Section 50
00-02-1031
2019-08-07
- 16 -
Temp Input Status Screen
t
The user can see the state of each temperature input in a
table
—whether it is OK or has a wiring fault.
X = OK
p = Wire Fault Leaking to DC+ (input still able to be read,
but some error is being introduced)
n = Wire Fault Leaking to DC- (input still able to be read,
but some error is being introduced)
P = Wire Fault Short to DC+ (input not able to be read)
N = Wire Fault Short to DC- (input not able to be read)
Shutdown History Screen
The history of the shutdowns are displayed on this screen,
with the most recent at the top of the list and the oldest at
the bottom.
The number displayed in the top right corner indicates how
many entries are in the list.
Each event is displayed with the event label on one line
and the real time clock and hour meter reading on the
following line.
Shutdown Snapshot Screen
The shutdown snapshot screen is a capture of the values
displayed on the line-by-line custom screen at the time of a
Fault SD or ESD event. These values will be retained and
display on the shutdown snapshot screen until the next
Fault SD or ESD event occurs. A
“---“ displayed instead of
a value indicates the shutdown snapshot has not captured
any data. Fault snapshots are taken only while the
equipment has been called to start/run. This behavior
ensures that repeated attempts to reset a fault will not
“clear” a previous run cycle’s fault snapshot.
NOTE:
Only the first two
line-by-line screens
configured will be captured on the fault snapshot
page. If no line-by-line custom screens are
configured, the shutdown snapshot will not
function.