Full Gauge PCT-120E plus Скачать руководство пользователя страница 6

F61 - Flow switch validation time:

Operating in rotation, pressurization, or depressurization mode, the flow switch contact is expected to be 
closed as soon as an output is activated (OUT1 or OUT2).

Operating in pressurization or depressurization mode: 

If the flow switch is not triggered during the 

time set in this function, the number of attempts to alert about a lack of flow is increased.

 

Operating in rotation mode: 

If the flow switch is not triggered during the time set in this function, the 

currently active pump is turned off, the number of attempts to alert about a lack of flow is increased and the 
running attempt goes to the other pump.
If the flow switch is not enabled in the “

[f59]

” function, this validation 

Operating mode of digital input 2

will not be run.
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F62 - Number of attempts to alert about lack of flow:

If the number of attempts to alert about a lack of flow set in this function is reached, the outputs are turned 
off and a message on the lack of water flow

 [Flo,]

. In this case, the outputs remain off and the system 

can only be re-established by resetting the rotation (by digital input or pressing the

 >

 key (see item 

6.3.8)).
The number of attempts for each output is reset when the flow switch is closed.

F63 - Cooling fluid:

Allows to define the cooling fluid that will be used in the calculations for superheating, subcooling, floating 
condensation, and floating evaporation.

[,,,1]

- R22

[,,,2]

- R32

[,,,3]

- R134A

[,,,4]

- R290

[,,,5]

- R404A

[,,,6]

- R410A

[,,,7]

- R507

[,,,8]

- R600A

[,,,9]

- R717

[,,10]

- R744

F64 - Superheating calculation:

The superheating control indicates how much gas is above the saturation temperature (boiling point) at a 
certain pressure.
A pressure transducer in the suction line and a temperature sensor at the evaporator outlet or in the 
compressor input (total) is required.

Superheating = suction temperature - saturated vapor temperature (flow curve).

[,,,0]

- Disable

[,,,1]

- Performs the calculation through the P1 pressure transducer and T1 temperature sensor

[,,,2]

- Performs the calculation through the P2 pressure transducer and T2 temperature sensor

[,,,3]

- Performs the calculation through the P1 pressure transducer and T1 temperature sensor and 

turns the OUT1 output off in the event of low superheating or high superheating alarms

[,,,4]

- Performs the calculation through the P2 pressure transducer and T2 temperature sensor and 

turns the OUT2 output off in the event of low superheating or high superheating alarms

Note:

 When a stage is set as an alarm, rotation, control of semi-artesian wells and water tanks or filter 

control,  the  corresponding  output  will  not  be  turned  off  in  the  event  of  a  low  superheating  or  high 
superheating alarm.

F65 - Low superheating alarm:

Temperature limit for indicating a low superheating

 [ASPL]

.

A low superheating indicates a high dosage of cooling fluid in the evaporator, which may damage the 
compressor through the intake of liquid.

F66 - High superheating alarm:

Temperature limit for indicating a high superheating alarm [

ASPh]

.

A high superheating indicates a low dosage of cooling fluid in the evaporator, which may cause high 
temperatures in the compressor through the intake of superheated gas, in addition to reduced evaporator 
capacity and reduced compressor operating life.

F67 - Subcooling calculation:

The subcooling control indicates how much cooling fluid is colder than the condensing temperature 
needed to prevent loss of performance by evaporating the cooling fluid prior to the expansion valve. 
A pressure transducer in the liquid line and a temperature sensor at the condenser outlet is required.

Subcooling = saturated liquid temperature - temperature in the liquid line.

[,,,0]

- Disable

[,,,1]

 - Performs the calculation through the P1 pressure transducer and T1 temperature sensor

[,,,2]

 - Performs the calculation through the P2 pressure transducer and T2 temperature sensor

F68 - Low subcooling alarm:

Temperature threshold for indicating a low subcooling alarm 

[ASbL]

.

A low subcooling indicates a low heat exchange in the evaporator and a risk of flash gas prior to the 
expansion valve.

F69 - High subcooling alarm:

Temperature threshold for indicating a high subcooling alarm 

[Asbh]

.

A subcooling may indicate high pressures in the system.

F70 - Floating condensation control (Dynamic Setpoint):

The  floating  condensation  control  is  intended  to  dynamically  adjust  the  setpoint  according  to  the 
temperature in the external environment, reducing energy consumption and increasing the performance 
coefficient of the system. The setpoint 

[Sp1,]

 is reduced in proportion to a reduction in the external 

temperature. Every 1°C/°F at which the outside temperature is reduced, 1°C/°F in the setpoint is reduced 
or the equivalent in PSI/BAR according to the curve of the fluid saturation pressure.

[,,,1] 

- Control over floating condensation 

using the P1 pressure transducer to measure 

pressure 

discharge pressure and uses the T1 temperature sensor to measure external temperature and 

 

reduce

the 1st stage pressure (

) setpoint

 [Sp1,]

.

depressurization

[,,,2]

 - Control over floating condensation 

using the T1 temperature sensor to measure 

temperature 

the temperature in the output of the condenser and uses the T2 temperature sensor to measure external 
temperature and 

the 1st stage () temperature setpoint 

[Sp1,]

.

reduce 

Note:

 For Floating Condensation Control to work, it is necessary to set the “

[f04]

 - 1st Stage Operation 

Mode (OUT1)" function as Floating Condensation Control. In case of low subcooling alarm

 [ASbL]

, the 

setpoint will return to its original value.

F71 - Floating condensation - Float start temperature

Temperature measured in the external sensor, below which the control of floating condensation begins to 
reduce the setpoint.

If the floating condensation is controlled through pressure, the minimum setpoint is limited by the value 
defined in the “

Minimum setpoint of pressure permitted to the end user OUT1

” function.

[f07]

If the floating condensation is controlled through temperature, the minimum setpoint is limited by the 
value defined in the “

Minimum setpoint of temperature permitted to the end user OUT1

” function.

[f16]

Note:

 The control of floating condensation pressure, this pressure is converted to temperature through 

the saturation of fluid curve.

F72 - Adiabatic condensation - Minimum external temperature (safe level):

Minimum threshold of temperature in the T1 sensor for evaporative condensation control to function. 
When T1 is below this value, the OUT2 output will not be activated (it remains off). 

F73 - Adiabatic condensation - Difference (T1-T2) for starting the pump:

Allows the temperature difference between the external environment sensor (T1) and the sensor after the 
water  curtain  (T2)  to  release  the  passage  of  water  (water  pump  or  valve).  When  the  temperature 
difference (T1-T2) is less than or equal to the value set in this function, the passage of water to the curtain 
is released. Water is sprayed by the pump (or valve) controlled by the OUT2 output reducing the dry-bulb 
temperature of the air passing through the water curtain providing low condensation temperatures in hot 
and dry climates, increasing the efficiency of the system.

F74 - Adiabatic condensation - Difference (T1-T2) for shutting down the pump:

Allows the temperature difference between the external environment sensor (T1) and the sensor after the 
water curtain (T2) to shut the passage of water (water pump or valve). When the temperature difference 
(T1-T2) is higher than or equal to the value set in this function, the passage of water to the curtain is 
blocked.

Note: 

[f37]

In order for the adiabatic condensation control to operate, the “

- 2nd Stage Operating Mode 

(OUT2)”  is  set  as  the  adiabatic  condensation  control  (differential  thermostat)  and  the  T1  and  T2 
temperature sensors are enabled on the digital inputs.

F75 - Floating evaporation (Dynamic Setpoint) - Float start temperature:

Temperature measured in the external sensor, below which the control of floating evaporation begins to 
increase the setpoint.
The maximum setpoint is limited by the value set in the “

Maximum setpoint of pressure permitted 

[f41]

to the end user OUT2

” function.

The  floating  evaporation  control  is  intended  to  dynamically  adjust  the  setpoint  according  to  the 
temperature in the external environment, reducing energy consumption and increasing the performance 
coefficient of the system. The setpoint

 [Sp2,]

 is 

in proportion to a reduction in the external 

elevated 

temperature.  Every  1°C/°F  at  which  the  outside  temperature  is  reduced,  the  1°C/°F  equivalent  is 

elevated 

in PSI/BAR in the setpoint according to the curve of the fluid saturation pressure.

Using the P2 pressure transducer to measure suction pressure and using the T2 temperature sensor to 
measure external temperature and increase the setpoint pressure (depressurization) of the 2nd stage 

[Sp2,]

.

Note:

 

[f37]

In order for the floating condensation control to operate, the “

- 2nd Stage Operating Mode 

(OUT2)” function needs to be set as the pressure (depressurization) floating evaporation control and the
temperature sensors are enabled on the digital inputs. In the event of a high temperature alarm (

 

[At1h]

), the setpoint will return to its original value.

F76 - Activation mode for the P1 pressure alarms:

F77 - Activation mode for the P2 pressure alarms:

F78 - Activation mode for the T1 temperature alarms:

F79 - 

:

Activation mode for the T2 temperature alarms

It enables you to operate the control outputs, turning them off in the event of a pressure (high / low) or 
temperature (high / low) alarm:

Note: 

The OUT2

 

[F37]

.

 

output will not be switched off, in case it is set as as alarm in

[,,,0]

- Don't activate the outputs 

[,,,1]

 - Only activate output OUT1 

[,,,2]

 - Only activate output OUT2 

[,,,3]

 - Activate both outputs

F80 - 

:

Number of times the temperature and pressure alarms wil be automatically reset

Number of times they can be automatically reset within 1 hour.
Whenever possible, the controller will try to correct the problem that set off an alarm. The reset 
system allows the user to configure how many times the controller will attempt to correct the issue 
automatically (automatic reset) before giving up and turning off the output as programmed through the 
functions 

[F76]

to 

[F79]

.

When  the  number  of  automatic  resets  allowed  within  1  hour  is  exceeded,  the  system  displays  the 
message

Interlock alarm, which requires the system to be reset manually.

[AInt]

 - 

To do this, access the quick menu via the key

according to chapter 6. Select

and use a short 

 

;

 [rEAr]

 

press of the 

key to confirm

F81 - Delay time until control is returned after a pressure / temperature alarm goes off:

This is the length of time the controller will keep the output switched off (as programmed using functions 

[F76]

to 

[F79]

) after the automatic correction of a pressure / temperature alarm).

F82 -Function lock mode: 

This allows and configures the function lock (see item 6.3.2).

[,,,0]

 - Does not allow the function lock

[,,,1] 

- It allows a partial lock where the control functions will be locked but the adjustment of the 

setpoint and hysteresis, date views, and maximum and minimum record views are allowed

[,,,2] 

- It allows the full lock, enabling only the date views and maximum and minimum record views

F83 - Time for functions lock:

Allows control functions lock (see item 6.3.2).

[,,15]

[,,60]

 - Defines the time in seconds for the controller to activate.

F84 - Control functions shutdown:

Allows the turning off of the control functions (see item 6.3.3).

[,,,0]

 - Disables the control functions shutdown

[,,,1]

- Enables to activate/deactivate the control functions only if the functions are unlocked

[,,,2]

- Enables to activate/deactivate the control functions even if the functions are locked

F85 -Address of the instrument in the RS-485 network:

Instrument's network address for communicating with Sitrad software.

Note:

 There can be no more than one instrument with the same address on a network.

Содержание PCT-120E plus

Страница 1: ...hands usingtheFGFinderapp ADJUST FOR REQUIRED PRESSURE SETPOINT ADJUST FOR REQUIRED DIFFERENTIAL HISTERESE VIEW HOUR METER RESET HOUR METER SELECT FUNCTION CONTROL FUNCTIONS ON OFF RESET THE SYSTEM EXIT FUNCTION Configurable dry contact Pressure resolution Temperature control range Approximate consumption 1 psi 0 1 bar Temperature resolution 0 1 C 1 F 50 to 200 C 58 to 392 F Power supply Water lev...

Страница 2: ...umentispoweredon initialdelay iscounted 6 3 4 Minimum and Maximum Records Pressing the quick touch key while the pressure temperature is displayed will show the message rEg thentheminimumpressure temperatureandmaximumpressure temperaturerecorded Note If the key is pressed while the records are being displayed the values will be reset and the message rSeT willbedisplayed 6 3 5 Alarm Inhibition A pr...

Страница 3: ...0 50 14 14 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14 5 0 50 50 50 50 50 50 50 0 0 0 10 10 10 10 OUT1 temperature setpoint Pressure Setpoint OUT2 Low subcooling alarm P1 transducer depth offset Maximum temperature setpoint allowed for the end user OUT2 Temperature control differential Hysteresis OUT1 Pressure control differential Hysteresis OUT2 High subcooling alarm Control of semi artesian wells o...

Страница 4: ...sis betweenswitchingcontroloutputONandOFF Example One wants to control the temperature at 4 0 C setpoint with a differential of 1 0 C Consequently the output will be turned off at 4 0 C and turned on again at 5 0 C 4 0 1 0 in cooling mode andtheoutputwillbeturnedoffat4 0 Candturnedonagainat3 C 4 0 1 0 inheatingmode F16 MinimumtemperaturesetpointallowedfortheenduserOUT1 Avoidsregulationofexcessivel...

Страница 5: ...etting F47 OUT2temperaturesetpoint Itisthereferencevalueforthetemperaturecontrol F48 Temperaturecontroldifferential Hysteresis OUT2 Itisthetemperaturedifference hysteresis betweenswitchingcontroloutputONandOFF F49 MinimumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationofexcessivelylowsetpointtemperaturesbymistake F50 MaximumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationof...

Страница 6: ...nimum setpoint is limited by the value definedinthe MinimumsetpointofpressurepermittedtotheenduserOUT1 function f07 If the floating condensation is controlled through temperature the minimum setpoint is limited by the valuedefinedinthe MinimumsetpointoftemperaturepermittedtotheenduserOUT1 function f16 Note The control of floating condensation pressure this pressure is converted to temperature thro...

Страница 7: ...ssory which stores the parameters of controllers At any time It is possible to load new parametersofacontrollerandunloadthemonaproductionline ofthesamecontroller forexample Itisprovidedwiththreetypesofconnectionsforloadingorunloadingtheparameters SerialRS 485 ItisconnectedviaRS 485networktothecontroller onlyforthosecontrollersprovidedwithRS 485 USB ItisconnectedtothecomputerviaUSBport usingtheSitr...

Отзывы: