Full Gauge PCT-120E plus Скачать руководство пользователя страница 5

F28 - Setpoint for semi-artesian wells or water tanks:

It is the reference value for controlling the water level. Level (in mwc) where the pump is switched off.

F29 -Hysteresis for semi-artesian wells or water tanks:

The difference in level between the pump switched ON and OFF.

F30 - Transducer P1 installation level for control of wells/tanks:

It is the reference value representing the distance (in meters) from the surface to the depth/height at which 
the P1 transducer is installed.
The value displayed when the display mode is equal to

 [MtrS]

- Depth/height of water level relative to 

the surface (in meters) will be the difference between this level and the water level read by the P1 
transducer.

F31 - Critical water level for control of wells/tanks:

Level (in mwc) at which the low water level alarm is generated

 [Ah2o]

.

If set as the control for the semi-artesian well, the pump is switched off if this level is reached in order to 
prevent the pump from running dry.
This alarm is only generated after the time specified in the “

[F57]

 - 

” setting.

Alarm validation time

F32 - Wells/tanks control time on (cyclical timer):

F33 - Wells/tanks control time off (cyclical timer):

These functions allow the length of time that instrument will control the pump operation to be regulated 
when the “

[F04] 

- 1st stage operating mode (OUT1)

” setting is set to control semi-artesian wells and 

water tanks (pressure switch with cyclical timer).
During the time it's turned on, the pump is controlled by the parameters for the water level setpoint and 
hysteresis. During the time it's turned off, the pump will continuously stay turned off and the level alarm will 
be ignored. This time is needed for the level of the well water to regenerate.
By setting the time to 0 (off), the control will remain constantly active.
Reversing the cyclical timer status can be performed manually through digital input 2 by setting the 

[f59]

 - 

” to reverse the cyclical timer.

Digital input 2 operating mode

F34 - Filter Control - Difference (P1-P2) for starting the pump:

Allows the pressure difference between the filter inlet transducer (P1) and the filter outlet transducer (P2) 
to be set in order to release the passage of liquid (pump or valve). When the pressure difference (P1-P2) 
is less than or equal to the value set in this function, the passage of liquid to the filter is released.

F35 - Filter Control - Difference (P1-P2) for shutting down the pump:

Allows the pressure difference between the filter inlet transducer (P1) and the filter outlet transducer (P2) 
to be set in order to close the passage of liquid (pump or valve). When the pressure difference (P1- P2) is 
higher than or equal to the value set in this function, the passage of liquid to the filter is shut.

F36 -Enable alarm for changing the filter:

Allows the alarm for changing the filter to be enabled.
When the difference (P1-P2) is greater than the value set in the “

[f35]

 - 

Filter Control - Difference (P1-

P2) to turn off the pump

function and remain at this value during the time set in the

Alarm

’’ 

 “

[f57]

Validation Time (OUT1 and OUT2)

function, an alarm

is generated and the instrument remains 

’’ 

 

[AF1L]

 

in this condition until a reset is performed via a digital input. To do this, the “Digital input 1 operating mode” 
function must be set as an alarm reset for changing the filter.

F37 - 2nd stage operation mode (OUT2):

[,,,0]

- Depressurization

[,,,1]

- Pressurization

[,,,2]

- Cooling

[,,,3]

- Heating

[,,,4]

- Rotation

[,,,5]

- Alarm

[,,,6]

- Adiabatic condensation control (differential thermostat)

[,,,7]

- Pressure floating evaporation control (depressurization)

[Off,]

- Off output

Nota¹: 

In order for OUT2 to operate in cooling or heating modes, the T2 temperature sensor must be 

enabled in the “

[f59] 

- Digital input 2 operating mode'’.

Nota²: 

[,,,5]

- Alarm

 - 

The output will be triggered if there is any alarm

F38 - Pressure Setpoint OUT2:

This is the reference value for pressure control.

F39 -Pressure control differential (Hysteresis) OUT2:

It is the pressure difference (hysteresis) between switching control output ON and OFF.

F40 - Minimum pressure setpoint allowed for the end user OUT2:

Avoids regulation of excessively low setpoint pressures by mistake.

F41 - Maximum pressure setpoint allowed for the end user OUT2:

Avoids regulation of excessively high setpoint pressures by mistake.

F42 -Lower transducer pressure limit P2 (pressure at 4mA):

Pressure applied to the pressure sensor when the output current is 4 mA.

F43 - Upper transducer pressure limit P2 (pressure at 20mA):

Pressure applied to the pressure sensor when the output current is 20 mA.

F44 -Transducer pressure offset P2:

Allows variants in the transducer pressure reading to be compensated.

F45 - Low pressure in transducer P2 alarm:

F46 - High pressure in transducer P2 alarm:

These are the minimum and maximum values for triggering the pressure alarm in the P2 transducer.
If these values are exceeded, the instrument displays low pressure 

[Plo2] 

or high pressure 

[Phi2]

messages, but these events only show up in alarms after the time set in the “

[f57]

 - 

TAlarm validation 

time

” setting.

F47 - OUT2 temperature setpoint:

It is the reference value for the temperature control.

F48 - Temperature control differential (Hysteresis) OUT2:

It is the temperature difference (hysteresis) between switching control output ON and OFF.

F49 - Minimum temperature setpoint allowed for the end user OUT2:

Avoids regulation of excessively low setpoint temperatures by mistake.

F50 - Maximum temperature setpoint allowed for the end user OUT2:

Avoids regulation of excessively high setpoint temperatures by mistake.

F51 - T2 sensor temperature indication offset:

Allows compensating deviations in the sensor temperature reading.

F52 - Low temperature alarm sensor T2:

F53 - High temperature alarm sensor T2:

These are the minimum and maximum values for triggering the temperature alarm in the T2 transducer.
These alarms are validated only after the time specified in the “

Alarm validation time

” setting

[f57]

F54 - Time for setpoints validation (OUT2):

Upon reaching the setpoint the pressure or temperature must remain in this condition until this time has 
elapsed  and  then  switch  off  the  control  output  (it  avoids  overshooting  in  the  pump/compressor 
activation)..
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F55 -Minimum output off time (delay between activations) (OUT2):

It is the minimum time the output will remain off, i.e. the length of time between the last start up and the 
next stop. The main purposes of this function are: minimize interferences in the mains of the facility 
caused by the simultaneous activation of loads and avoid unnecessary activation of loads when there are 
fast variations of pressure in the system.
This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F56 - Maximum output operating time OUT2 for maintenance (hourmeter):

Whenever the output is activated, the apparatus will count its operating time. When the counted time is 
equal or longer than the one set in this function, the display will show the message 

[Man2]

, signaling 

that the compressor/pump must be serviced.

F57 - Alarm Validation Time (OUT1 and OUT2):

This is the time that a (pressure or temperature) alarm will remain disabled even in alarm conditions.
This inhibition time starts to be counted after the power on delay expires.
A low pressure (

[Plo1]

 or 

[Plo2]

) and high pressure (

[Phi1] 

or 

[Phi2]

) event needs to remain 

in this condition for the time set in this function so that the instrument can generate low pressure (

[AP1L]

 

or

 [AP2L]

) and high pressure (

[AP1h]

 or

 [Ap2h]

) alarms.

The low temperature (

[At1L] 

and 

[At2L]

), high temperature (

[At1h]

 and 

[At2h]

), subcooling 

(

[ASbL]

 and 

[Asbh]

), superheating (

[ASPL]

 and 

[ASPh]

),filter change (

[Af1l]

) alarms and 

low water level alarm

 [ALLo]

, are also validated only in the time set in this function.

The external alarms for the digital inputs (

[din1]

 and 

[din2]

), do not have a time for validation.

If an alarm is inhibited by the user (by pressing the 

>

 key for two seconds), this time is reset.

This function can be disabled by adjusting it to the minimum value 0 

[no,,]

.

F58 - Operating mode of the digital input 1:

It allows choosing the operating mode of the digital input 1.

[,,,0]

- Disable

[,,,1]

- Temperature sensor 1

[,,,2]

- Enables 1st stage control (OUT1) (external switch, N.O. contact)

[,,,3]

- Enables 1st stage control (OUT1) (external switch, N.C. contact)

[,,,4]

- Time reset for rotation and choice of output (pulser, N.O. contact)

[,,,5]

- Time reset for rotation and choice of output (pulser, N.C. contact)

[,,,6]

- External alarm 

[din1]

 functioning in the OUT1 output turning it off (N.O. contact)

[,,,7]

- External alarm 

[din1]

 functioning in the OUT1 output turning it off (N.C. contact)

[,,,8]

- Alarm reset for filter change (pulser, N.O. contact)

[,,,9]

- Alarm reset for filter change (pulser, N.C. contact)

[,,10]

- Inhibition of alarms (N.O. contact)

[,,11]

- Inhibition of alarms (N.C. contact)

[,,12]

- Switch off the controller (contact N.O)

[,,13]

- Switch off the controller (contact N.C)

F59 - Operating mode of the digital input 2:

It allows choosing the operating mode of the digital input 2.

[,,,0]

- Disable

[,,,1]

- Temperature sensor 2

[,,,2]

- Enables 1st stage control (OUT2) (external switch, N.O. contact)

[,,,3]

- Enables 1st stage control (OUT2) (external switch, N.C. contact)

[,,,4]

- Flow switch (N.O. contact)

[,,,5]

- Flow switch (N.C. contact)

[,,,6]

- External alarm 

[din2]

 functioning in the OUT2 output turning it off (N.O. contact)

[,,,7]

- External alarm 

[din2]

 functioning in the OUT2 output turning it off (N.C. contact)

[,,,8]

- Reverses the state of the cyclical timer (pulser, N.O. contact)

[,,,9]

- Reverses the state of the cyclical timer (pulser, N.C. contact)

[,,10]

- Inhibition of alarms (N.O. contact)

[,,11]

- Inhibition of alarms (N.C. contact)

[,,12]

- Switch off the controller (contact N.O)

[,,13]

- Switch off the controller (contact N.C)

F60 -Rotation time between OUT1 and OUT2:

If the “

[f37]

 - 

’’ function is set to rotate, the OUT2 output will operate 

2nd stage (OUT2) operating mode

as a backup for the OUT1 output, thus activation of the outputs will alternate over time causing each pump 
to work for a certain time and accumulate similar usage times.
After the time set in this function is exceeded, the control output will be alternated in the 

next cycle.

Note:

 If the “

[f37]

- 2nd stage (OUT2) operating mode” function is set to rotate, the control parameters

(pressure, temperature and alarms) related to the 2nd stage will be ignored, because OUT2 control will be 
related to the 1st stage parameters.

Содержание PCT-120E plus

Страница 1: ...hands usingtheFGFinderapp ADJUST FOR REQUIRED PRESSURE SETPOINT ADJUST FOR REQUIRED DIFFERENTIAL HISTERESE VIEW HOUR METER RESET HOUR METER SELECT FUNCTION CONTROL FUNCTIONS ON OFF RESET THE SYSTEM EXIT FUNCTION Configurable dry contact Pressure resolution Temperature control range Approximate consumption 1 psi 0 1 bar Temperature resolution 0 1 C 1 F 50 to 200 C 58 to 392 F Power supply Water lev...

Страница 2: ...umentispoweredon initialdelay iscounted 6 3 4 Minimum and Maximum Records Pressing the quick touch key while the pressure temperature is displayed will show the message rEg thentheminimumpressure temperatureandmaximumpressure temperaturerecorded Note If the key is pressed while the records are being displayed the values will be reset and the message rSeT willbedisplayed 6 3 5 Alarm Inhibition A pr...

Страница 3: ...0 50 14 14 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14 5 0 50 50 50 50 50 50 50 0 0 0 10 10 10 10 OUT1 temperature setpoint Pressure Setpoint OUT2 Low subcooling alarm P1 transducer depth offset Maximum temperature setpoint allowed for the end user OUT2 Temperature control differential Hysteresis OUT1 Pressure control differential Hysteresis OUT2 High subcooling alarm Control of semi artesian wells o...

Страница 4: ...sis betweenswitchingcontroloutputONandOFF Example One wants to control the temperature at 4 0 C setpoint with a differential of 1 0 C Consequently the output will be turned off at 4 0 C and turned on again at 5 0 C 4 0 1 0 in cooling mode andtheoutputwillbeturnedoffat4 0 Candturnedonagainat3 C 4 0 1 0 inheatingmode F16 MinimumtemperaturesetpointallowedfortheenduserOUT1 Avoidsregulationofexcessivel...

Страница 5: ...etting F47 OUT2temperaturesetpoint Itisthereferencevalueforthetemperaturecontrol F48 Temperaturecontroldifferential Hysteresis OUT2 Itisthetemperaturedifference hysteresis betweenswitchingcontroloutputONandOFF F49 MinimumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationofexcessivelylowsetpointtemperaturesbymistake F50 MaximumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationof...

Страница 6: ...nimum setpoint is limited by the value definedinthe MinimumsetpointofpressurepermittedtotheenduserOUT1 function f07 If the floating condensation is controlled through temperature the minimum setpoint is limited by the valuedefinedinthe MinimumsetpointoftemperaturepermittedtotheenduserOUT1 function f16 Note The control of floating condensation pressure this pressure is converted to temperature thro...

Страница 7: ...ssory which stores the parameters of controllers At any time It is possible to load new parametersofacontrollerandunloadthemonaproductionline ofthesamecontroller forexample Itisprovidedwiththreetypesofconnectionsforloadingorunloadingtheparameters SerialRS 485 ItisconnectedviaRS 485networktothecontroller onlyforthosecontrollersprovidedwithRS 485 USB ItisconnectedtothecomputerviaUSBport usingtheSitr...

Отзывы: