Future Design FDC-C22 Скачать руководство пользователя страница 8

FDC_C-Series_Quick_Operation_User_Manual_UMQOC621A.doc Page 

8

 of 

20

 

 
 

 

Modbus 

Register 

Address 

Parameter 
Notation 

Parameter Description 

Range 

56 

A4MD 

Alarm 4 operation mode 

NoRM

: Normal alarm action

  

LtCH: 

Latching alarm action

  

HoLd: 

Hold alarm action

  

Lt.Ho: 

Latching & Hold action 

SP.Ho: 

Set point holding alarm 

57 

A4HY 

Hysteresis control of alarm 4 

Low: 0.1°C   High: 50.0°C(90.0°F) 

58 

A4FT 

Alarm 4 failure transfer mode 

OFF

: Alarm output OFF if sensor fails 

ON

: Alarm output ON if sensor fails 

59 

A4SP 

Alarm 4 set point 

Low: -19999  High: 45536 

60 

A4DV 

Alarm 4 deviation value 

Low: -19999  High: 45536 

61 

BPL1 

Bumpless transfer value of MV1

Low: 0.00  High: 100.00 

62 

BPL2 

Bumpless transfer value of MV2 

Low: 0.00  High: 100.00 

63 

CJCL 

Sense voltage during cold junction calibration low 

Low: 0  High: 7552 

64 

PV64 

Process value 

Low: -19999  High:45536 

65 

SV65 

Current set point value 

Low: SP1L  High:SP1H

66 

MV1 66 

Output  1 %Value(Heating)

Low: 0.00  High: 100.00 % 

67 

MV2 67 

Output  2 %Value(Cooling) 

Low: 0.00  High: 100.00 % 

68 

TIMER 

Remaining time of dwell timer 

Low: 0.0  High: 4553.6 

69 

EROR 

Error code 

Low: 0  High: 65535 

70 

MODE 

Operation mode & alarm status 

Low: 0  High: 65535 

71 PROG71 

Program 

code 

C22:22.XX  C62:62.XX  C82:82.XX  C83:83.XX  

C72:72.XX  C42:42.XX  R22:23.XX 

72 

CMND 

Command code 

Low: 0  High: 65535 

73 

JOB1 

Job code 

Low: 0  High: 65535 

74 

JOB2 

Job code 

Low: 0  High: 65535 

75 

JOB3 

Job code 

Low: 0  High: 65535 

76 

CJCT 

Cold Junction Temperature 

Low: -4000  High: 9000 

77 

ADLO 

mV calibration low coefficient

Low: -1999  High: 1999

78 

ADHI 

mV calibration high coefficient 

Low: -1999  High: 1999 

79 

RTDL 

RTD calibration low coefficient 

Low: -1999  High: 1999 

80 

RTDH 

RTD calibration high coefficient 

Low: -1999  High: 1999 

81 

CJLO 

Cold junction calibration low coefficient 

Low: -5.00  High: 40.00 

82 

CJHI 

Cold junction calibration high coefficient 

Low: -1999  High: 1999 

83 

V1L 

V1 calibration low coefficient

Low: -1999  High: 1999

84 

V1G 

V1 calibration high coefficient 

Low: -1999  High: 1999 

85 

MA1L 

MA1 calibration low coefficient 

Low: -1999  High: 1999 

86 

MA1G 

MA1 calibration high coefficient 

Low: -1999  High: 1999 

87 

V2L 

V2 calibration low coefficient 

Low: -1999  High: 1999 

88 

V2G 

V2 calibration high coefficient

Low: -1999  High: 1999

89 

MA2L 

MA2 calibration low coefficient

Low: -1999  High: 1999

90 

MA2G 

MA2 calibration high coefficient 

Low: -1999  High: 1999 

91 

PL1L 

Power limit 1 low 

Low: 0  High:PL1H or 50% 

92 

PL1H 

Power limit 1 high 

Low: PL1L  High: 100 % 

93 

PL2L 

Power limit 2 low 

Low: 0  High: PL2H or 50% 

94 

PL2H 

Power limit 2 high Low: 

PL2L  

High: 100 % 

Содержание FDC-C22

Страница 1: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 1 of 20 PID Fuzzy Logic Process Controller C22 C62 C82 C83 C72 C42 R22 Quick Operation User Manual UMQOC621A September 2018...

Страница 2: ...rt the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs 2 MENU FLOWCHART 5 Sec 6 2 Sec 7 4 Sec 8 6 Sec 9 8 Sec 5 Sec 5 Sec 2 3 Sec User Menu Setup...

Страница 3: ...2 2 Output Menu oUT Use or key to get oUT in the lower display then use key to enter output menu parameters or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2 O2TY O2FT CYC2 CPB DB PL1L PL1H PL2L PL2H 2 2...

Страница 4: ...parameters or SET PRoF PROF TSP7 RMPU RPT7 STAR SKT7 END TSP8 PFR RPT8 HBLO SKT8 HBHI TSP9 HBT RPT9 CYCL SKT9 CYCR TSPA STEP RPTA TIMR SKTA STAT TSPB TSP1 RPTB RPT1 SKTB SKT1 TSPC TSP2 RPTC RPT2 SKTC...

Страница 5: ...rrent input 0 5V 0 5VDC linear voltage input 1 5V 1 5VDC linear voltage input 0 10 0 10VDC linear voltage input 9 UNIT Input unit selection oC C unit oF F unit Pu Process unit 10 DP Decimal point sele...

Страница 6: ...Relay output SSrd Solid state relay drive output 4 20 4 20mA linear current 0 20 0 20mA linear current 0 5V 0 5VDClinear voltage 1 5V 1 5VDC linear voltage 0 10 0 10VDC linear voltage 30 O2FT Output 2...

Страница 7: ...Output 48 A3FN Alarm 3 function for alarm 3 output NoNE No alarm function dtMR Dwell timer action dE HI Deviation high alarm dE Lo Deviation low alarm db HI Deviation band out of band alarm db Lo Devi...

Страница 8: ...535 71 PROG71 Program code C22 22 XX C62 62 XX C82 82 XX C83 83 XX C72 72 XX C42 42 XX R22 23 XX 72 CMND Command code Low 0 High 65535 73 JOB1 Job code Low 0 High 65535 74 JOB2 Job code Low 0 High 655...

Страница 9: ...A3SP is moved to USER Menu A3dV A3DV is moved to USER Menu A4HY A4HY is moved to USER Menu A4SP A4SP is moved to USER Menu A4dV A4DV is moved to USER Menu PL1L PL1L is moved to USER Menu PL1H PL1H is...

Страница 10: ...ission output Remote SP 1 5V 1 5VDC retransmission output Remote SP 0 10 0 10VDC retransmission output Remote SP A 4 20 Alarm 4 4 20mA retransmission output Remote SP A 0 20 Alarm 4 0 20mA retransmiss...

Страница 11: ...nt for heater short 1 Low 0 0 High 120 0 123 HS2T Triple point current for heater short 2 Low 0 0 High 120 0 124 RMSP Remote SP type None No Remote SP 4 20 4 20mA retransmission output 0 20 0 20mA ret...

Страница 12: ...CoNt Run Profile as RUN CONT PV Run Profile as RUN PV HoLd Run Profile as RUN HOLD StoP Run Profile as RUN STOP 144 E4FN Event input 4 function SP5 SP5 activated to replace SP1 Others Same as E3FN 14...

Страница 13: ...13 of 20 161 222 For Profiler parameters description please refer to full version user manual 4 WIRING DIAGRAM C22 Terminal Connection C62 Terminal Connection C82 C42 Terminal Connection C83 Terminal...

Страница 14: ...MD and A4MD available for each alarm function A1FN A2FN A3FN and A4FN In addition to the alarm output output 2 can also be configured as an alarm But output 2 has only provides 8 different alarm funct...

Страница 15: ...t type will be stored in the memory If the input type is changed a calibration error will occur and an error code is displayed 5 10 Digital Filter In certain applications the process value is too unst...

Страница 16: ...nsmission option installed RELO and REHI are adjusted to specify the low scale and high scale values of retransmission 10 HEATER CURRENT MONITORING A current transformer CT98 1 is required to measure...

Страница 17: ...data to the slave 15 ER15 Communication error write a value which is out of range to a register Do not write an over range data to the slave register 16 EIER Event Input Error Two or more event input...

Страница 18: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 18 of 20 Page Left Intentionally Blank...

Страница 19: ...rnians about significant exposures to chemicals that cause cancer birth defects or other reproductive harm These chemicals can be in the products that Californians purchase in their homes or workplace...

Страница 20: ...s or losses whether direct indirect incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control product...

Отзывы: