Section 50
00-02-1031
2019-08-07
- 33 -
Rod load Setup Screen
Rod Load setup screen is visible if Compressor Rod Load
is configured in the Centurion. For each throw setup in the
configuration, the user can view and set these parameters.
a) Throw Type: Display for the set action of the
compressor throw. If set to Single or Double by the
configuration tool, the user may change the action
back and forth if the compressor geometry is
changed. Blank or Tandem options are Read Only
b) Rod Size: Setpoint displayed in inches or
centimeters, depending on the configured Rod
Load Units, for the rod size.
c) Suction Pressure: Display for the input channel
used as suction pressure for the throw.
d) Suction Pressure Drop: Setpoint in Percent for the
pressure drop from the measurement point to the
internal cylinder pressures. This is aggregate of
valve and piping pressure losses.
e) Discharge Pressure: Display for the input channel
used as suction pressure for the throw.
f) Discharge Pressure Drop: Setpoint in Percent for
the pressure drop from the internal cylinder
pressures to the measurement point. This is
aggregate of valve and piping pressure losses.
g) Cylinder Size: Setpoint displayed in inches or
centimeters, depending on the configured Rod
Load Units, for the cylinder size.
h) Hi Compression: Setpoint in lbs-force or Newtons,
depending on the configured Rod Load Units, for
the rod load alarm event.
i)
Hi Hi Compression: Setpoint in lbs-force or
Newtons, depending on the configured Rod Load
Units, for the rod load shutdown event.
j)
Hi Tension: Setpoint in lbs-force or Newtons,
depending on the configured Rod Load Units, for
the rod load alarm event.
k) Hi Hi Tension: Setpoint in lbs-force or Newtons,
depending on the configured Rod Load Units, for
the rod load shutdown event.
NOTE:
These are the options shown for single or double
acting options. If the throw is a tandem type, it will have
twice the settings, (a low pressure (LP) and high pressure
(HP) set of setpoints.