14. ERROR CODE: 

Error 

Code 

Display 

Symbol 

Description & Reason 

Corrective Action 

4 ER04 

Illegal setup values used: 

COOL is used for OUT2 

when DIRT (cooling action) is used for OUT1, or 

when PID mode is not used for OUT1 (PB =0 and/or 

TI=0)  

Check and correct setup values of OUT2, PB1, PB2, TI1, 

TI2 and OUT1. IF OUT2 is needed for cooling control, the 

controller should use PID mode (PB

 0 and TI

0) and 

OUT1 should use reverse mode (heating action), otherwise, 

OUT2 cannot be used for cooling control. 

10 

ER10 

Communication error: bad function code 

Correct the communication software to meet the protocol 
requirements. 

11 ER11 

Communication error: 

register address out of range 

Do not issue an over range address of register to the slave. 

14 ER14 

Communication error: 

attempt to write a read only 

data 

Do not write a read only data or a protected data to the 

slave. 

15 ER15 

Communication error:

 write a value which is out of 

range to a register 

Do not write an over range data to the slave register. 

16 EIER 

Event Input Error: 

Two or more event inputs are set 

to the same function 

Do not set the same function in two or more Event Input 

Function parameters (E1FN through E6FN). 

26 ATER 

Auto-Tuning Error:

 Failed to perform auto-tuning 

function 

1. The PID values obtained after auto-tuning process are 

out of range, retry auto-tuning. 

2. Do not change the set point value during auto-tuning 

process. 

3. Use manual tuning instead of auto-tuning process. 

4. Do not set a zero value for TI. 
5. Do not set a zero value for PB. 

6. Touch RESET key. 

29 

EEPR 

EEPROM can't be written correctly 

Return to factory for repair. 

30 CJER Cold junction compensation for Thermocouple 

malfunction 

Return to factory for repair. 

39 SBER 

Input sensor break, or input current below 1mA if 4-

20mA is used, or input voltage below 0.25V if 1-5V is 

used 

Replace input sensor. 

40 

AADER  A to D converter or related component(s) malfunction

Return to factory for repair. 

UMQOC621A SEP 2018 

 

 

Содержание FDC-C22

Страница 1: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 1 of 20 PID Fuzzy Logic Process Controller C22 C62 C82 C83 C72 C42 R22 Quick Operation User Manual UMQOC621A September 2018...

Страница 2: ...rt the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs 2 MENU FLOWCHART 5 Sec 6 2 Sec 7 4 Sec 8 6 Sec 9 8 Sec 5 Sec 5 Sec 2 3 Sec User Menu Setup...

Страница 3: ...2 2 Output Menu oUT Use or key to get oUT in the lower display then use key to enter output menu parameters or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2 O2TY O2FT CYC2 CPB DB PL1L PL1H PL2L PL2H 2 2...

Страница 4: ...parameters or SET PRoF PROF TSP7 RMPU RPT7 STAR SKT7 END TSP8 PFR RPT8 HBLO SKT8 HBHI TSP9 HBT RPT9 CYCL SKT9 CYCR TSPA STEP RPTA TIMR SKTA STAT TSPB TSP1 RPTB RPT1 SKTB SKT1 TSPC TSP2 RPTC RPT2 SKTC...

Страница 5: ...rrent input 0 5V 0 5VDC linear voltage input 1 5V 1 5VDC linear voltage input 0 10 0 10VDC linear voltage input 9 UNIT Input unit selection oC C unit oF F unit Pu Process unit 10 DP Decimal point sele...

Страница 6: ...Relay output SSrd Solid state relay drive output 4 20 4 20mA linear current 0 20 0 20mA linear current 0 5V 0 5VDClinear voltage 1 5V 1 5VDC linear voltage 0 10 0 10VDC linear voltage 30 O2FT Output 2...

Страница 7: ...Output 48 A3FN Alarm 3 function for alarm 3 output NoNE No alarm function dtMR Dwell timer action dE HI Deviation high alarm dE Lo Deviation low alarm db HI Deviation band out of band alarm db Lo Devi...

Страница 8: ...535 71 PROG71 Program code C22 22 XX C62 62 XX C82 82 XX C83 83 XX C72 72 XX C42 42 XX R22 23 XX 72 CMND Command code Low 0 High 65535 73 JOB1 Job code Low 0 High 65535 74 JOB2 Job code Low 0 High 655...

Страница 9: ...A3SP is moved to USER Menu A3dV A3DV is moved to USER Menu A4HY A4HY is moved to USER Menu A4SP A4SP is moved to USER Menu A4dV A4DV is moved to USER Menu PL1L PL1L is moved to USER Menu PL1H PL1H is...

Страница 10: ...ission output Remote SP 1 5V 1 5VDC retransmission output Remote SP 0 10 0 10VDC retransmission output Remote SP A 4 20 Alarm 4 4 20mA retransmission output Remote SP A 0 20 Alarm 4 0 20mA retransmiss...

Страница 11: ...nt for heater short 1 Low 0 0 High 120 0 123 HS2T Triple point current for heater short 2 Low 0 0 High 120 0 124 RMSP Remote SP type None No Remote SP 4 20 4 20mA retransmission output 0 20 0 20mA ret...

Страница 12: ...CoNt Run Profile as RUN CONT PV Run Profile as RUN PV HoLd Run Profile as RUN HOLD StoP Run Profile as RUN STOP 144 E4FN Event input 4 function SP5 SP5 activated to replace SP1 Others Same as E3FN 14...

Страница 13: ...13 of 20 161 222 For Profiler parameters description please refer to full version user manual 4 WIRING DIAGRAM C22 Terminal Connection C62 Terminal Connection C82 C42 Terminal Connection C83 Terminal...

Страница 14: ...MD and A4MD available for each alarm function A1FN A2FN A3FN and A4FN In addition to the alarm output output 2 can also be configured as an alarm But output 2 has only provides 8 different alarm funct...

Страница 15: ...t type will be stored in the memory If the input type is changed a calibration error will occur and an error code is displayed 5 10 Digital Filter In certain applications the process value is too unst...

Страница 16: ...nsmission option installed RELO and REHI are adjusted to specify the low scale and high scale values of retransmission 10 HEATER CURRENT MONITORING A current transformer CT98 1 is required to measure...

Страница 17: ...data to the slave 15 ER15 Communication error write a value which is out of range to a register Do not write an over range data to the slave register 16 EIER Event Input Error Two or more event input...

Страница 18: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 18 of 20 Page Left Intentionally Blank...

Страница 19: ...rnians about significant exposures to chemicals that cause cancer birth defects or other reproductive harm These chemicals can be in the products that Californians purchase in their homes or workplace...

Страница 20: ...s or losses whether direct indirect incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control product...

Отзывы: