Occupancy / Vacancy Sensor Only Learn Procedure

1.  Charge the Occupancy / Vacancy Sensor per instructions.
2.  Apply power to FDLR product.
3.  Press and hold LRN button on FDLR product until LED starts flashing slowly (approximately 1/2 second).
4.  Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5.  LED on FDLR product will stay ON for 4 seconds acknowledging telegram reception.
6.  Repeat steps 3-5 for additional Occupancy / Vacancy Sensors.

Optional Modes

page 4

•  Relay state after power-up can be set to ON, OFF or LAST STATE
•  Relay state after power-up is LAST STATE by default.

Setting Relay State to OFF at Power-up:
1.  While device is not powered, press and hold the LRN button.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 3 times.
4.  Release the LRN button.
Relay will always be OFF at power-up.

Setting Relay State to ON at Power-up:
1.  While device is not powered, press and hold the CLR button.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 2 times.
4.  Release the CLR button.
Relay will always be ON at power-up.

Setting Relay State to LAST STATE at Power-up: (Default Mode) **
1.  While device is not powered, press and hold the LRN and CLR buttons.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 1 time.
4.  Release the LRN and CLR buttons.
Relay will return to LAST STATE at power-up.

Relay State

•  Activating Repeater Mode allows FDLR product to repeat signals from other EnOcean devices within range. The FDLR product “hears” 
    the signal and echoes it but will not respond to it unless it has been linked to the transmitting device.
•  FDLR product will allow a signal to be repeated up to two times. 

Enabling Repeater Mode 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED starts 
      flashing slowly (approximately 1/2 second).
3.  Press and hold the CLR button for 3 seconds until LED flashes 

      twice

 indicating Repeater Mode is enabled.

Disabling Repeater Mode 

1.  Apply power to FDLR product.
2.  Press and hold LRN button on FDLR product until LED       
      starts flashing slowly (approximately 1/2 second).
3.  Press and hold the CLR button for 3 seconds until LED 
      flashes 

three

 times indicating Repeater Mode is disabled.

Repeater Mode

B.  Auto On:  

FDLR Product and an Occupancy / Vacancy Sensor (FDLTVW  or  FDLTVC)

•  Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
•  It may take up to 2 minutes for the FDLR product to respond to the Occupancy / Vacancy Sensor immediately following Link.
•  Optional mode: Repeater (see page 4)

393278

Содержание FDLR20GV

Страница 1: ...link with an FDLR product and be bi directional Relay state at power up can be set to ON OFF or LAST STATE default Each FDLR product can be Linked to up to 30 transmitters of any combination page 1 90...

Страница 2: ...ion Applications 393278 page 2 Lighting Applications Simple Lighting Control FDLR20GV and FDLTS2 or FDLTKEY 60Hz A C Power Yel Org Blk Red FDLR20GV FDLTS2 Rocker Switch or FDLTKEY Keycard Switch Prp G...

Страница 3: ...OFF 2 flashes 4 Press and hold LRN button on FDLR Product for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Insert and remove the card on the switch you are learning t...

Страница 4: ...up Setting Relay State to LAST STATE at Power up Default Mode 1 While device is not powered press and hold the LRN and CLR buttons 2 Power up the device 3 Wait approximately 3 seconds until the LED bl...

Страница 5: ...es 5 Press and hold the CLR button for 3 seconds until LED flashes twice indicating Delay Mode is enabled Disabling Delay Mode 1 Apply power to FDLR product 2 Press and hold LRN button on FDLR product...

Страница 6: ...conds acknowledging telegram reception 6 To learn more FDLTMAG repeat steps 3 5 WDWS EN3 Rocker Switch PTAC unit with RIBWxxxB EN3 in Hotel Room Energy Control Mode in Momentary Mode with Keycard Swit...

Страница 7: ...Sharpsville IN 46068 Toll Free 800 888 5538 Office 765 883 5538 Fax 765 883 7505 Email sales functionaldevices com Website www functionaldevices com Hotel Room Energy Control FDLR Product with FDLTMAG...

Отзывы: