CHT - Ceiling Hinge Telescopic
SLQV
CH-T Contact Closure
- Use an RJ45 connector in the CCI
socket on the control box to operate
via contact closure
LED 1
LED 2
LED 3
LED 4
LED 5
CONTACT CLOSURE INPUT
NOTE:
Earlier versions of the control board
may not have these contact closure
LED indicators.
568A
568B
1
12V SUPPLY
12V SUPPLY - CURRENT LIMITED
W/G
W/O
2
12V LATCH
When 12V attached, device will go OUT to 90 degrees. When
12V removed, device will go IN.
G
O
3
GROUND
GROUND
W/O
W/G
4
PIN 4 NOT USED
BL
BL
5
DEVICE LATCH
Short to GROUND (pin 3), device will go OUT to 90 degrees.
When short removed, device will go IN.
W/BL
W/BL
LED 4
6
DEVICE STOP
Momentary short to GROUND (pin 3), stops device in current
position.
O
G
LED 3
7
DEVICE OUT
Momentary short to GROUND (pin 3), makes device go OUT.
W/BR
W/BR
LED 2
8
DEVICE IN
Momentary short to GROUND (pin 3), makes device go IN.
BR
BR
LED 1
PIN
DESCRIPTION
ACTION
WIRE / CABLE
CONTACT CLOSURE
LED INDICATOR