Future Design FDC-C22 Скачать руководство пользователя страница 11

FDC_C-Series_Quick_Operation_User_Manual_UMQOC621A.doc Page 

11

 of 

20

 

 
 

 

110 

BAUD 

Baud rate of digital communication 

2K4

: 2.4 Kbits/s baud rate 

4K8:

 4.8 Kbits/s baud rate 

9K6:

 9.6 Kbits/s baud rate 

14K4:

 14.4 Kbits/s baud rate 

19K2:

 19.2 Kbits/s baud rate 

28K8:

 28.8 Kbits/s baud rate 

38K4:

 38.4 Kbits/s baud rate 

57K6: 

57.6 Kbits/s baud rate 

115K: 

115.2 Kbits/s baud rate 

111 

DATA 

Data bit count of digital communication 

7bIt: 

7 data bits

8bIt

:8 data bits

 

112 

PARI 

Parity bit of digital communication 

EVEN:

 Even parity

 

Odd: 

Odd parity

 

NoNE: 

No parity bit

 

113 

STOP 

Stop bit count of digital communication 

1bIt: 

One stop bit

 

2bIt: 

Two stop bits

 

114 

CT1R 

Reading of CT 1 

Low: 0.0  High: 150.0 

115 

CT2R 

Reading of CT 2 

Low: 0.0  High: 150.0 

116 

HBEN 

Enable Heater break detection 

oFF:

 Off   1  

oN:

 On 

117 

HBHY 

Heater break hysteresis 

Low: 0.1  High: 50.0 

118 

HB1T 

Triple point current for heater break 1

Low: 0.0  High: 120.0

119 

HB2T 

Triple point current for heater break 2

Low: 0.0  High: 120.0

120 HSEN  Enable 

Heater 

short 

detection 

oFF:

 Off   1  

oN:

 On 

121 

HSHY 

Heater short hysteresis 

Low: 0.1  High: 50.0 

122 

HS1T 

Triple point current for heater short 1 

Low: 0.0  High: 120.0 

123 

HS2T 

Triple point current for heater short 2

Low: 0.0  High: 120.0

124 

RMSP 

Remote SP type 

None

: No  Remote  SP

4-20:

 4-20mA retransmission output 

0-20:

 0-20mA retransmission output 

0-5V:

 0-5VDC retransmission output 

1-5V:

 1-5VDC retransmission output 

0-10:

 0-10VDC retransmission output 

125 

RINL 

Remote SP Input low scale value 

Low: -19999  High:RINH-50 

126 

RINH 

Remote SP Input high scale value

Low: RINL+50  High:45536 

127 FILE  Default 

File 

Selection 

dFLt:

Default Menu

Ld.Us: 

Load User Setting 

St.Us: 

Store User Setting

 

128 

PV 

Process value 

Low: -19999  High: 45536 

129 

SV 

Current set point value 

Low: SP1L  High: SP1H 

130 

MV1 

Output 1 percentage value (Heating)

Low: 0.00  High: 100.00 

131 

MV2 

Output 2 percentage value (Cooling) 

Low: 0.00  High: 100.00 

132 

PASS 

Password entry 

Low: 0  High: 9999 

133 

CODE 

Security code for parameter protection 

Low: 0  High: 9999 

0 = unprotected  1000 = user mode unprotected  9999=SPx (1 

to 7) unprotected 

134 

OFTL 

Offset value for low point calibration

Low: -1999  High: 1999

135 

OFTH 

Offset value for high point calibration 

Low: -1999  High: 1999 

136 

CALO 

Input signal value during low point calibration 

Low: -19999  High: CAHI-1 

137 

CAHI 

Input signal value during high point calibration 

Low: CALO+1  High: 45536 

138~139 … 

Reserved 

140 PROG Program code 

Same as PROG71

Содержание FDC-C22

Страница 1: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 1 of 20 PID Fuzzy Logic Process Controller C22 C62 C82 C83 C72 C42 R22 Quick Operation User Manual UMQOC621A September 2018...

Страница 2: ...rt the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs 2 MENU FLOWCHART 5 Sec 6 2 Sec 7 4 Sec 8 6 Sec 9 8 Sec 5 Sec 5 Sec 2 3 Sec User Menu Setup...

Страница 3: ...2 2 Output Menu oUT Use or key to get oUT in the lower display then use key to enter output menu parameters or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2 O2TY O2FT CYC2 CPB DB PL1L PL1H PL2L PL2H 2 2...

Страница 4: ...parameters or SET PRoF PROF TSP7 RMPU RPT7 STAR SKT7 END TSP8 PFR RPT8 HBLO SKT8 HBHI TSP9 HBT RPT9 CYCL SKT9 CYCR TSPA STEP RPTA TIMR SKTA STAT TSPB TSP1 RPTB RPT1 SKTB SKT1 TSPC TSP2 RPTC RPT2 SKTC...

Страница 5: ...rrent input 0 5V 0 5VDC linear voltage input 1 5V 1 5VDC linear voltage input 0 10 0 10VDC linear voltage input 9 UNIT Input unit selection oC C unit oF F unit Pu Process unit 10 DP Decimal point sele...

Страница 6: ...Relay output SSrd Solid state relay drive output 4 20 4 20mA linear current 0 20 0 20mA linear current 0 5V 0 5VDClinear voltage 1 5V 1 5VDC linear voltage 0 10 0 10VDC linear voltage 30 O2FT Output 2...

Страница 7: ...Output 48 A3FN Alarm 3 function for alarm 3 output NoNE No alarm function dtMR Dwell timer action dE HI Deviation high alarm dE Lo Deviation low alarm db HI Deviation band out of band alarm db Lo Devi...

Страница 8: ...535 71 PROG71 Program code C22 22 XX C62 62 XX C82 82 XX C83 83 XX C72 72 XX C42 42 XX R22 23 XX 72 CMND Command code Low 0 High 65535 73 JOB1 Job code Low 0 High 65535 74 JOB2 Job code Low 0 High 655...

Страница 9: ...A3SP is moved to USER Menu A3dV A3DV is moved to USER Menu A4HY A4HY is moved to USER Menu A4SP A4SP is moved to USER Menu A4dV A4DV is moved to USER Menu PL1L PL1L is moved to USER Menu PL1H PL1H is...

Страница 10: ...ission output Remote SP 1 5V 1 5VDC retransmission output Remote SP 0 10 0 10VDC retransmission output Remote SP A 4 20 Alarm 4 4 20mA retransmission output Remote SP A 0 20 Alarm 4 0 20mA retransmiss...

Страница 11: ...nt for heater short 1 Low 0 0 High 120 0 123 HS2T Triple point current for heater short 2 Low 0 0 High 120 0 124 RMSP Remote SP type None No Remote SP 4 20 4 20mA retransmission output 0 20 0 20mA ret...

Страница 12: ...CoNt Run Profile as RUN CONT PV Run Profile as RUN PV HoLd Run Profile as RUN HOLD StoP Run Profile as RUN STOP 144 E4FN Event input 4 function SP5 SP5 activated to replace SP1 Others Same as E3FN 14...

Страница 13: ...13 of 20 161 222 For Profiler parameters description please refer to full version user manual 4 WIRING DIAGRAM C22 Terminal Connection C62 Terminal Connection C82 C42 Terminal Connection C83 Terminal...

Страница 14: ...MD and A4MD available for each alarm function A1FN A2FN A3FN and A4FN In addition to the alarm output output 2 can also be configured as an alarm But output 2 has only provides 8 different alarm funct...

Страница 15: ...t type will be stored in the memory If the input type is changed a calibration error will occur and an error code is displayed 5 10 Digital Filter In certain applications the process value is too unst...

Страница 16: ...nsmission option installed RELO and REHI are adjusted to specify the low scale and high scale values of retransmission 10 HEATER CURRENT MONITORING A current transformer CT98 1 is required to measure...

Страница 17: ...data to the slave 15 ER15 Communication error write a value which is out of range to a register Do not write an over range data to the slave register 16 EIER Event Input Error Two or more event input...

Страница 18: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 18 of 20 Page Left Intentionally Blank...

Страница 19: ...rnians about significant exposures to chemicals that cause cancer birth defects or other reproductive harm These chemicals can be in the products that Californians purchase in their homes or workplace...

Страница 20: ...s or losses whether direct indirect incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control product...

Отзывы: