![Functional Devices FDLR20GV Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/functional-devices/fdlr20gv/fdlr20gv_manual_2346124005.webp)
Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free:
(800) 888-5538
Office:
(765) 883-5538
Fax:
(765) 883-7505
Email:
Website:
www.functionaldevices.com
page 5
Delay Mode
• Typically used with Hotel Room Energy Control (see page 7).
• Activating Delay Mode allows the FDLR product to ignore
temporary
changes in switch states.
• The Delay Mode causes a delay of 10 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also pre
vents the relay from activating following a deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring
window and door contacts that may be briefly opened and then closed. If the contact remains open for longer than 90 seconds the
relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes again, to FLASH, FLASH, FLASH, OFF
(3 flashes).
5. Press and hold the CLR button for 3 seconds until LED flashes
twice
indicating Delay Mode is enabled.
Disabling Delay Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes to FLASH, FLASH,
OFF (2 flashes).
4. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes again, to FLASH,
FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED
flashes
three
times indicating Delay Mode is disabled.
<10s
Off
On
Off
On
>10s
10s
90s
90s
90s
Wireless
Command
Relay
State
Alarm Mode
• Activating Alarm Mode requires all learned contact switches, FDLTMAG, to transmit a CLOSED telegram before
relay will activate. Relay will deactivate if any contact switch transmits an OPEN telegram.
Enabling Alarm Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED flashes
t
wice
indicating Alarm Mode is enabled.
Disabling Alarm Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes to FLASH, FLASH, OFF
(2 flashes).
4. Press and hold the CLR button for 3 seconds until LED
flashes
three
times indicating Alarm Mode is disabled.
393278