6.3.2 Control functions shutdown
If the Control Function Lockdown is active, the controller will operate only as a voltage indicator, while
leaving the output relay off.
This feature is managed by the function ‘‘
[,F22]
-
Control function shutdown’’
:
[,,no]
Control functions shutdown disabled
[,,,1]
Control functions shutdown enabled if the functions lockdown is not active
[,,,2]
Control functions shutdown always enabled
After the Control Functions Shutdown has been enabled, to activate it, the user must use the Quick menu
key and navigate it to
[Ctrl]
, then confirm the selection with the set key. After the user confirmed the
selection, the messages
[Ctrl]
[Off,]
are shown on the display. While the Control Functions
Lockdown is active, the controller will alternate the voltages of each phase with the message
[Off,]
.
To deactivate the Control Functions Shutdown, the user needs to use the same procedure as to activate
this feature: use the Quick menu key and navigate to
[Ctrl]
, then confirm the selection with the set
key.
After the selection confirmation, the messages
[Ctrl]
[On,,]
are shown on the display.
Note: After the Control Functions Shutdown deactivation (control functions re-enabled), the
PhaseLog
e
plus
will respect the delays set in the functions "
[,f13]
- Delay to enable load
output during controller startup" and "
[,F14]
- Minimum time to reactivate load output.
6.3.3 Minimum and maximum voltages visualisation
To visualize minimum and maximum voltages of each phase, press the key
<
(short touch). First the
message
[Uo-r]
is shown, afterwards its minimum and maximum voltages will be displayed. The
same applies to the voltages on phase S (
[Uo-S]
-> Min voltage -> Max voltage) and phase T
(
[Uo-T]
-> Min voltage - > Max voltage)
6.3.4 Voltages measured visualisation
To switch between the visualisation of the phase R, phase S or phase T, press
>
until the desired
information appears on the display. The selected voltage will be shown on the display for 15 seconds;
after this period the preferential indication will be exhibited (as adjusted in parameter
[,F21]
).
6.4 Advanced operations
6.4.1 Access to main menu
To access the main menu, press the keys
<
and
>
simultaneously. When the keys are released, the
following options will be displayed:
[Code]
- Access code input
[Func]
- Advanced parameters adjustment
[ClO,]
- Display/Adjust current date and time
6.4.2 Access code
To enter the access code, use the keys
<
and
>
; to confirm press the key
/
. To change any
parameter or to adjust the date and time, use the access code
[123,]
.
NOTE:
If the functions lockdown is active, the message
[LOC,]
will be displayed when the user tries to
insert the access code using the keys
<
or
>
.
6.4.3 Advanced parameters adjustment
To select the desired function, use the
<
and
>
keys. After selecting the function, press the
/
key
(short touch), to visualize its current value. If the correct access code has been entered, the user can
adjust the parameter value using the keys
<
and
>
; to store the value and return to the previous
menu, press the key
/
(short touch). To return to the previous menu without saving, press and hold the
key
/
until the message
[----]
is shown. In either case, to exit this menu and return to normal
operation (voltage indication), press and hold/until
[----]
appears.
NOTE:
If the functions lockdown is active or if the incorrect access code has been inserted, the message
[LOC,]
will be displayed when the user tries to adjust the value of any advanced parameter using the
keys
<
or
>
.
6.4.4 Setting date and time
When you select the
[ClO,]
menu, if the access code
[123]
has been inserted, the controller enters
the date and time adjstment mode. To change a value, use the keys
<
and
>
; when ready press
/
to
store the desired value. If the date inserted is invalid, the message
[ECLO]
will be displayed. You can
also set the date and time using the provided menu. In this case, it is not necessary to enter the access
code.
Example 1
(Correct access code has been inserted):
[,00d]
- day
[,00M]
- month
[,00Y]
- year
[00:00]
Number of phases in operation
Enables the detection of phase inversion
Sensitivity of the angular asymmetry
Time to validate angular asymmetry
Sensitivity of the modular asymmetry
Time to validate modular asymmetry
Minimum operating voltage
Maximum operating voltage
Time for validation of out of range voltage
Offset of R voltage indication
Offset of S voltage indication
Offset of T voltage indication
Delay to energize the controller
Time to reset the relay
Triggering the data logger
Time between each sample in memory
Changes in voltage to force the writing of data
Changes output state to force the writing of data
Overwrite the old data from the data logger
Preferential indication on the display
Time for functions lockdown
Control functions shutdown
Address in RS-485 network
[,F01]
[,F02]
[,F03]
[,F04]
[,F05]
[,F06]
[,F07]
[,F08]
[,F09]
[,F10]
[,F11]
[,F12]
[,F13]
[,F14]
[,F15]
[,F16]
[,f17]
[,f18]
[,F19]
[,F20]
[,F21]
[,F22]
[,F23]
Description
Fun
Min
Max
Unit.
Standard
1
0-no
0
0
0
0
90
90
0
-20
-20
-20
0
0
0
5
3
0-no
0-no
0
no
no
1
6.5 Parameters table
-
-
-
sec.
-
sec.
Vac
Vac
sec.
Vac
Vac
Vac
sec.
sec.
-
sec.
Volts
-
-
-
sec.
-
-
4
1-yes
80
5
80
5
90
600
5
0
0
0
0
5
1
300
[OFF,]
0-no
1-yes
3
no
no
1
4
1-yes
100
30
100
30
600
600
30
20
20
20
999
999
2
999
[OFF,]
1-yes
1-yes
3
60
2
247
hour
minute
flashing
Legend:
[yes,]
= yes
[no,,]
= no
6.5.1Parameters description
F01 - Number of phases in operation:
This parameter configures which phases will be monitored by the instrument:
[,,,1]
- Only the R phase (used in single-phase connections)
[,,,2]
- R and S phases (used in two-phase connections)
[,,,3]
- R, S and T phases (used in three-phase star connections)
[,,,4]
- R, S and T phases (used in three-phase triangle connections)
F02 - Detection of phase inversion:
This parameter enables/disables the phase sequence monitoring. If this function is enabled and a phase
has been inverted, the output relay will remain open and an alarm will be set, thereby protecting the load
against possible phase inversions.
Note:
Protection against phase inversion is only available if
[,F01]
is set to the value 3 or 4.
F03 - Angular asymmetry sensitivity:
This parameter adjusts the sensitivity with which the
PhaseLog
e
plus
will detect phase angle
asymmetries. The higher the value of this parameter, the lower will be the tolerance against this
error. If you wish to disable this monitoring, simply set the function with the value 0.
The equation to determine the detection limits of the alarm is presented in chapter 8.2 - Detection of
angular / modular asymmetry alarms. It should be noted that the limits to indicate angular asymmetry
error are given by "mean of the lags + tolerance" and "mean of the lags - tolerance". In this way, it is
important to note that the alarm detection limit depends on the current values of each measured
phase. To illustrate, knowing that the phase difference between two voltage phases in a three-phase
system is ± 120 ° and the total sum of the phase-shifts is equal to 360 °, if the function is set to the
value
[,f03]
= 80, then we have:
- Upper limit: the alarm will be triggered when the angular mismatch is greater than 144º.
- Lower limit: the alarm will be triggered when the angular mismatch is less than 96º.
F04 - Time to validate angular asymmetry:
Time in seconds that the three-phase monitor waits to validate the angular asymmetry error.
F05 - Modular asymmetry sensitivity:
On this parameter the user can adjust the sensitivity with which
PhaseLog
e
plus
will detect the
phase asymmetry of the phases set in
[,f01]
. The higher the value of this parameter, easier the
controller will detect the error. If you wish to deactivate this monitoring, simply set the function to
00.0.
The equation for determining the detection limits of the alarm is presented in chapter 8.2 - Detection
of angular / modular asymmetry alarms. It should be noted that the limits to indicate modular
asymmetry error are given by "mean of the vo tolerance" and "mean of the voltages -
tolerance". In this way, it is important to note that the alarm detection limit depends on the current
values of each measured phase.
For example, considering that the function is set to the value
[,F05]
= 80 and that the voltages of
the phases R and S are equal to 220 V
RMS
, then:
- Upper limit: the alarm will be triggered when the phase T voltage is higher than 293 V
RMS
, because
it will be higher than the mean of the measured values (244 V
RMS
) plus the calculated tolerance (48
V
RMS
).
- Lower limit: the alarm will be triggered when the phase T voltage is less than 159 V
RMS
, because it
will be less than the average of the measured values (199 V
RMS
) less the calculated tolerance (39
V
RMS
).
F06 - Time to validate modular asymmetry:
Time in seconds that the three-phase monitor waits to validate the modular asymmetry error.
F07 - Minimum operating voltage:
Minimum voltage threshold to trigger the out-of-range alarm and open the load relay.
F08 - Maximum operating voltage:
Maximum voltage threshold to trigger the out-of-range alarm and open the load relay.
F09 - Time for validation of out of range voltage:
Time in seconds that the three-phase monitor waits to validate the out of range voltage alarms
(
[,F07]
/
[,F08]
).
Note:
If there is any error in the voltage reading (
[E-t,]
,
[E-r,]
or
[E-s,]
active), this function is
ignored, therefore the output is disabled immediately.
F10 - Offset of R voltage indication:
This parameter lets you adjust the R phase voltage indication offset.
F11 - Offset of S voltage indication:
This parameter lets you adjust the S phase voltage indication offset.
F12 - Offset of T voltage indication:
This parameter lets you adjust the T phase voltage indication offset.
F13 - Delay to energize the controller:
Time in seconds in wish the
PhaseLog
e
plus
will wait before triggering its output.
F13 - Delay to enable load output during controller startup:
Time in seconds that the
PhaseLog
e
plus
will wait before activating its load output during startup.
F14 - Minimum time to reactivate load output:
Time in seconds that the
PhaseLog
e
plus
will wait before reactivating its load output once it has
been deactivated.
F15 - Data logger operating mode:
This parameter controls the datalogger operating mode:
[,,,0]
- Always off
[,,,1]
- Always on
[,,,2]
- Manual operation
F16 - Datalogger sample period
Period of time in seconds between each voltage sample stored in the controller's datalogger.
F17 - Force datalogger write on voltage change
If the datalogger has been activated and if any monitored voltage suffers a change greater than ou equal
to the value set in this parameter, the
PhaseLog
e
plus
will force a data recording in memory
regardless of the sampling time set in F16. This functions is evaluated once per second. This function
can be set from 3 to 50 volts; to deactivate it, press the
<
key until the
[Off,]
message appears on
the display.
NOTICE:
The controller is equipped with a an auxiliary internal power supply in order to keep its date and time in the case
of an energy shortage.A fully charged battery can provide enough energy to keep the time and date running for
some weeks. If the controller remains turned off for a prolonged period of time, it will display the
message
[ECLO]
; in this case the controller's date and time has been lost due to low battery and the user must
adjust it again. To completely recharge a dischaged battery, keep the controller turned on for at least 5 hours.