Future Design FDC-C22 Скачать руководство пользователя страница 15

FDC_C-Series_Quick_Operation_User_Manual_UMQOC621A.doc Page 

15

 of 

20

 

 
 

 

5.7 Ramp: 

The ramping function is performed during power up as well as any time the set point is changed. Choose MINR or HRR for 

the RAMP setting, and the controller will perform the ramping function. The ramp rate is programmed by adjusting the RR setting. 

The ramping function is disabled as soon as the Failure mode, the Manual control mode, the Auto-tuning mode or the Calibration 

mode occur. 

 

5.8 Dwell Timer: 

The Dwell timer can be with or without a Ramp.  Alarm outputs can be configured as dwell timers by selecting dtMR 

for A1FN. If A1FN is set to dtMR, Alarm 1 will act as a dwell timer. Similarly, Alarm 2, Alarm 3 and Alarm 4 will act as dwell timers if 

A2FN, A3FN, or A4FN is set to dtMR. When the dwell timer is configured, the parameter DTMR is used for dwell time adjustment. 

The dwell time is measured in minutes ranging from 0.0 to 4553.6 minutes. The Timer starts to count as soon as the Process Value 

(PV) reaches its set point (SV), and triggers an alarm output once the time has elapsed.

 

 

5.9 User Calibration: User calibration allows the user to offset the permanent factory calibration. There are two parameters: 

Offset Low (OFTL) and Offset High (OFTH) for adjustment to correct an error in the process value. 

There are two parameters for the sensor input.  These two signal values are CALO and CAHI. The input signal low and high values 

are to be entered in the CALO and CAHI parameters respectively.  
Press and hold the 

 key until the setup Menu page is obtained.  Then, press and release the 

 key to navigate to the 

calibration low parameter OFTL. Send your low signal to the sensor input of the controller, then press and release the

 key.  If 

the process value (the upper display) is different from the input signal, the user can use 

and

 keys to change the OFTL 

value (the lower display) until the process value is equal to the value the user needs. Press and hold the 

key for 5 seconds to 

complete the low point calibration.  A similar procedure is applied for high scale calibration. 

As shown below, the two points OFTL and OFTH construct a straight line. For the purpose of accuracy, it is best to calibrate with the 

two points as far apart as possible. After the user calibration is complete, the input type will be stored in the memory. If the input 

type is changed, a calibration error will occur and an error code 

 is displayed.

 

 

 

5.10 Digital Filter: 

In certain applications the process value is too unstable to be read. To improve this, a programmable low pass filter 

incorporated in the controller can be used. This is a first order filter with a time constant specified by the FILT parameter.  A value of 

0.5 seconds is used as a factory default.  Adjust FILT to change the time constant from 0 to 60 seconds.  0 seconds represents no 

filter applied to the input signal.

 

 
5.11 Failure Transfer: 

The controller will enter failure mode if one of the following conditions occurs. 

1.

 

SBER error occurs due to an input sensor break, input current below 1mA for 4-20mA or input voltage below 0.25V for 1-5V. 

2.

 

ADER error occurs due to the A-D converter of the controller fails. Output 1 and Output 2 will perform the failure transfer (O1.ft & 

O2.ft) function as the controller enters failure mode. 

3.

 

Alarm Failure Transfer: An alarm failure transfer is activated as the controller enters failure mode. After that, the alarm output will 

transfer to the ON or OFF state which is determined by the set value of A1FT, A2FT, A3FT, and A4FT. 

 

5.12 Soft-Start: 

The controller has soft start function to limit the control output on out1 and out2 for a programmable time SFT or up to 

a programmed threshold value SFTH. The first of two will terminate soft start function and the normal PID control begins. This 

function is useful for effects such as suppressing the heater output during equipment startup, or lightening the load. 

Note:

 In Profile Version controllers If PFR is set to other than SP1 then the profile function will continue with the set parameter 

during power recovery. If PFR is set to SP1 then the profile will continue to run with soft start parameters during power recovery. 

There are 5 parameters available for soft start function. They are as below. 

1. SFt:

 Soft start time. If SFt 

0, then the Soft start function will be enabled. The SFt can be set in the form of Hour: Minute. The 

range can be set is 00.00 to 99:59. 

2. SFL1:

 Soft Start output limit for output 1. It can be set from PL1L to PL1H. 

3. SFL2:

 Soft Start output limit for output 2. It can be set from PL2L to PL2H. 

4. SFtH:

 Soft start threshold value. The Soft start will be aborted when the process value is greater than or equal to SFtH.  

5. SFtR: 

Soft start time. It will show the remaining time of soft start when it is running. 

Содержание FDC-C22

Страница 1: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 1 of 20 PID Fuzzy Logic Process Controller C22 C62 C82 C83 C72 C42 R22 Quick Operation User Manual UMQOC621A September 2018...

Страница 2: ...rt the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs 2 MENU FLOWCHART 5 Sec 6 2 Sec 7 4 Sec 8 6 Sec 9 8 Sec 5 Sec 5 Sec 2 3 Sec User Menu Setup...

Страница 3: ...2 2 Output Menu oUT Use or key to get oUT in the lower display then use key to enter output menu parameters or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2 O2TY O2FT CYC2 CPB DB PL1L PL1H PL2L PL2H 2 2...

Страница 4: ...parameters or SET PRoF PROF TSP7 RMPU RPT7 STAR SKT7 END TSP8 PFR RPT8 HBLO SKT8 HBHI TSP9 HBT RPT9 CYCL SKT9 CYCR TSPA STEP RPTA TIMR SKTA STAT TSPB TSP1 RPTB RPT1 SKTB SKT1 TSPC TSP2 RPTC RPT2 SKTC...

Страница 5: ...rrent input 0 5V 0 5VDC linear voltage input 1 5V 1 5VDC linear voltage input 0 10 0 10VDC linear voltage input 9 UNIT Input unit selection oC C unit oF F unit Pu Process unit 10 DP Decimal point sele...

Страница 6: ...Relay output SSrd Solid state relay drive output 4 20 4 20mA linear current 0 20 0 20mA linear current 0 5V 0 5VDClinear voltage 1 5V 1 5VDC linear voltage 0 10 0 10VDC linear voltage 30 O2FT Output 2...

Страница 7: ...Output 48 A3FN Alarm 3 function for alarm 3 output NoNE No alarm function dtMR Dwell timer action dE HI Deviation high alarm dE Lo Deviation low alarm db HI Deviation band out of band alarm db Lo Devi...

Страница 8: ...535 71 PROG71 Program code C22 22 XX C62 62 XX C82 82 XX C83 83 XX C72 72 XX C42 42 XX R22 23 XX 72 CMND Command code Low 0 High 65535 73 JOB1 Job code Low 0 High 65535 74 JOB2 Job code Low 0 High 655...

Страница 9: ...A3SP is moved to USER Menu A3dV A3DV is moved to USER Menu A4HY A4HY is moved to USER Menu A4SP A4SP is moved to USER Menu A4dV A4DV is moved to USER Menu PL1L PL1L is moved to USER Menu PL1H PL1H is...

Страница 10: ...ission output Remote SP 1 5V 1 5VDC retransmission output Remote SP 0 10 0 10VDC retransmission output Remote SP A 4 20 Alarm 4 4 20mA retransmission output Remote SP A 0 20 Alarm 4 0 20mA retransmiss...

Страница 11: ...nt for heater short 1 Low 0 0 High 120 0 123 HS2T Triple point current for heater short 2 Low 0 0 High 120 0 124 RMSP Remote SP type None No Remote SP 4 20 4 20mA retransmission output 0 20 0 20mA ret...

Страница 12: ...CoNt Run Profile as RUN CONT PV Run Profile as RUN PV HoLd Run Profile as RUN HOLD StoP Run Profile as RUN STOP 144 E4FN Event input 4 function SP5 SP5 activated to replace SP1 Others Same as E3FN 14...

Страница 13: ...13 of 20 161 222 For Profiler parameters description please refer to full version user manual 4 WIRING DIAGRAM C22 Terminal Connection C62 Terminal Connection C82 C42 Terminal Connection C83 Terminal...

Страница 14: ...MD and A4MD available for each alarm function A1FN A2FN A3FN and A4FN In addition to the alarm output output 2 can also be configured as an alarm But output 2 has only provides 8 different alarm funct...

Страница 15: ...t type will be stored in the memory If the input type is changed a calibration error will occur and an error code is displayed 5 10 Digital Filter In certain applications the process value is too unst...

Страница 16: ...nsmission option installed RELO and REHI are adjusted to specify the low scale and high scale values of retransmission 10 HEATER CURRENT MONITORING A current transformer CT98 1 is required to measure...

Страница 17: ...data to the slave 15 ER15 Communication error write a value which is out of range to a register Do not write an over range data to the slave register 16 EIER Event Input Error Two or more event input...

Страница 18: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 18 of 20 Page Left Intentionally Blank...

Страница 19: ...rnians about significant exposures to chemicals that cause cancer birth defects or other reproductive harm These chemicals can be in the products that Californians purchase in their homes or workplace...

Страница 20: ...s or losses whether direct indirect incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control product...

Отзывы: