Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
101
Procedure for compressor installation
Reverse procedure to removing the compressor.
Precautions for installation of compressor.
1 When brazing, do not apply the flame on the terminal.
2 When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Thermistor (Discharge)
Thermistor (comp. Temp.)
Cut the binder, and remove
the heat insulation.
Remove the Thermistor (Discharge).
Remove the Thermistor (comp. temp.)
and the Thermistor (Discharge).
Remove the COMP BOLTS.
(3 places)
Cut the Discharge pipe in this range
Range
Range
Range
Cut the Suction pipe in this range. Cut the Injection port in this range
Keep their shape better.
There is a possibility of catching fire to oil when removing by the welding without cutting it.
Range
screw
Remove the 2 mounting screws.
Remove this place, and remove
COMPRESSOR with
ACCUMULATOR.
Single-Phase type