FT-C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1
Page 14
2
2.9.6
PRESSURISED SYSTEMS
Nitrogen pressurisation may be used to advantage where the total system content is very large or in
a system operating near or above the vapour pressure of the fluid employed or if the inlet of the DA
tank is not the highest point in the piping system.
In conjunction with this system, an automatic venting device must be fitted to the system expansion
tank. Consult Fulton Ltd for further details.
The location for the liquid level switch is a 2 ½” connection on the same end of the tank as the inlet.
The liquid level switch is supplied and shipped with the unit, and must be installed by the customer
and then wired to the control panel.
Note:
If the tank is located outdoors nitrogen pressurisation is required.
Liquid Level
Switch
FIG. 10 LIQUID LEVEL SWITCH
Содержание FT-0080C
Страница 38: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 30...
Страница 80: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 72...
Страница 85: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 77 5...
Страница 86: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 78 5...
Страница 87: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 79 5...
Страница 88: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1 Page 80 5...
Страница 90: ...FT C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1...