Full Gauge PCT-120E plus Скачать руководство пользователя страница 4

6.6.1 Description of the parameters

F01 - Access Code:

It  is  required  when  intending  to  change  the  configuration  parameters.  Entering  of  the  code  is  not 
required if the intention is just visualizing the parameters adjusted.
It allows entering of the expected access codes:

[,123]

- Allows access for changing the table parameters

[,231]

- Allows the unit of pressure and temperature measurement to be set

F02 - Display indication mode:

Specify the display preference:

[,,,1]

- Pressure in the transducer P1

[,,,2]

- Pressure in the transducer P2

[,,,3]

- Pressure differential between P1 and P2

[,,,4]

- Depth/height of water level in an mwc

[,,,5]

- Depth/height of water level in relation to surface (in meters)

[,,,6]

- Sensor T1 temperature

[,,,7]

- Sensor T2 temperature

[,,,8]

- Temperature differential between T1 and T2

[,,,9]

- Saturation temperature related to the pressure transducer P1

[,,10]

- Saturation temperature related to the pressure transducer P2

[,,11]

- Superheating temperature

[,,12]

- Subcooling temperature

[,,13]

- Display alternately the P1 transducer pressure and the P2 Transducer pressure

[,,14]

- Display alternately the P1 transducer pressure and the T2 Sensor Temperature

If the measurement is not available (e.g. sensor is disabled), the message 

[Eind] 

will be displayed.

F03 - Delay when powering the instrument on (initial delay):

This  is  the  time  elapsed  from  initialization,  during  which  the  instrument  just  displays  the 
pressure/temperature without activating outputs or validating alarms. In multi-instrument installations, 
spikes in demand can be prevented by assigning different values to this function and causing loads to be
triggered at different times.
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F04 - 1st stage operation mode (OUT1):

[,,,0]

- Depressurization

[,,,1]

- Pressurization

[,,,2]

- Cooling

[,,,3]

- Heating

[,,,4]

- Floating Condensation Control

[,,,5]

- Control for semi-artesian wells and water tanks (pressure control with cyclical timer)

[,,,6]

- Filter control (differential pressure control)

Note: 

In order for OUT1 to operate in cooling or heating modes, the T1 temperature sensor must be

enabled in the “digital input 1 operating mode

'’. 

[F58]

F05 - Pressure Setpoint OUT1:

This is the reference value for pressure control.

F06 - Pressure control differential (Hysteresis) OUT1:

It is the pressure difference (hysteresis) between switching control output ON and OFF.
Example: To control the pressure in 150 PSI (setpoint) with differential of 20 PSI. Therefore, in the 
depressurizing mode, the output will be switched off at 150 PSI and switched back on at 170 PSI (150 + 
20).
In the pressurizing mode, the output will be switched off at 150 PSI and switched back on at 130 PSI (150
- 20).

F07 - Minimum pressure setpoint allowed for the end user OUT1:

Avoids regulation of excessively low setpoint pressures by mistake.

F08 - Maximum pressure setpoint allowed for the end user OUT1:

Avoids regulation of excessively high setpoint pressures by mistake.

F09 - Lower transducer pressure limit P1 (pressure at 4mA):

Pressure applied to the pressure transducer when a 4 mA current in PSI or Bar is displayed in its output.

F10 - Upper transducer pressure limit P1 (pressure at 20mA):

Pressure applied to the pressure transducer when a 20 mA current in PSI or Bar is displayed in its 
output.

Note: 

When the 1st stage operational mode is set to control semi-artesian wells and water tanks, the 

mwc unit is used and the instrument factors in the values for the 

and

positions for the 

[F24] 

 [F25] 

to the pressure sensor limits.

F11 - Transducer pressure offset P1:

Allows to compensate reading differences of the pressure transducer.

F12 - Low pressure in transducer P1 alarm:

F13 - High pressure in transducer P1 alarm:

These are the minimum and maximum values for triggering the pressure alarm in the P1 transducer. If 
these values are exceeded, the instrument displays low pressure

 [Plo1]

 or high pressure

 [Phi1]

messages, but these events only show up in alarms after the time set in the “

[F57]

- Alarm validation 

time

” setting.

F14 - OUT1 temperature setpoint:

It is the reference value for the temperature control.

F15 - Temperature control differential (Hysteresis) OUT1:

It is the temperature difference (hysteresis) between switching control output ON and OFF. 
Example:  One  wants  to  control  the  temperature  at  4.0°C  (setpoint)  with  a  differential  of  1.0°C. 
Consequently, the output will be turned off at 4.0°C and turned on again at 5.0°C (4.0 + 1.0) in cooling 
mode, and the output will be turned off at 4.0°C and turned on again at 3°C (4.0 - 1.0) in heating mode.

F16 - Minimum temperature setpoint allowed for the end user OUT1:

Avoids regulation of excessively low setpoint temperatures by mistake.

F17 - Maximum temperature setpoint allowed for the end user OUT1:

Avoids regulation of excessively high setpoint temperatures by mistake.

F18 - T1 sensor temperature indication offset:

Allows compensating deviations in the sensor temperature reading.

F19 - Low temperature alarm sensor T1:

F20 - High temperature alarm sensor T1:

These are the minimum and maximum values for triggering the temperature alarm in the T1 transducer. 
These alarms are validated only after the time specified in the “Alarm validation time” setting.

F21 - Time for setpoints validation (OUT1):

Upon reaching the setpoint the pressure or temperature must remain in this condition until this time has 
elapsed and then switch off the control output (it avoids overshooting in the pump/compressor activation).
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F22 - Minimum output off time (delay between activations) (OUT1):

It is the minimum time the output will remain off, i.e. the length of time between the last start up and the 
next stop. The main purposes of this function are: minimize interferences in the mains of the facility 
caused by the simultaneous activation of loads and avoid unnecessary activation of loads when there are 
fast variations of pressure in the system.
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F23 - Maximum output operating time OUT1 for maintenance (hourmeter):

Whenever the output is activated the apparatus will count its operating time. When the counted time is 
equal or longer than the one set in this function, the display will show the message

signaling 

 

[Man1]

that the compressor/pump must be serviced.

F24 - Lower pressure limit in mwc of transducer P1 (4 mA):

Water level in (mwc) when the pressure transducer displays a 4 mA current in its output.

F25 -Upper pressure limit in mwc of transducer P1 (20 mA):

Water level in (mwc) when the pressure transducer displays a 20 mA current in its output.

Note:

 Use the conversion table above to properly choose the pressure transducer. Example: for a 200 

PSI transducer, the maximum limit in this function is 140.6 mwc (200 PSI*0.703 = 140.6 mwc).

F26 - P1 transducer depth offset:

Allows to compensate water level reading differences of the pressure transducer.

F27 - Control of semi-artesian wells or water tanks:

Selects the control mode (semi-artesian wells or tanks) if the

1st stage operating mode

 “

[F04]

 

(OUT1)

’’ 

function is set to control semi-artesian wells and water tanks.

[,,,0]

 

Semi-artesian wells control (depressurization with cyclical timer). This mode controls the 

pump for withdrawing water from semi-artesian wells, indicating the water level coming from the P1 
transducer reading.

[,,,1]

 - 

Water tank control (pressurization with cyclical timer). This mode controls the pump for 

supplying water into the tanks, indicating the water level coming from the P1 transducer reading.
Installation examples:

Despressurization

Pressurization

Pressure [ PSI ]

Pressure [ PSI ]

170 PSI

150 PSI

150 PSI

130 PSI

Relay On

Relay On

Se Hysteresis

Setpoint

Setpoint

Setpoint - Hysteresis

Time [S]

Time [S]

Relay Off

Relay Off

Refrigeration

Heating

Temperature [ °C ]

Temperature [ °C ]

5°C

4°C

4°C

3°C

Relay On

Relay On

Se Hysteresis

Setpoint

Setpoint

Setpoint - Hysteresis

Time [S]

Time [S]

Relay  Off

Relay Off

mwc x pressure conversion

1 mca

10,197 bar

0,703 PSI

1 mca

SURFACE

WATER LEVEL

LEVEL READ BY THE
TRANSDUCER

SETPOINT

HYSTERESIS

CRITICAL LEVEL

TRANSDUCER
INSTALLATION LEVEL

WATER LEVEL

DRAWDOWN

LEVEL READ BY THE

TRANSDUCER

TRANSDUCER

INSTALLATION LEVEL

HYSTERESIS: REACTIVATE THE PUMP

HYSTERESIS: REACTIVATE THE PUMP

SETPOINT: PUMP SHUTDOWN

SETPOINT: PUMP SHUTDOWN

CRITICAL LEVEL

SETPOINT

HYSTERESIS

PUMPING LEVEL DEPTH

STATIC WATER LEVEL

PUMP

SEMI-ARTESIAN WELL

WATER TANK

Содержание PCT-120E plus

Страница 1: ...hands usingtheFGFinderapp ADJUST FOR REQUIRED PRESSURE SETPOINT ADJUST FOR REQUIRED DIFFERENTIAL HISTERESE VIEW HOUR METER RESET HOUR METER SELECT FUNCTION CONTROL FUNCTIONS ON OFF RESET THE SYSTEM EXIT FUNCTION Configurable dry contact Pressure resolution Temperature control range Approximate consumption 1 psi 0 1 bar Temperature resolution 0 1 C 1 F 50 to 200 C 58 to 392 F Power supply Water lev...

Страница 2: ...umentispoweredon initialdelay iscounted 6 3 4 Minimum and Maximum Records Pressing the quick touch key while the pressure temperature is displayed will show the message rEg thentheminimumpressure temperatureandmaximumpressure temperaturerecorded Note If the key is pressed while the records are being displayed the values will be reset and the message rSeT willbedisplayed 6 3 5 Alarm Inhibition A pr...

Страница 3: ...0 50 14 14 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14 5 0 50 50 50 50 50 50 50 0 0 0 10 10 10 10 OUT1 temperature setpoint Pressure Setpoint OUT2 Low subcooling alarm P1 transducer depth offset Maximum temperature setpoint allowed for the end user OUT2 Temperature control differential Hysteresis OUT1 Pressure control differential Hysteresis OUT2 High subcooling alarm Control of semi artesian wells o...

Страница 4: ...sis betweenswitchingcontroloutputONandOFF Example One wants to control the temperature at 4 0 C setpoint with a differential of 1 0 C Consequently the output will be turned off at 4 0 C and turned on again at 5 0 C 4 0 1 0 in cooling mode andtheoutputwillbeturnedoffat4 0 Candturnedonagainat3 C 4 0 1 0 inheatingmode F16 MinimumtemperaturesetpointallowedfortheenduserOUT1 Avoidsregulationofexcessivel...

Страница 5: ...etting F47 OUT2temperaturesetpoint Itisthereferencevalueforthetemperaturecontrol F48 Temperaturecontroldifferential Hysteresis OUT2 Itisthetemperaturedifference hysteresis betweenswitchingcontroloutputONandOFF F49 MinimumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationofexcessivelylowsetpointtemperaturesbymistake F50 MaximumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationof...

Страница 6: ...nimum setpoint is limited by the value definedinthe MinimumsetpointofpressurepermittedtotheenduserOUT1 function f07 If the floating condensation is controlled through temperature the minimum setpoint is limited by the valuedefinedinthe MinimumsetpointoftemperaturepermittedtotheenduserOUT1 function f16 Note The control of floating condensation pressure this pressure is converted to temperature thro...

Страница 7: ...ssory which stores the parameters of controllers At any time It is possible to load new parametersofacontrollerandunloadthemonaproductionline ofthesamecontroller forexample Itisprovidedwiththreetypesofconnectionsforloadingorunloadingtheparameters SerialRS 485 ItisconnectedviaRS 485networktothecontroller onlyforthosecontrollersprovidedwithRS 485 USB ItisconnectedtothecomputerviaUSBport usingtheSitr...

Отзывы: