oducts Ltd oducts Ltd oducts Ltd Building 846 Bentwaters Parks Rendlesham Woodbridge Suffolk IP12 2TW T T T T Tel el el el el 01394 421160 01394 421160 01394 421160 01394 421160 01394 421160 Fax Fax Fax Fax Fax 01394 421170 01394 421170 01394 421170 ...

Страница 9: ...e 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Se...

Страница 10: ...444 E mail info harbertech co uk www harbertech co uk GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Products Ltd oducts Ltd oducts Ltd oducts Ltd oducts Ltd Building 846 Bentwaters Parks Rendlesham Woodbridge Suffolk IP12 2TW T T T T Tel el el el el 01394 421160 01394 421160 01394 421160 01394 421160 01394 421160 Fax Fax Fax Fax Fax 01394 421170 01394 421170 01394 421170 ...

Страница 11: ...ERVICING 6 SERVICING 4 INST 4 INST 4 INST 4 INST 4 INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 11 1 3 Parts Supplied m e t I t r a P y t Q s e t o N 1 l o r t n o C ...

Страница 12: ...ctor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical terminals are exposed ISOLATE THE TRI CORE HEATER BEFORE REMOVING ITS COVER Earth protection Earth Continuity Conductors must be fitted and must comply with IEE Wiring Regulations HTS REF GAH ELECTR...

Страница 13: ...ction IMPORTANT All installations should have a scale protection device fitted and in areas known to have hard water a water softening device is strongly recommended The cylinder is not guaranteed against damage caused by scale Higher water temperatures of 65 C and above can cause excessive scale GAH recommend and promote the use of scale prevention devices and water softeners in areas that are kn...

Страница 14: ...te any system previously supplied Manual Part No MAN1019 Manual Ref ES02 Issue 13 Date 25 02 13 GAH HEATING PRODUCTS LIMITED will not accept responsibility for any damage or personal injury caused by not giving due consideration to the above safety recommendations OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS SEALANTS ADHESIVES AND PAINTS Sealants Adhesives and Pa...

Страница 15: ...FETY TH SAFETY TH SAFETY TH SAFETY 15 OPERA OPERA OPERA OPERA OPERATOR CONTROLS 2 TOR CONTROLS 2 TOR CONTROLS 2 TOR CONTROLS 2 TOR CONTROLS 2 If the over temperature cut out trips more than once switch off the Electrastream isolating switch and contact your installer 2 1 4 Heating Motorised Valve When the room thermostat is calling for heat and the Electrastream control unit is set for heat ON the...

Страница 16: ...1170 01394 421170 01394 421170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pursuance of a policy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does n...

Страница 17: ...4 Installation 4 1 Building Control 31 4 2 Electrical 31 4 3 Hot Water System 33 4 4 Heating System 37 4 5 Expansion Discharge 40 4 6 System Pressure 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Ser...

Страница 18: ...TS ADHESIVES AND PAINTS Sealants Adhesives and Paints are used in the construction of the Electrastream components When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connec...

Страница 19: ...Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52 Health Safety Health Safety Health Safety Health Safety Health Safety Inside Front Cover 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 4 INST 4 INST 4 I...

Страница 20: ...2 2TW T T T T Tel el el el el 01394 421160 01394 421160 01394 421160 01394 421160 01394 421160 Fax Fax Fax Fax Fax 01394 421170 01394 421170 01394 421170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pursuance of a policy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included...

Страница 21: ...g Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52 Health Safety Health Safety Health Safety...

Страница 22: ...ch they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical terminals are exposed ISOLATE THE TRI CO...

Страница 23: ...TH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 23 TECHNICAL INFORMA TECHNICAL INFORMA TECHNICAL INFORMA TECHNICAL INFORMA TECHNICAL INFORMATION 3 TION 3 TION 3 TION 3 TION 3 3 1 Specifications Cylinder WRC Certificate No 0605118 l e d o M m a e r t s a r t c e l E 0 3 1 L E B 0 3 1 P E B 0 5 1 L E B 0 5 1 P E B 5 1 2 P T E B r e d n i l y C y t i c a p a C 1 0 3 e r t i l e r t i l 0 5 1 1 2 5 ...

Страница 24: ...mendations OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS SEALANTS ADHESIVES AND PAINTS Sealants Adhesives and Paints are used in the construction of the Electrastream components When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Cont...

Страница 25: ...31 4 2 Electrical 31 4 3 Hot Water System 33 4 4 Heating System 37 4 5 Expansion Discharge 40 4 6 System Pressure 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routi...

Страница 26: ...Fax 01394 421170 01394 421170 01394 421170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pursuance of a policy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this m...

Страница 27: ...iring 29 Section 4 Installation Section 4 Installation Section 4 Installation Section 4 Installation Section 4 Installation 4 1 Building Control 31 4 2 Electrical 31 4 3 Hot Water System 33 4 4 Heating System 37 4 5 Expansion Discharge 40 4 6 System Pressure 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5...

Страница 28: ...0 01394 421170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pursuance of a policy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does not commit GAH to...

Страница 29: ... Section 4 Installation Section 4 Installation Section 4 Installation 4 1 Building Control 31 4 2 Electrical 31 4 3 Hot Water System 33 4 4 Heating System 37 4 5 Expansion Discharge 40 4 6 System Pressure 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicin...

Страница 30: ...Pr GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Products Ltd oducts Ltd oducts Ltd oducts Ltd oducts Ltd Building 846 Bentwaters Parks Rendlesham Woodbridge Suffolk IP12 2TW T T T T Tel el el el el 01394 421160 01394 421160 01394 421160 01394 421160 01394 421160 Fax Fax Fax Fax Fax 01394 421170 01394 421170 01394 421170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pu...

Страница 31: ... ater Bye laws ater Bye laws ater Bye laws ater Bye laws and Curr Curr Curr Curr Current Building R ent Building R ent Building R ent Building R ent Building Regulations egulations egulations egulations egulations paying particular attention to G3 and Part L 1 2 and HSE HSE HSE HSE HSE requirements should be considered when installing an Electrastream System 4 2 Electrical 4 2 1 Electrical Regulat...

Страница 32: ...tion to the above safety recommendations OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS SEALANTS ADHESIVES AND PAINTS Sealants Adhesives and Paints are used in the construction of the Electrastream components When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core He...

Страница 33: ...at any convenient above ground location within the property As Electrastream is a sealed system the cylinder is equally effective on any floor The cylinder must always be installed vertically Avoid positioning the cylinder where it may be subjected to frost The floor must give adequate support to the filled cylinder Cylinders must have frost protection when they are installed where low temperature...

Страница 34: ...hey do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical terminals are exposed ISOLATE THE TRI CORE HEATER BEFORE REMOV...

Страница 35: ...LA ALLA ALLATION TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 35 INST INST INST INST INSTALLA ALLA ALLA ALLA ALLATION 4 TION 4 TION 4 TION 4 TION 4 4 3 7 Pipework When all pipework has been installed...

Страница 36: ...1170 01394 421170 01394 421170 email mail gah co uk www gah co uk In pursuance of a policy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does not commit GAH to update an...

Страница 37: ...Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52 Health Safety Health Safety Health Safety Health Safety Health Safety Inside Front Cover 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 4 INST 4 INST 4 INST 4 INST 4 INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTRE...

Страница 38: ...RIALS OTHER MATERIALS OTHER MATERIALS OTHER MATERIALS SEALANTS ADHESIVES AND PAINTS Sealants Adhesives and Paints are used in the construction of the Electrastream components When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply ...

Страница 39: ...rvicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52 Health Safety Health Safety Health Safety Health Safety Health Safety Inside Front Cover 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 4 INST 4 INST 4 INS...

Страница 40: ...unction boxes 4 5 2 Expansion Discharge Self Sealing Valve A Hepvo Self Sealing Valve enables alternative discharge arrangements to be used however its use and installation must be approved by the local building control Refer to G3 Regulation and valve supplier manufacturers instructions for installation and servicing requirements 4 5 3 Expansion Discharge Pipe To Gully The discharge pipe from the...

Страница 41: ...A ALLA ALLA ALLATION TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 41 INST INST INST INST INSTALLA ALLA ALLA ALLA ALLATION 4 TION 4 TION 4 TION 4 TION 4 Diagram 1 T T T T Typical dischar ypical discha...

Страница 42: ...TERIALS SEALANTS ADHESIVES AND PAINTS Sealants Adhesives and Paints are used in the construction of the Electrastream components When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate...

Страница 43: ... 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52 He...

Страница 44: ... right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does not commit GAH to update any system previously supplied Manual Part No MAN1019 Manual Ref ES02 Issue 13 Date 25 02 13 GAH HEATING PRODUCTS LIMITED will not accept responsibility for ...

Страница 45: ...ion 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing Section 6 Servicing 6 1 Routine Service 50 Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding Section 7 Fault Finding 7 1 Fault Finding 52...

Страница 46: ...olicy of constant development GAH HEATING PRODUCTS LIMITED reserve the right to change Electrastream parts or design without notice therefore certain details included in this manual may not be correct at the time of printing Any modification and improvements detailed in this manual does not commit GAH to update any system previously supplied Manual Part No MAN1019 Manual Ref ES02 Issue 13 Date 25 ...

Страница 47: ...G EAR UDING EAR UDING EAR UDING EARTH WIRING HAS BEEN INSTALLED TH WIRING HAS BEEN INSTALLED TH WIRING HAS BEEN INSTALLED TH WIRING HAS BEEN INSTALLED TH WIRING HAS BEEN INSTALLED CORRECTL CORRECTL CORRECTL CORRECTL CORRECTLY Y Y Y Y CONFORMS TO CURRENT REGULATIONS AND A SATISFACTORY CONFORMS TO CURRENT REGULATIONS AND A SATISFACTORY CONFORMS TO CURRENT REGULATIONS AND A SATISFACTORY CONFORMS TO C...

Страница 48: ...nents When used in the manner for which they are intended they do not present any known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical ter...

Страница 49: ...H SAFETY TH SAFETY 49 STAGE 9 ACCUMULATOR PRESSURE Accumulators are supplied by GAH with a preset air charge of 2 Bar 28 30psi The Combination Valve supplied with the Electrastream Plus has an integral pressure reducing valve fixed at 3 5 Bar Therefore there is a pressure differential of 1 5 bar between the system pressure and the air charge of the Accumulator When the incoming mains pressure is l...

Страница 50: ...ylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical terminals are exposed ISOLATE THE TRI CORE HEATER BEFORE REMOVING ITS COVER Earth protection Earth Continuity Conductors must be fitted and must com...

Страница 51: ...n 4 Installation Section 4 Installation Section 4 Installation 4 1 Building Control 31 4 2 Electrical 31 4 3 Hot Water System 33 4 4 Heating System 37 4 5 Expansion Discharge 40 4 6 System Pressure 43 4 7 Electrastream Connections 44 Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning Section 5 Commissioning 5 1 Commissioning 47 Section 6 Servicing Secti...

Страница 52: ...ny known hazard ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC The Cylinder Tri Core Heater Pump Thermostats and Contactor Box all have electrical supply of 230V enough to endanger life Always isolate before connection adjustment servicing and repair When the Tri Core Heater cover is removed high power live electrical terminals are exposed ISOLATE THE TRI CORE HEATER BEFORE REMOVING ITS COVER Earth ...

Страница 53: ... Front Cover 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 6 SERVICING 4 INST 4 INST 4 INST 4 INST 4 INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION IMPORTANT BEFORE STARTING THE INSTALLATION OF THE ELECTRASTREAM CHECK ALL COMPONENTS HAVE BEEN DELIVERED AND ARE IN SATISFACTORY CONDITION Refer to 1 3 HEAL HEAL HEAL HEAL HEALTH SAFETY TH SAFETY TH SAFETY TH SAFETY TH SAFETY 53 Indirect cylind...

Страница 54: ...EATING PRODUCTS LTD TD TD TD TD Manual by Harber Technical Services Tel Fax 01263 515444 E mail info harbertech co uk www harbertech co uk GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Pr GAH Heating Products Ltd oducts Ltd oducts Ltd oducts Ltd oducts Ltd Building 846 Bentwaters Parks Rendlesham Woodbridge Suffolk IP12 2TW T T T T Tel el el el el 01394 421160 01394 421160 01394 421160 ...

Страница 55: ...55 ...

Страница 56: ...56 GAH Heating Products Ltd Building 846 Bentwaters Parks Rendlesham Woodbridge Suffolk IP12 2TW www gah co uk Tel 01394 421160 Fax 01394 421170 email mail gah co uk heating products ...

Отзывы: