6. OPERATIONS
6.1 Quick Access Menu Map
To access or browse the quick access menu, use the
;
key (quick touch) while the controller is displaying the pressure.
Each touch displays the next function in the list
;
to confirm, use the
/
key (quick touch).
1. DESCRIPTION
The
PCT-120e
plus
is an easy to install and operate two-stage pressure controller designed for
systems that require effective pressure control. Operating in pressurization, despressurization,
refrigeration, heating or alarm mode, it directly controls loads of up to 1HP. It also has digital inputs that
allow external devices to be used for protecting the controller system, hourmeters that store the number
of hours compressors/pumps are operating and indicate when maintanance should be performed on
them. Operating in combination with temperature sensors, it also performs dynamic and adiabatic
condensation control, dynamic evaporation, superheating and subcooling monitoring, promoting
greater energy efficiency in the system. It also has serial output for communication with Sitrad and an
intelligent locking function, preventing unauthorized persons from changing the control parameters.
2. APPLICATIONS
•
Control over suction or discharge in refrigeration systems, air compressors, semi-artesian pumps,
water tanks and filters, superheating and subcooling monitoring.
evolution
DIGITAL PRESSURE CONTROLLER
AND INDICATOR
Ver
.02
PCT-120
e
plus
PCT-120
e
plus
PCT-120
el
plus 12v
PCT-120
el
plus 24v
5. INSTALLATIONS - PANEL AND ELECTRIC CONNECTIONS
3. TECHNICAL SPECIFICATIONS
Panel
(Side view)
71
mm
± 0,5
29
mm
± 0,5
Panel (Front view)
Dimensions of the clip
for fixing the instrument
WARNING
FOR INSTALLATIONS THAT REQUIRE WATER TIGHTNESS, THE OPENING TO INSTALL THE CONTROLLER MUST BE 71,5 x 29,5 mm
(28,15 x 11,6 in) MAXIMUM. THE SIDE LATCHES MUST BE FIXED SO THAT THEY PRESS THE SEALING GASKET TO PREVENT
INFILTRATION BETWEEN THE OPENING AND THE CONTROLLER.
IMPORTANT
3/32''(2.4mm) SLOTTED SCREWDRIVER FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
PHILLIPS SCREWDRIVER
FOR ADJUSTMENTS AT THE POWER TERMINALS.
#1
IT IS ESSENTIAL TO USE THE CORRECT TOOLS IN ORDER TO AVOID DAMAGES TO THE INSTRUMENT'S CONNECTION
TERMINALS:
Have this manual in your hands
using the
FG Finder
app.
ADJUST FOR REQUIRED
PRESSURE (SETPOINT)
;
;
ADJUST FOR REQUIRED
DIFFERENTIAL (HISTERESE)
;
VIEW HOUR METER
;
RESET HOUR METER
SELECT FUNCTION
;
;
CONTROL FUNCTIONS
(ON/OFF)
;
RESET THE SYSTEM
EXIT FUNCTION
;
Configurable dry contact
Pressure resolution
Temperature control range
Approximate consumption
1 psi / 0,1 bar
Temperature resolution
0,1°C / 1°F
-50 to 200°C / -58 to 392°F
Power supply
Water level resolution
Operating temperature
Maximum current
Operating humidity
Product dimensions
Digital Inputs
0,1 mca
0 to 60°C / 32 to 140°F
10 to 90% UR (no condensation)
76 x 34 x 77 mm (W x H x D) (2,99 x 1,33 x 3,03'’)
IP 65 (frontal)
Protection level
Dimensions of the clip for fixing the instrument
71 0,5 x 29 0,5 mm (2,80 x 0,01 x 1,14 x 0,01'’)
Pressure control range
Water level control range
Sensors available for acquisition
PCT-120E Plus:
PCT-120EL Plus
12Vac/dc:
PCT-120EL Plus
24Vac/dc:
90~240Vac (50/60 Hz)
12Vac/dc 10% (50/60 Hz)
24Vac/dc 10% (50/60 Hz)
±
±
-14 to 850 psi / -1 to 58.6 bar (configurable sensor
operating range)
0 to 250 mwc (configurable sensor operating range)
OUT1: 16A / 1HP 250Vac
OUT2: 16A / 1HP 250Vac
SB69 - 100A* (0 a 100 psi / 0 a 6,9 bar)
SB69 - 200A* (0 a 200 psi / 0 a 13,8 bar)
SB69 - 500A* (0 a 500 psi / 0 a 34,4 bar)
SB69 - 850A* (0 a 850 psi / 0 a 58,7 bar)
SB70* - (-50 a 105°C / -58 a 221°F)
SB59* - (-50 a 200°C / -58 a 392°F)
*Sensors sold separately
PCT-120
e
plus
PCT-120
e
plus
5.1 INSTALLATION - ELECTRIC CONNECTIONS
;
FUNCTION LOCK
4VA
±
4. INDICATORS AND KEYS
Led indicator (pressure units: psi/bar)
PCT-120
e
plus
Upper key
Lower key
Set key
Quick Access
Menu key
Temperature unit indication LED
Water level unit indication LED (mwc)
Led indicator (output 2 on/off)
Led indicator (output 1 on/off)
P B
2
m
Control
Functions
Shutdown
Functions
Lock
Serial
Programming
Protection
Level
IP 65
FRONT
Hourmeter
Supervisory
System
Electrical connection of pressure
sensors:
Brown: 12Vdc
Green or White: 4~20mA
E l e c t r i c a l c o n n e c t i o n o f
temperature sensors/digital inputs:
D1/T1: Pins 4-8
D2/T2: Pins 7-8
GREEN OR WHITE
GREEN OR WHITE
GREEN OR WHITE
GREEN OR WHITE
BROWN
BROWN
GREEN OR WHITE
GREEN OR WHITE
BROWN
+12VDC
+12VDC
+12VDC
D1/T1
D1/T1
D1/T1
D2/T2
D2/T2
GND
GND
12Vac/dc
24Vac/dc
Power supply
Power supply
SITRAD
SITRAD
D2/T2
P1
P1
P1
P2
P2
P2
SITRAD
GND
90~240Vac
16A 1HP
16A 1HP
16A 1HP
16A 1HP
16A 1HP
90~240 Vac Connection
12 Vac/dc Connection
24 Vac/dc Connection
16A 1HP