Functional Devices FDLR20GV Скачать руководство пользователя страница 5

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068

Toll Free:

  (800)  888-5538   

Office: 

(765)  883-5538                 

Fax: 

(765) 883-7505

Email:

 [email protected]

Website:

 www.functionaldevices.com   

page 5

Delay Mode

•  Typically used with Hotel Room Energy Control (see page 7).
•  Activating Delay Mode allows the FDLR product to ignore 

temporary

 changes in switch states. 

•  The Delay Mode causes a delay of 10 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also pre
    vents the relay from activating following a deactivation for 90 seconds (see Figure 4, below).
•  The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring 
    window and door contacts that may be briefly opened and then closed. If the contact remains open for longer than 90 seconds the 
    relay will deactivate.
•  The ON delay prevents the relay from immediately responding to a closed contact.
•  The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.

Enabling Delay Mode

 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED starts 
     flashing slowly (approximately 1/2 second).
3.  Press and hold LRN button on FDLR product for 3 seconds until 
      LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4.  Press and hold LRN button on FDLR product for 3 seconds until 
      LED pattern changes again, to FLASH, FLASH, FLASH, OFF 
      (3 flashes).
5.  Press and hold the CLR button for 3 seconds until LED flashes 

      twice

 indicating Delay Mode is enabled.

Disabling Delay Mode 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED    
      starts flashing slowly (approximately 1/2 second).
3.  Press and hold LRN button on FDLR product for 3 
      seconds until LED pattern changes to FLASH, FLASH, 
      OFF (2 flashes).
4.  Press and hold LRN button on FDLR product for 3 
      seconds until LED pattern changes again, to FLASH,  
      FLASH, FLASH, OFF (3 flashes).
5.  Press and hold the CLR button for 3 seconds until LED 
      flashes 

three

 times indicating Delay Mode is disabled.

<10s

Off

On

Off

On

>10s

10s

90s

90s

90s

Wireless

Command

Relay

State

Alarm Mode

•  Activating Alarm Mode requires all learned contact switches, FDLTMAG, to transmit a CLOSED telegram before 
   relay will activate. Relay will deactivate if any contact switch transmits an OPEN telegram.

Enabling Alarm Mode 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED starts 
     flashing slowly (approximately 1/2 second).
3.  Press and hold LRN button on FDLR product for 3 seconds until 
      LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4.  Press and hold the CLR button for 3 seconds until LED flashes 

t

      wice

 indicating Alarm Mode is enabled.

Disabling Alarm Mode 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED     
     starts flashing slowly (approximately 1/2 second).
3.  Press and hold LRN button on FDLR product for 3 
     seconds until LED pattern changes to FLASH, FLASH, OFF 
     (2 flashes).
4.  Press and hold the CLR button for 3 seconds until LED   
      flashes 

three

 times indicating Alarm Mode is disabled.

393278

Содержание FDLR20GV

Страница 1: ...link with an FDLR product and be bi directional Relay state at power up can be set to ON OFF or LAST STATE default Each FDLR product can be Linked to up to 30 transmitters of any combination page 1 90...

Страница 2: ...ion Applications 393278 page 2 Lighting Applications Simple Lighting Control FDLR20GV and FDLTS2 or FDLTKEY 60Hz A C Power Yel Org Blk Red FDLR20GV FDLTS2 Rocker Switch or FDLTKEY Keycard Switch Prp G...

Страница 3: ...OFF 2 flashes 4 Press and hold LRN button on FDLR Product for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Insert and remove the card on the switch you are learning t...

Страница 4: ...up Setting Relay State to LAST STATE at Power up Default Mode 1 While device is not powered press and hold the LRN and CLR buttons 2 Power up the device 3 Wait approximately 3 seconds until the LED bl...

Страница 5: ...es 5 Press and hold the CLR button for 3 seconds until LED flashes twice indicating Delay Mode is enabled Disabling Delay Mode 1 Apply power to FDLR product 2 Press and hold LRN button on FDLR product...

Страница 6: ...conds acknowledging telegram reception 6 To learn more FDLTMAG repeat steps 3 5 WDWS EN3 Rocker Switch PTAC unit with RIBWxxxB EN3 in Hotel Room Energy Control Mode in Momentary Mode with Keycard Swit...

Страница 7: ...Sharpsville IN 46068 Toll Free 800 888 5538 Office 765 883 5538 Fax 765 883 7505 Email sales functionaldevices com Website www functionaldevices com Hotel Room Energy Control FDLR Product with FDLTMAG...

Отзывы: