4. INDICATIONS AND KEYS

6.2 Quick access keys map

When the controller is displaying the voltages, it is possible to access the some controller functions by 
quickly pressing the folowing keys:

<

<

Quick touch: Measures display

Quick touch: Display of minimum and maximum voltages of each voltage

Hold for 1 second to access the main menu

6.3 Basic operations
6.3.1Functions Lockdown

For safety reasons, this controller provides the ability to lock the function adjustment. With this feature 
activated, the parameters are protected against tampering; however they can still be visualized. 
If a user tries to change a parameter value while the functions lockdown is active, the message 

[LOC,]

 

will appear on the display. To enable the functions lockdown, the function “

[,F21]

 

- Time for functions 

lockdown”

 must be set to a value greater than 14 (if the user tries to decrease it to a value smaller  than 

15, the message

 [no,,]

 will be displayed, indicating that this feature will be disabled. Once the 

functions lockdown is enabled, to activate it the user must press the key 

;

 (short touch) and select

 

[LOC,]

,  press 

/

  (short  touch)  to  confirm,  then  hold  the  key 

>

  until  the  message

 [LOC,] 

appears. When the key is released, the message 

[On,,]

will be shown on the display.

To unlock, turn off the controller and turn it back on while holding the key 

>

. Keep the key pressed until 

the message 

[LOC,]

 appears. When the key is released, the message

 [Off,]

 will be shown on the 

display.

1. DESCRIPTION

The 

PhaseLog

plus

 is an instrument for monitoring and protection of electrical equipment for 

industrial, commercial and residential facilities.

Through  the  method  of True  RMS*  voltage  measurement,  the 

PhaseLog

plus

  also  monitors 

power quality and protects mono / bi / three phase loads against: under and over voltage, angular 
asymmetry,  modular  asymmetry,  phase  loss  and  phase  sequence  inversionThe  internal  datalogger 
stores the voltages of each phase of the electrical grid during periods of time determined by the user. 
Time  and  date  of  each  sample  is  stored  as  well  (internal  real-time  clock).  All  functions  of  the        

PhaseLog

plus

 can be changed through the software SITRAD®, which can be acessed through 

the  internet  (computer/iOS/Android).  This  software  is  also  used  to  retrieve  the  data  stored  in  its 
datalogger. 
*True RMS: Real voltage value (Root Mean Square), values evaluated taking into consideration the 
contribution of the high frequency noise on the network (harmonic distortion). That's the real voltage 
being perceived by the connected load (i.e. motors, compressors, etc). Using this method, it is possible 
to accurately measure the voltage at any waveform, whereas the traditional methods are only able to 
measure correctly pure sine waveforms.

 2. APPLICATION

              

• Energy quality monitoring
• Motors protection
• Electrical panels protection
• Other multiphase equipments protection      

 3. TECHNICAL SPECIFICATIONS

evolution

 

 

VOLTAGE MONITOR WITH PROTECTION

FOR THREE-PHASE LOADS AND

INTERNAL DATALOGGER

PHASELOGEV04-02T-17179

Control functions

shutdown

Functions

lockdown

Serial

programming

Protection

level

Datalogger

IP 65

FRONT

LOG

System

supervisor

<

<

and

V

er

.04

PhaseLog  

plus

e

5. INSTALLATION - ELECTRICAL CONNECTIONS

Connection 90 ~ 264V

Serial communication

RS-485

A

B

Power

supply

90 ~ 264Vac 

N

O

C

O

M

M

O

N

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

Connection 12Vdc

Star

Delta

Phase

Terminal connections

Connection Types

15

R

15

16 

S  

 17

T  

 14

N  

-

16 

 17

Three-phase Star

Single-phase

R

(Pin 15)

R

(Pin 15)

S

(Pin 16)

T

(Pin 17)

N

(Pin 14)

N

(Pin 14)

Phase R

Phase R

Neutral

Neutral

Phase S

Phase T

Three-phase Delta

T

(Pin 17)

R

(Pin 15)

S

(Pin 16)

Phase R

Phase T

Two-phase

R

(Pin 15)

N

(Pin 14)

 R

Phase

S

(Pin 16)

 S

Phase

Neutral

N

Phase

R

Phase

S

Phase

T

Phase monitoring

Load

Serial communication

RS-485

A

B

N

O

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

N

Phase

R

Phase

S

Phase

T

Phase monitoring

Load

C

O

M

M

O

N

5. INSTALLATION - ASSEMBLING

Panel (Front View)

Panel

(Side View)

Dimension of the clipping

for fixing of the 

instrument in panel

71 

 mm

± 0,5

29 

 mm

± 0,5 

ATTENTION

FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO 
AVOID LIQUID CONTACT, THE CUT FOR THE CONTROLLER 
MUST BE OF 70,5X29mm MAXIMUM. THE SIDE LOCKS MUST 
BE FIXED SO IT PRESSES THE RUBBER SEALING AVOIDING 
INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.

IMPORTANT

THE  USE  OF  APPROPRIATE  TOOLS  IS  ESSENTIAL  TO  AVOID 
DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:

SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE 
SIGNAL TERMINALS;
SCREWDRIVER  PHILLIPS  #1  FOR  ADJUSTMENTS  IN  THE 
POWER TERMINALS;

6. OPERATIONS

6.1 Quick access menu map

By pressing 

, it is possible to navigate through the function menus. For more details, see chapter 6.3. 

;

See the functions map below:

;

FUNCTIONS LOCKDOWN

;

CONTROL FUNCTIONS 
SHUTDOWN

 

PhaseLog

plus

 

PhaseLog

plus

DISPLAY MIN. AND MÁX.

;

 

PhaseLog

plus

CLEAR MIN. AND MÁX. VALUES

;

 

PhaseLog

plus

DISPLAY SELECTED 
VOLTAGE DURING 10 SEC.

;

 

PhaseLog

plus

FUNCTION SELECTION

;

DATE AND TIME SETTING

;

ON/OFF DATA LOGGER
(MANUAL MODE)

;

 

PhaseLog

plus

 

PhaseLog

plus

 

PhaseLog

plus

EXIT FUNCTION

;

 

PhaseLog

plus

+12 VDC

GND

Power

Power
supply

+

-

Power supply
Indirect supply

90 ~ 264 Vac (50/60 Hz)
12Vdc/350mA

Monitoring voltage range

90 to 600 VRMS (phase voltages)
90 to 600 VRMS (line voltages)

Monitoring frequency range

35 to 80 Hz

Frequency of sampling

7 Khz

Error  (25ºC)

< 1% of full scale range

Resolution

1 Vac in all range

Maximum Current

3A / 250Vac 

Operational Temperature

0 to 50°C

Operational Humidity

10 to 90% UR (without condensation)

Minimum delay to open load output 
relay in case of failure

1 s

Dimensions

76 x 34 x 77 mm (WxHxD)

Dimensions of the clipping for fixing
of the instrument

71 ± 0,5 x 29 ± 0,5 mm (see item 5)

/

 Hold down for 2 seconds: The current day, month, year, hour, and minute 

                                     will be shown in sequence on the display.

PhaseLog

e

 

plus

PhaseLog

e

 

plus

PhaseLog  

plus

e

Lower Key

Upper Key

Set Key

User-friendly
Menu Key

Phase R indication LED

Phase S indication LED

Phase T indication LED

Relay open/closed indication LED

Alarm indication LED

Connection Star indication LED

Connection Delta indication LED