9. OPTIONAL ITEMS - Sold Separately
9.1
EasyProg ver. 02
It is an accessory that has as its main function to store the parameters of the controllers. At any time, you
can load new parameters of a controller and unload them on a production line (of the same controller), for
example. It has three types of connections to load or unload the parameters:
- Serial RS-485:
It connects via RS-485 network to the controller (only for controllers that have RS-485).
- USB:
it can be connected to the computer via the USB port, using Sitrad's Recipe Editor. The parameters
can be copied, edited and saved in
EasyProg ver. 02
. The USB port can also have the function of
electrically feeding the
EasyProg ver. 02
and the controller (when the USB and Serial TTL are used
together).
9.2 Ecase
Protective cover for controllers (Evolution line), which prevents the entrance of water and inner moisture. It
protects the product when washing is carried out in the location where the controller is installed.
- Serial TTL:
The controller can be connected directly to
EasyProg ver. 02
by the TTL Serial connection.
Thus the
EasyProg ver. 02
may be fed by
PhaseLog
, or vice versa.
e
plus
9.4 Surge Protective Device (SPD)
Wiring diagram for instalation of SPD in
magnectic contactor
SPD
A1
A2
A1 and A2 are the terminals
of the contactor coil.
Wiring diagram for instalation of SPD in line
with loads
LOAD
For direct drive take in to
consideration the specified
maximum current.
9.3 Extension Frame
The Full Gauge Controls extension frame allows the installation of Evolution / Ri line with measures
76x34x77 mm (dimensions of the clipping for fixing in the extension frame is 71x29mm) in varied
situations, since it eliminates precision cut to embed the instrument. Allows customization via a sticker with
the brand and the company contact, and accompany two 10A (250 Vac) switches that can trigger internal
light, air curtain, on / off system or fan.
RC FILTER
EasyProg
ver. 02
Obs.1:
These errors are triggered if the respective measured voltage is outside the equipment's voltage
control range.
Obs.2:
These alarms are triggered if the respective measured voltage is smaller than the value specified
in
[,F07]
or greater than the value specified in
[,F08]
.
Obs.3:
Unable to find entry point in the datalogger to start to record data. In this case, it is recommended
to download all data from the datalogger before erasing it. To ignore the error and clear all records from
the datalogger, use the access code
[612,]
.
Obs. 4:
Controller's internal memory failed its self-test (send instrument for service).
8.1 Explanatory chart
Angular Asymmetry (F03)
Modular Asymmetry (F05)
Voltage
Time
Maximum voltage (F08)
Minimum voltage (F07)
R
S
T
Phase
Sequence (F02)
8. PARAMETERS ANALYZED
8.2 Detection alarms angular/modular asymmetry
S =
Sensibility (0 to 100%)
Modular asymmetry:
Tolerance = (100 - S) x (Average Measured voltages)
100
Angular asymmetry:
Tolerance = (100 - S) x (Average Measured phase difference)
100
Alarm activation condition: (both cases)
Measured value higher than average value + tolerance or Measured value lower than average value -
tolerance
RS-485
A - Orange
B - Red
- Brown
LEGEND
SPD
7. SIGNALLING
[E-R,]
[E-S,]
[E-T,]
[A-1,]
[A-2,]
[A-3,]
[A-4,]
[A-5,]
[A-6,]
[ECLO]
[OFF,]
[aDfl]
[EDTL]
[mem,]
[EMEM]
(flashing)
[pppp]
}
Obs. 1
Obs. 2
}
Obs. 3
}
Obs. 4
}
Error reading R phase voltage.
Error reading S phase voltage.
Error reading T phase voltage.
R phase voltage out of range alarm.
S phase voltage out of range alarm.
T phase voltage out of range alarm.
Angular asymmetry alarm.
Modular asymmetry alarm.
Incorrect phase sequence alarm.
Date and/or time invalid.
Control functions shutdown active (controller on standby).
Datalogger full alarm.
Datalogger error.
Memory error.
Reconfigure the values of the functions.
Initializing memory.
F18 - Force datalogger write on load output change:
If the datalogger has been activated and if the load output change its state, the
PhaseLog
e
plus
will
force a data recording in memory regardless of the sampling time set in
[,F16]
.
F19 - Overwrite old data on the Datalogger:
This parameter controls whether the controller should overwrite the old data in the datalogger once its
memory is full. This function prevents that the latest data evaluated by the equipment be lost.
F20 - Display preferential indication:
This parameter configures which voltage phase will be shown by default on the display:
[,,,0]
- R Phase voltage
[,,,1]
- S Phase voltage
[,,,2]
- T Phase voltage
[,,,3]
- Alternate the display of all phase voltages
F21 - Key pressed time to activate the functions lockdown:
This parameter controls how much time the user must press the
>
key to activate the functions
lockdown. Once activated, this functions protects the parameters against tampering, although the user
still will be able to visualize its parameters. To obtain further informations on how to activate/deactivate
the functions lockdown, see chapter 6.3.1 - Functions Lockdown.
F22 - Control functions shutdown:
This parameter enables/disables the load output switching off to perform maintenance. To obtain further
informations on how to activate/deactivate the Control functions shutdown, see chapter 6.3.2 - Control
functions shutdown.
F23 - Address in RS-485 network:
Instrument address on the network to communicate with SITRAD® software.
Note:
In the same network, there cannot be more than one instrument with the same address.