Page 17
OPERATION - 3
3.3
FILLING THE FEEDWATER TANk
1.
Isolate the boiler for initial tank fill to prevent the boiler from draining the tank
2. Ensure the tank drain valve is SHUT
3. Ensure Boiler and Pump switches are both in the OFF position
4. Switch the supply main isolator and door isolator to the ON position
5. Check:
a) Circuit live indicator illuminates.
b) Tank Low Water indicator illuminates
c) The fan runs
6. Turn the water supply ON
7. Check:
a)
The tank fills.
b) When working level is reached the Tank Low Water lamp extinguishes
9.
Boiler On/Off Switch
10.
Pump On/Off Switch
In the off position the feedwater pump control circuits are isolated.
11.
Audible Alarm
12.
Feedwater Tank Low Water Indicator
This light will illuminate if there is a low water condition in the feedwater tank.
The boiler feedwater pump will be inhibited until the water level in the tank is restored.
13.
Feedwater Tank Element On/Of Switch (if fitted)
If fitted. The switch is illuminated in the on position and the element is energised.
The switch is not illuminated when element is de-energised.
14.
Feedwater Tank Element Fault Indicator (if fitted)
The feedwater tank element has its own M.C.B. which will activate the indicator and shut down
the electrical supply to the element. It is safe to operate the boiler with the faulty element
switched off providing the faulty element is not allowing water to escape.