59
Display code
Problem
Cause
Help
A search is performed for
the sensor
"Unlocking active leaf"
No error
y
y
Test run
y
y
See point 6.5
A search is performed for
the sensor
"Unlocking passive leaf"
No error
y
y
Test run
y
y
Test run
A search is performed for
the sensor
"Locking" active leaf
No error
y
y
Test run
y
y
Test run
A search is performed for
the sensor "Locked"
No error
y
y
Test run
y
y
Test run
Programming mode
active
y
y
Service plug not
removed or latchbolt
monitoring not
actuated longer than
5 s
y
y
Exit programming
mode
(see point 6.2)
Lock does not unlock
electrically
No error
y
y
Deadbolt at the active
leaf has been moved
to the locked position
(only B-2393x)
y
y
Unlock manually
the active leaf
Capacity check
No error
y
y
When the emergency
power backup system
B-54903-23-3-9
is connected, the
controller checks the
capacity on a daily
basis
The "unlocked" sensor
position is lost during
daytime release and the
motor runs briefly
No error
y
y
Motor dips during
daytime release due
to heavy vibrations
and readjusts in the
unlocking direction
y
y
Check the closing
speed and door strike
at the door closer and
reduce if necessary,
providing it can still be
ensured that the door
leaf closes.
Otherwise no
remedial action is
required.
Bus error
y
y
Communication error
between lock and
controller
y
y
Check wiring
(BR-GN, BL-RT)
(see point 2.3)
Содержание BKS B-2193 Series
Страница 111: ...111 Certificaciones y y 1 2 A B C 3 7 7 B 1 3 2 y y 2 AC 3 7 7 B 1 3 4 y y EN 14846 0 0 3 S 3 E 0 0 0 y y y y DO 5 0 y y...
Страница 141: ...141...
Страница 143: ...143 1 2 3 4...
Страница 145: ...145 A 3 Profilfr sung A 3 Profile cutout A 3 Fraisage du profil A 3 Fresado del perfil 384 346 144 121 23 1050 OFF...
Страница 146: ...146 B 2193x B 2393x 06 2019 22288S Designed in Germany Notizen Notes Notes Notas...
Страница 147: ...147 Notizen Notes Notes Notas...