Split system (Single phase and 3-phase type)
Maintenance Document
1544-1
35
2.3 Sensor
Values
2.3.1
Outdoor Unit Temperature Sensors
Outdoor Heat Exchanger (outlet), Outdoor Heat Exchanger (middle)
Temperature (°C)
-10
-5 0 10 15 20 25 30
Resistance value (k
)
27,5
20,9 16,1 12,4 9,73 7,67 6,1 3,95
Outdoor Discharge Pipe / Compressor / Expansion valve inlet
Temperature (°C)
0
5 10 15 20 30 40 50 60
Resistance value (k
)
168
130 101 79 63 40 26,3
17,8 12,3
Temperature (°C)
70
80 90 100 120
Resistance value (k
)
8,7
6,3 4,6 3,4 2
Outdoor Temperature
Temperature (°C)
-20
-10 -5 0 5 10 15 20 30
Resistance value (k
)
115
62,3 46,6 35,2 26,9 20,7 16,1 12,6 7,97
Temperature (°C)
40
50 60 70
Resistance value (k
)
5,18
3,45 2,36 1,65
Heat sink
Temperature (°C)
0
5 10 15 20 30 40 50 60
Resistance value (k
)
15,8
12,2 9,5 7,5 5,9 3,78 2,50 1,69 1,17
Temperature (°C)
70
80 90 100 110 120
Resistance value (k
)
0,83
0,60 0,44 0,33
0,25
0,19
2.3.2 Hydraulic
Unit
Temperature Sensors
Heat Exchanger (Condensing sensor)
Temperature (°C)
0
5 10 15 20 25 30 35 40 45 50
Resistance value (k
)
176 134 103 80,3 62,9 49,7 39,6 31,7 25,6 20,8 17,1
Outdoor sensor
Temperature (°C)
-20
-15 -10 -5 0 5 10 15 20
Resistance value (k
)
7,60
5,85
4,60
3,60 2,85 2,30 1,85 1,50 1,20
Temperature (°C)
25
30 35 40 45
Resistance value (k
)
1
0,83 0,70 0,58 0,48
Heat pump flow and return sensor – DHW and heating zone 2 sensor – Swimming pool return sensor
Temperature (°C)
-15
-10 -5 0 5 10 15 20 25
Resistance value (k
)
72,5
55 42 32,5 25 20 15,7
12,5 10
Temperature (°C)
30
35 40 45 50 55 60 65 70
Resistance value (k
)
8
6,5 5 4 3,5
3 2,5
2 1,7