 6. OPERATIONS

6.1 Quick Access Menu Map

To access or browse the quick access menu, use the  

;

key (quick touch) while the controller is displaying the pressure. 

Each touch displays the next function in the list

 ;

 to confirm, use the 

/

key (quick touch).

 1. DESCRIPTION

The 

PCT-120e 

plus

 is an easy to install and operate two-stage pressure controller designed for 

systems  that  require  effective  pressure  control.  Operating  in  pressurization,  despressurization, 
refrigeration, heating or alarm mode, it directly controls loads of up to 1HP. It also has digital inputs that 
allow external devices to be used for protecting the controller system, hourmeters that store the number 
of hours compressors/pumps are operating and indicate when maintanance should be performed on 
them.  Operating  in  combination  with  temperature  sensors,  it  also  performs  dynamic  and  adiabatic 
condensation  control,  dynamic  evaporation,  superheating  and  subcooling  monitoring,  promoting 
greater energy efficiency in the system. It also has serial output for communication with Sitrad and an 
intelligent locking function, preventing unauthorized persons from changing the control parameters.

 2. APPLICATIONS

  

• 

Control over suction or discharge in refrigeration systems, air compressors, semi-artesian pumps, 

water tanks and filters, superheating and subcooling monitoring.

evolution

 

 

DIGITAL PRESSURE CONTROLLER

AND INDICATOR

Ver

.02

PCT-120

plus

PCT-120

plus

PCT-120

el

 

plus 12v

PCT-120

el

 

plus 24v

5. INSTALLATIONS - PANEL AND ELECTRIC CONNECTIONS

3. TECHNICAL SPECIFICATIONS

Panel 

(Side view)

71 

 mm

± 0,5

29 

 mm

± 0,5 

Panel (Front view)

Dimensions of the clip
for fixing the instrument

WARNING

FOR INSTALLATIONS THAT REQUIRE WATER TIGHTNESS, THE OPENING TO INSTALL THE CONTROLLER MUST BE 71,5 x 29,5 mm
(28,15 x 11,6 in) MAXIMUM. THE SIDE LATCHES MUST BE FIXED SO THAT THEY PRESS THE SEALING GASKET TO PREVENT 
INFILTRATION BETWEEN THE OPENING AND THE CONTROLLER.

IMPORTANT

3/32''(2.4mm) SLOTTED SCREWDRIVER FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
PHILLIPS SCREWDRIVER

FOR ADJUSTMENTS AT THE POWER TERMINALS.

 #1 

IT  IS  ESSENTIAL  TO  USE  THE  CORRECT  TOOLS  IN  ORDER  TO  AVOID  DAMAGES  TO  THE  INSTRUMENT'S  CONNECTION 
TERMINALS:

Have this manual in your hands 

using the 

FG Finder 

app.

ADJUST FOR REQUIRED
PRESSURE (SETPOINT)

;

;

ADJUST  FOR  REQUIRED
DIFFERENTIAL (HISTERESE)

;

VIEW HOUR METER

;

RESET HOUR METER

SELECT FUNCTION

;

;

CONTROL FUNCTIONS 
(ON/OFF)

;

RESET THE SYSTEM

EXIT FUNCTION

;

Configurable dry contact

Pressure resolution

Temperature control range 

Approximate consumption 

1 psi / 0,1 bar

Temperature resolution

0,1°C / 1°F

-50 to 200°C / -58 to 392°F

Power supply

Water level resolution

 

Operating temperature

Maximum current

 

Operating humidity

 

Product dimensions

 

Digital Inputs

  

0,1 mca

0 to 60°C / 32 to 140°F

10 to 90% UR (no condensation)

76 x 34 x 77 mm (W x H x D) (2,99 x 1,33 x 3,03'’)

IP 65 (frontal)

Protection level

Dimensions of the clip for fixing the instrument

71   0,5 x 29    0,5 mm (2,80 x 0,01 x 1,14 x 0,01'’)

Pressure control range 

Water level control range

Sensors available for acquisition 

PCT-120E Plus:
PCT-120EL Plus

 

12Vac/dc: 

   

PCT-120EL Plus

 

24Vac/dc: 

   

90~240Vac (50/60 Hz) 

12Vac/dc 10% (50/60 Hz) 
24Vac/dc 10% (50/60 Hz) 

±

±

-14 to 850 psi / -1 to 58.6 bar (configurable sensor
operating range)

0 to 250 mwc (configurable sensor operating range)

OUT1: 16A / 1HP 250Vac
OUT2: 16A / 1HP 250Vac

SB69 - 100A* (0 a 100 psi / 0 a 6,9 bar)
SB69 - 200A* (0 a 200 psi / 0 a 13,8 bar)
SB69 - 500A* (0 a 500 psi / 0 a 34,4 bar)
SB69 - 850A* (0 a 850 psi / 0 a 58,7 bar)
SB70* - (-50 a 105°C / -58 a 221°F)
SB59* - (-50 a 200°C / -58 a 392°F)
*Sensors sold separately

PCT-120

plus

PCT-120

plus

 

5.1 INSTALLATION - ELECTRIC CONNECTIONS

;

FUNCTION LOCK

 4VA

±

4. INDICATORS AND KEYS

Led indicator (pressure units: psi/bar)

PCT-120

plus

Upper key

Lower key

Set key

Quick Access

Menu key

Temperature unit indication LED

Water level unit indication LED (mwc)

Led indicator (output 2 on/off)

Led indicator (output 1 on/off)

P B

2

m

Control

Functions
Shutdown

Functions

Lock

Serial

Programming

Protection

Level

IP 65

FRONT

Hourmeter

Supervisory

System

Electrical  connection  of  pressure 
sensors:
Brown: 12Vdc
Green or White: 4~20mA

E l e c t r i c a l   c o n n e c t i o n   o f 
temperature sensors/digital inputs:
D1/T1: Pins 4-8
D2/T2: Pins 7-8

GREEN OR WHITE

GREEN OR WHITE

GREEN OR WHITE

GREEN OR WHITE

BROWN

BROWN

GREEN OR WHITE

GREEN OR WHITE

BROWN

+12VDC

+12VDC

+12VDC

D1/T1

D1/T1

D1/T1

D2/T2

D2/T2

GND

GND

12Vac/dc

24Vac/dc

Power supply

Power supply

SITRAD

SITRAD

D2/T2

P1

P1

P1

P2

P2

P2

SITRAD

GND

90~240Vac

16A 1HP

16A 1HP

16A 1HP

16A 1HP

16A 1HP

90~240 Vac Connection

12 Vac/dc Connection

24 Vac/dc Connection

16A 1HP

Содержание PCT-120E plus

Страница 1: ...hands usingtheFGFinderapp ADJUST FOR REQUIRED PRESSURE SETPOINT ADJUST FOR REQUIRED DIFFERENTIAL HISTERESE VIEW HOUR METER RESET HOUR METER SELECT FUNCTION CONTROL FUNCTIONS ON OFF RESET THE SYSTEM EXIT FUNCTION Configurable dry contact Pressure resolution Temperature control range Approximate consumption 1 psi 0 1 bar Temperature resolution 0 1 C 1 F 50 to 200 C 58 to 392 F Power supply Water lev...

Страница 2: ...umentispoweredon initialdelay iscounted 6 3 4 Minimum and Maximum Records Pressing the quick touch key while the pressure temperature is displayed will show the message rEg thentheminimumpressure temperatureandmaximumpressure temperaturerecorded Note If the key is pressed while the records are being displayed the values will be reset and the message rSeT willbedisplayed 6 3 5 Alarm Inhibition A pr...

Страница 3: ...0 50 14 14 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 14 5 0 50 50 50 50 50 50 50 0 0 0 10 10 10 10 OUT1 temperature setpoint Pressure Setpoint OUT2 Low subcooling alarm P1 transducer depth offset Maximum temperature setpoint allowed for the end user OUT2 Temperature control differential Hysteresis OUT1 Pressure control differential Hysteresis OUT2 High subcooling alarm Control of semi artesian wells o...

Страница 4: ...sis betweenswitchingcontroloutputONandOFF Example One wants to control the temperature at 4 0 C setpoint with a differential of 1 0 C Consequently the output will be turned off at 4 0 C and turned on again at 5 0 C 4 0 1 0 in cooling mode andtheoutputwillbeturnedoffat4 0 Candturnedonagainat3 C 4 0 1 0 inheatingmode F16 MinimumtemperaturesetpointallowedfortheenduserOUT1 Avoidsregulationofexcessivel...

Страница 5: ...etting F47 OUT2temperaturesetpoint Itisthereferencevalueforthetemperaturecontrol F48 Temperaturecontroldifferential Hysteresis OUT2 Itisthetemperaturedifference hysteresis betweenswitchingcontroloutputONandOFF F49 MinimumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationofexcessivelylowsetpointtemperaturesbymistake F50 MaximumtemperaturesetpointallowedfortheenduserOUT2 Avoidsregulationof...

Страница 6: ...nimum setpoint is limited by the value definedinthe MinimumsetpointofpressurepermittedtotheenduserOUT1 function f07 If the floating condensation is controlled through temperature the minimum setpoint is limited by the valuedefinedinthe MinimumsetpointoftemperaturepermittedtotheenduserOUT1 function f16 Note The control of floating condensation pressure this pressure is converted to temperature thro...

Страница 7: ...ssory which stores the parameters of controllers At any time It is possible to load new parametersofacontrollerandunloadthemonaproductionline ofthesamecontroller forexample Itisprovidedwiththreetypesofconnectionsforloadingorunloadingtheparameters SerialRS 485 ItisconnectedviaRS 485networktothecontroller onlyforthosecontrollersprovidedwithRS 485 USB ItisconnectedtothecomputerviaUSBport usingtheSitr...

Отзывы: